Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Request for Inspection

(RFI)

Project BATU HIJAU CCPP-1 RFI No. BHCP1-JEL-RFI-C00-Z0094

Subcontractor JEL / PT JEL Request Date 09-Mar-23

Discipline Civil Inspection Date 10-Mar-23 Time 10:00 AM

Location Koboi Benete & Mataram Lab System Concrete Design Trial Mix

ITP No. BHCP1-00-YYY-QP-Q-0002 Rev. B


ITP 2.4 Concrete Compressive strength test
Description
ITP Step No. 2.0

Inspection Point JEL H OE W Owner W

No. Inspection Object Quantity Remarks

Inspection for the 3 day old compressive strength test of


concrete cylinder at Koboi Benete & Mataram Laboratory to the
1 following samples of concrete grade:
1) C35 N/mm2 Imprv-A (N.M, T-5 Cement) slump: 120 ±20 mm
2) C35 N/mm2 Imprv-A (P.M, T-5 Cement) slump: 120 ±20 mm

No. Drawing No. Rev.

1 Concrete mix design

Comments

Accepted □ Accepted with comments □ Rejected □ Cancelled □


Name / Signature / Date

Subcontractor Contractor OE Owner Other Discipline


Form Number: BHCP1-00-YYY-PR-Q-0003-02A
-02A Rev.2
PT SUMBAWA APSARA BETON
KONCRETE KOBOI
Jl. Lintas Samota Km.6, Kelapis, Kel. Brang Biji, Kec. Sumbawa
Kabupaten Sumbawa, NTB

MIX PROPORTION DATA SHEET

Record No. : 010/TM/KK-JEL/XII/2022.


Project : Batu Hijau Combined Cycle Power Plant
Contractor : PT Jurong Engineering Lestari
Location : Batu Hijau, Kabupaten Sumbawa Barat, NTB

Concrete Strength : 35 N/mm2


Max Slump : 120 ± 20 mm
(Normal Mix) Imprv. A
Size of Coarse Aggregates : 20 mm (max)

Mix Proportion for 1 m3 concrete (SSD condition)

SG Weight Volume
Material Type Remarks
(kg/m3) (kg) (m3)

Cement Type V 3000 385 0.13 Semen Indonesia


Water 998 160 0.16 Loc : West Sumbawa
Coarse Aggregate 2720 765 0.28 Loc : West Sumbawa
Fine Aggregate 2600 1105 0.43 Loc : West Sumbawa

SG Weight Volume
Material Type Remarks
(kg/L) (kg) (L)
Admixture (Retarder) Type D 1.20 2.31 1.93 Ex : Nexco
Admixture (Superplasticiser) Type F 1.10 3.47 3.15 Ex : Nexco

Total Volume (m3) 1.00


Concrete Density (kg/m3) 2420.8
W/C 0.42
Sand/Aggregate 59%

*OPC T5 - Trial will do using Production Scale

Note :
Refer to ACI 318R-2019, ACI 211
Prior to Production Scale Trial Mix, the composition shall be adjusted and optimized for best results as required.
Mix Design will be continously adjusted & optimized along the project based on actual onsite condition.

Sumbawa, January 8th, 2023.


PT Sumbawa Apsara Beton

(Muhammad Ridwan Siregar)


PT SUMBAWA APSARA BETON
KONCRETE KOBOI
Jl. Lintas Samota Km.6, Kelapis, Kel. Brang Biji, Kec. Sumbawa
Kabupaten Sumbawa, NTB

MIX PROPORTION DATA SHEET

Record No. : 011/TM/KK-JEL/XII/2022.


Project : Batu Hijau Combined Cycle Power Plant
Contractor : PT Jurong Engineering Lestari
Location : Batu Hijau, Kabupaten Sumbawa Barat, NTB

Concrete Strength : 35 N/mm2


Max Slump : 120 ± 20 mm
(Pump Mix) Imprv. A
Size of Coarse Aggregates : 20 mm (max)

Mix Proportion for 1 m3 concrete (SSD condition)

SG Weight Volume
Material Type Remarks
(kg/m3) (kg) (m3)

Cement Type V 3000 385 0.13 Semen Indonesia


Water 998 160 0.16 Loc : West Sumbawa
Coarse Aggregate 2720 700 0.26 Loc : West Sumbawa
Fine Aggregate 2600 1167 0.45 Loc : West Sumbawa

SG Weight Volume
Material Type Remarks
(kg/L) (kg) (L)
Admixture (Retarder) Type D 1.20 2.31 1.93 Ex : Nexco
Admixture (Superplasticiser) Type F 1.10 3.47 3.15 Ex : Nexco
Ex : Normet
Total Volume (m3) 1.00
Concrete Density (kg/m3) 2418.0
W/C 0.42
Sand/Aggregate 63%

*OPC T5 - Trial will do using Production Scale

Note :
Refer to ACI 318R-2019, ACI 211
Prior to Production Scale Trial Mix, the composition shall be adjusted and optimized for best results as required.
Mix Design will be continously adjusted & optimized along the project based on actual onsite condition.

Sumbawa, January 8th, 2023.


PT Sumbawa Apsara Beton

(Muhammad Ridwan Siregar)