Low voltage products

Cable current transformers


types: KOLMA, KOLA, KOKM, KORI, KOLT
2 Cable current transformers
Index

Transformers for residual current measurement


KOLMA, KOLA ............................................................................................................. 4
How to select the correct residual current transformers ............... 4
Technical data ............................................................................................................ 4
Installation ..................................................................................................................... 4
Ordering data ............................................................................................................. 6
Overall dimensions ................................................................................................. 7
Indoor cable current transformers
KOKM ................................................................................................................................. 8
Technical data ............................................................................................................ 8
Ordering data .......................................................................................................... 10
Overall dimensions .............................................................................................. 12
KOKM (for ZX panels) ........................................................................................... 17
Technical data ......................................................................................................... 17
Overall dimensions .............................................................................................. 19
KOKM (for RMU) ...................................................................................................... 28
Electrical parameters ......................................................................................... 28
Terminal marking ................................................................................................... 29
Overall dimensions, connection diagram ............................................. 30
Indoor special current transformer
KORI ................................................................................................................................. 33
Technical data ......................................................................................................... 33
Overall dimensions .............................................................................................. 34
Current transformers for oil-immersed transformers
KOLT ................................................................................................................................ 35
Technical data ......................................................................................................... 35
Overall dimensions .............................................................................................. 37

Cable current transformers 3


Transformers for residual current measurement
types KOLMA, KOLA

KOLMA_ and KOLA_ cable current transformer are used to Table 2. Technical data
measure the sum of 3-phase currents in a 3-phase cable. Under Rated voltage 0.72 kV (1)

normal operating conditions this sum is zero. In the event of an Insulation test voltage 50 Hz 1 min 3 kV (IEC 60044-1)
earth-fault it is equal to the earth-fault current and a corresponding Frequency 50 Hz (60 Hz)
current flows in the secondary winding. Rated thermal current 1.2 x I pn
These transformer types are used together with static earth-fault Short-time withstand current Ith 1 s 60 x Ipn (2)

relays, and as well as measuring residual current, for example, Peak withstnad current Idyn 2.5 x Ith
they can be used to prewarn of, or locate an earth-fault. An Secondary terminals for 6 mm2 conductor
busbar or cable serves as the primary conductor. Operating temperature range –25 ... +40°C
Conformity with standards IEC 60044-1
How to select the correct residual current transformers (1) The insulation level of the primary conductor determines the maximum operating
The transformer for an earth-fault relay is selected according to voltage.
(2) KOLA 06 B2 is type tested for 10 kA 3 s.
dimension of the window and construction of the transformer.
For types KOLMA 06 A1, and KOLMA 06 D1, the number of turns
used in the secondary winding is selected according to the relay The primary winding of indoor type cable current transformers is
setting value and the earth-fault current or the required current either a cable or a busbar, which is insulated for the application
ratio. In addition correct functioning of the earth-fault protection voltage. The secondary winding and ring shaped iron core is cast
relays for KOLMA 06 A1 and KOLMA 06 D1 is easy to test by in resin which has good electrical and mechanical properties.
means of the transformer test winding (terminals P1x - P2x). The
test winding is rated for 6 A maximum continuous current. Installation
The KOLMA-type transformers must be installed before the cables
Table 1. Selection of residual current transformers and cable terminations are connected.
Type Window Construction Weight With the KOLA 06 B2 and KOLA 06 D2 types, the ring core can
diameter [mm] [kg] be opened and the transformer installed even though the cable is
KOLMA 06 A1 90 Ring core, multi-tap secondary 7.0 already connected. The two halves of the ring core are tightened
KOLMA 06 A2 58 Ring core 2.9 together with four screws, which also guide the halves to the cor-
KOLMA 06 B2 100 Ring core 5.4 rect position. The secondary winding is distributed over both
KOLMA 06 D1 180 Ring core, multi-tap secondary 11.5 halves of the core. The two sections of the winding are joined
KOLMA 06 D2 180 Ring core 11.4 together with two connecting pieces.
KOLA 06 B2 100 Split ring core 6.0 Cable current transformers are fastened either by means of the
KOLA 06 D2 180 Split ring core 11.0 fixing base or by the nuts cast into the transformer frame. When

4 Cable current transformers


installing the transformer, the effect of the current on the metal
armour or in the protective conductor must be eliminated.
In case the metal armour or the protective conductor is drawn
through the transformer, the earthing conductor must be drawn
back through the transformer for earthing. The earthing conductor
between the cable termination box and the transformer must not
be connected to conductive structures, and the metal cable termi-
nation box must be insulated from the supporting structures.
On a multi-ratio transformer the unconnected secondary winding
terminals and test winding must not be short circuited.

Number of turns and terminal markings

#ABLE
0 0
+/,-!  !
+/,-!  $      Openable residual current transformers, type (KOLA 06 B2) complete
3 3 3 3 3 0X 0X with fixing base KOLMA-ZK 1 and terminal cover KOK-ZAX 14.

+/,-!  ! 4ESTWINDING
#ABLE
+/,-!  "
+/,-!  $ 0 0
+/,!  "
+/,!  $ 
3 3

Table 3. Current ratios and rated burdens for accuracy class


10P10
Current Secondary Burden/VA Type
ratio [A] terminals KOLMA 06 A1 KOLMA 06 D1
50/1 S4 - S5 1.0 0.5
70/1 S3 - S4 2.0 1.0
100/1 S1 - S4 2.5 2.0
150/1 S1 - S5 5.0 4.0
50/5 S1 - S2 1.0 0.5
100/5 S2 - S3 2.5 1.5
150/5 S1 - S3 4.0 3.0
250/5 S4 - S5 7.5 5.0
350/5 S3 - S4 10.0 7.5
500/5 S1 - S4 15 10
600/5 S3 - S5 20 15
750/5 S1 - S5 20 15

Cable current transformers 5


Table 4. Standard technical parameters for KOLMA_ and KOLA_
Type Primary Secondary Accuracy Burden Dimensions
current [A] current [A] class [A] [VA] inner [mm] outer [mm] height [mm]
KOLMA 06 A2 100 1 10P10 2 58 140 65
KOLMA 06 B2 100 1 10P10 2 100 196 65
KOLMA 06 D2 100 1 10P10 2 180 270 80
KOLA 06 B2 50 1 10P10 0.5 100 228 85
KOLA 06 B2 100 1 10P10 2 100 228 85
KOLA 06 B2 200 1 10P10 4 100 228 85
KOLA 06 B2 200 5 10P10 4 100 228 85
KOLA 06 B2 400 5 5P10 5 100 228 85
KOLA 06 B2 500 5 5P20 2.5 100 228 85
KOLA 06 B2 600 1 10P10 2 100 228 85
KOLA 06 B2 1,250 1 5P20 5 100 228 85
KOLA 06 B2 1,500 1 5P10 2.5 100 228 85
KOLA 06 B2 1,600 5 1 20 100 228 85
KOLA 06 D2 50 1 10P10 0.5 180 315 85
KOLA 06 D2 100 1 10P10 2 180 315 85
KOLA 06 D2 150 1 10P10 2 180 315 85
KOLA 06 D2 200 1 10P10 5 180 315 85
KOLA 06 D2 200 5 10P10 2 180 315 85
KOLA 06 D2 300 1 10P10 5 180 315 85
KOLA 06 D2 400 1 10P10 5 180 315 85
KOLA 06 D2 400 5 5P10 5 180 315 85
KOLA 06 D2 1,000 1 5P10 10 180 315 85
KOLA 06 D2 1,800 5 1 20 180 315 85
KOLA 06 J2 50 1 10P10 0.5 300 x 497 410 x 610 90
KOLA 06 J2 100 1 10P10 1 300 x 497 410 x 610 90
KOLA 06 J2 1,250 1 5P20 5 300 x 497 410 x 610 90
KOLA 06 J2 1,250 5 10P10 1 300 x 497 410 x 610 90

If other electrical parameters other than those given in the tables are required please contact our sales department.

Warranty Ordering data


A two-year warranty period is granted from the date the trans- The order should contain the following data:
former starts to operate. However, a maximum warranty period – Type of current transformer
of three years is granted from the time of purchase. The warranty – Rated primary current/rated secondary current [A/A]
only covers manufacturing defects and does not include defects – Rated burden and accuracy class for each winding [VA]
due to: – Short-time thermal current Ith
– Incorrect transport – Standard
– Incorrect storage – Quantity
– A failure to follow instructions correctly during installation and
operation Order example
– Incorrect selection of the transformer for the electric power KOLA 06 B2; 100/1 A/A; 2 VA; 10P10; Ith = 60xIpn/1s; IEC
system 60044-1; 12 Pcs.

6 Cable current transformers


Overall dimensions

KOLMA 06 A1 KOLMA 06 A2, B2

Weight: app. 7,5 kg Type Dimensions [mm] Weight


A B C D [kg]
KOLMA 06 A2 177 86 140 58 4,7
KOLMA 06 B2 229 112 195 100 8,5
KOLMA 06 D1, D2

Weight: app. 13 kg
Cable current transformers 7
KOLA 06 B2 KOLA 06 D2

Weight: app. 8 kg Weight: app. 12,5 kg

KOLA 06 J2

Weight: app. 32 kg

8 Cable current transformers


Indoor cable current transformers
type KOKM

KOKM_ current transformers are suitable for measuring phase


currents. A busbar or cable serves as the primary conductor. Se-
ries KOKM current transformers can also be used for measuring
the phase current at voltages higher than 0.72 kV (for KOKM 06)
or 1.2 kV (for KOKM 1), if the insulation of the primary conduc-
tor satisfies the requirements of the respective standards for the
operating voltage. The secondary winding and ring shaped iron
core are cast in resin which has good electrical and mechanical
properties.

Table 6. Technical data


Transformer type KOKM 06_ KOKM 1_
Rated voltage Um [kV] 0.72 (1) 1.2 (1)

Power frequency test voltage Up (1 min) [kV] 3 6


Lighting test voltage Upp [kV] - -
Frequency fn [Hz] 50 or 60
Max. primary current Ipn [A] 50 ÷ 2,000 50 ÷ 10,000
Rated secondary current I sn [A] 1 or 5
Rated thermal current Icont [A] 1.2 x I pn (2)

Short-time withstand current Ith (1 s) [kA] 60 x Ipn ( Max. 100 kA)


Peak withstand current I dyn [kA] 2.5 x I th (Max. 250 kA)
Secondary terminals for 6 mm 2 conductor
Operating temperature range [°C] -25 … +40
Transport and storage [°C] -40 … +55
Electrical standards IEC, VDE, ANSI, BS, AS, CAN
(1) The insulation level of the primary conductor determines the maximum operating voltage.
(2) Max. Icont for KOKM 06 Icont = 2 400 A, for KOKM 1 Icont= 10 000 A.

Cable current transformers 9


Table 7. Standard parameters for KOKM 1_
Type Current Accuracy class Burden Dimensions
primary [A] secondary [A] [VA] inner [mm] outer [mm] height [mm]
KOKM 1 BC10 200 5 5P20 5 42 148 100
KOKM 1 DC8 100 1 10P10 2 60 148 80
KOKM 1 DF12 100 5 0.5 3 60 186 120
KOKM 1 DC6 150 1 5P20 1 60 148 60
KOKM 1 DC14 150 5 5P10 10 60 148 140
KOKM 1 DC12 300 5 5P10 15 60 148 120
KOKM 1 DC16 400 5 5P20 10 60 148 160
KOKM 1 DH10 5,000 5 1 10 60 200 100
KOKM 1 EC8 100 1 5P20 1 70 148 80
KOKM 1 EF16 100 1 0.5 1 70 186 160
KOKM 1 EC8 150 1 5P20 1 70 148 80
KOKM 1 EC6 200 1 5P20 1 70 148 60
KOKM 1 EC16 250 1 5P10 20 70 148 160
KOKM 1 EH16 250 1 5P20 20 70 200 160
KOKM 1 EC10 400 1 5P10 10 70 148 100
KOKM 1 EF14 400 1 5P20 20 70 186 140
KOKM 1 FC6 50 5 10P10 0.5 85 148 60
KOKM 1 FC16 300 5 5P10 10 85 148 160
KOKM 1 FC8 600 5 0.5 15 85 148 80
KOKM 1 FC12 600 5 0.5 50 85 148 120
KOKM 1 FC8 1,000 5 0.5 50 85 148 80
KOKM 1 GF6 50 5 10P10 0.5 90 186 60
KOKM 1 GF8 1,000 5 0.5 50 90 186 80
KOKM 1 GF6 1,500 5 0.5 50 90 186 60
KOKM 1 HF8 50 1 10P10 1 100 186 80
KOKM 1 HF8 50 5 10P10 1 100 186 80
KOKM 1 HH16 50 5 10P10 5 100 200 160
KOKM 1 HF12 100 1 10P20 2 100 186 120
KOKM 1 HK10 150 1 5P10 10 100 250 100
KOKM 1 HK10 200 1 5P10 10 100 250 100
KOKM 1 HK10 250 5 5P20 10 100 250 100
KOKM 1 HK10 300 5 5P20 10 100 250 100
KOKM 1 HK14 400 1 5P20 30 100 250 140
KOKM 1 HF6 400 5 10P10 5 100 186 60
KOKM 1 HF6 500 1 1 15 100 186 60
KOKM 1 HJ8 2,000 1 5P20 30 100 235 80
KOKM 1 KH8 50 1 10P10 1 120 200 80
KOKM 1 KH8 50 5 10P10 1 120 200 80
KOKM 1 KH18 200 5 5P20 5 120 200 180
KOKM 1 KH18 300 5 5P20 10 120 200 180
KOKM 1 KH10 1,000 1 5P10 20 120 200 100
KOKM 1 KH8 1,000 5 5P20 10 120 200 80
KOKM 1 KH8 1,500 5 0.5 50 120 200 80
KOKM 1 KH8 2,000 5 0.5 50 120 200 80
KOKM 1 KK10 2,500 5 5P20 10 120 250 100
KOKM 1 NK8 50 1 10P10 1 155 250 80
KOKM 1 NK12 50 1 10P10 2 155 250 120
KOKM 1 NK20 50 1 10P10 5 155 250 200
KOKM 1 NL14 50 1 10P10 5 155 270 140
KOKM 1 NL8 3,000 1 5P20 5 155 270 80
KOKM 1 RL12 50 1 10P10 2 180 270 120
KOKM 1 RL8 100 1 5P10 1 180 270 80
KOKM 1 RL12 100 1 5P10 5 180 270 120
KOKM 1 RL8 150 1 10P10 2 180 270 80
KOKM 1 RL20 300 5 5P20 10 180 270 200
KOKM 1 UT10 50 1 10P10 5 250 450 100
KOKM 1 UP16 100 5 10P10 5 250 340 160

The Parameters depend on the transfomer type (size); generally, the bigger the current transformer, the higher the technical parameters.
If other electrical parameters other than those given in the tables are required please contact our sales department.

10 Cable current transformers


Ordering data
The order should contain the following data:
– Type of current transformer
– Rated primary current/rated secondary current [A/A]
– Rated burden and accuracy class for each winding [VA]
– Short-time thermal current Ith
– Dimension of the window [mm]
– Standard
– Quantity

Order example
KOKM 1 FC 8; 600/5 A/A; 10 VA; 0.5; Ith = 60xIpn/1s;
IEC 60044-1; 9 Pcs.

Terminal markings

P1 P2

KOKM 1 NK 10
S1 S2
one secondary winding example: 100/1 [A/A]

P1 P2

S1 S2 S3
multi-tap secondary winding example: 50-100/1 [A/A]

P1 P2

1S 1 1S 2 2S 1 2S2
two secondary windings example: 800/5/5 [A/A/A]

Warranty
A two-year warranty period is granted from the date the trans-
former starts to operate. However, a maximum warranty period
of three years is granted from the time of purchase. The warranty
only covers manufacturing defects and does not include defects
due to:
– Incorrect transport
– Incorrect storage
– A failure to follow instructions correctly during installation and
operation
– Incorrect selection of the transformer for the electric power
system

Cable current transformers 11


Table 8. KOKM 1_
Outer Hole diameter [mm] Drawing Casting Total Hole center
diameter A B D E F G H K N R S U W X Y Z height height height
[mm] 33 42 60 70 85 90 100 120 155 180 200 250 350 400 450 500 [mm] [mm] [mm]
C 148 60 60 60 60 60 KOKM 1_C_ 183 249 112
160 160 160 160 160
F 186 60 60 60 60 60 60 60 Range of transformer width KOKM 1_F_ 213 279 131
160 160 160 160 160 160 160
H 200 80 80 80 80 80 80 80 80 KOKM 1_H_ 235 301 138
180 180 180 180 180 180 180 180
J 235 80 80 80 80 80 80 80 80 KOKM 1_J_ 265 331 158
300 300 300 300 300 300 300 300
K 250 80 80 80 80 80 80 80 80 80 KOKM 1_K_ 275 341 158
200 200 200 200 200 200 200 200 200
L 270 80 80 80 80 80 80 80 80 80 80 80 KOKM 1_L_ 297 363 158
200 200 200 200 200 200 200 200 200 200 200
M 280 80 80 80 80 80 80 80 80 80 80 80 KOKM 1_M_ 297 363 158
240 240 240 240 240 240 240 240 240 240 240
P 340 80 80 80 80 80 80 80 80 80 80 80 KOKM 1_P_ 379 445 204
200 200 200 200 200 200 200 200 200 200 200
T 450 80 80 80 80 80 80 80 80 80 KOKM 1_T_ 465 513 225
200 200 200 200 200 200 200 200 200
W 590 80 80 80 80 80 80 80 80 80 80 80 KOKM 1_W_ 605 653 300
200 200 200 200 200 200 200 200 200 200 200

Example

KOKM 1 D C 10
Transformers width
10 = 100 mm (possibility – 6, 8, 10, 12, 14, 16, 18, 20, 22, 24,... 30)

Outer diameter
C = 148 mm

Hole diameter
D = 60 mm

Rate voltage 1 = 1.2 kV

Type KOKM – indoor use


(Type KOKU – outdoor use)

12 Cable current transformers


Overall dimensions

KOKM 1_C_ KOKM 1_F_


124
52

20
20

11

B±2 (10 0 0...160)


B ±2 (120...160)

C
40
B ±2 (60...10 0)

B±2 (60...80)

40
11
80 52
1
M6 113 140
M5 18,5
1
113 80
18,5

M6
M5 18,5
23

18,5
6

23
P1

6
40 P1
40
236 ±3
183 ±2

+2
Di
0

266 ±3

213 ±2
+3 0

Di
112 ±2

P1 P2
P1 P2

131 ±2
186
14

M8 S1 S2
18

14
S1 S2

18
M8
148
170
KOKM 1 _ C __ KOKM 1 _ F __
Di = 33 42 60 70 85
Di = 33 42 60 70 85 90 100
A B D E F A B D E F G H

6 8 10 12 14 16 6 8 10 12 14 16
B = 60 80 100 120 140 160
C= 80 100 120 Note: B= 60 80 100 120 140 160 Note:
1) KOKM 1_C6 without the cover C= 60 80 100 120
1) KOKM 1_F6 without the cover

KOKM 1_H_ KOKM 1_J_


B±2 (10 0...180)

80
B±2 (80)

18,5
40
11

18,5

52
6

140 80

M6 18,5
113
18,5

M5
23

P1 40
288 ±3

+30
235±2

Di

P1 P2
138 ±2

200

M8 S1 S2
14
18

170

KOKM 1 _ H _
Di = 33 42 60 70 85 90 100 120 N
A B D E F G H K

8 10 12 14 16 18

B= 80 100 120 140 160 180


C= 60 80 100 120 140

Cable current transformers 13


Overall dimensions

KOKM 1_K_ KOKM 1_L_

20
20

14
14

B±2
B ±2

C
C

40
40
150
150
246
246
113 80
M6 18,5
80 M5
113

18,5
M6 M5 18,5

23

6
18,5
P1

23
40

6
P1
40

P1 P2

350 ±3

297 ±2
+3
Di
0
328±3

S1 S2
275±2

+3
Di
0

158 ±2
0
270 -2
158 ±2

15
18
0
250 -2
M8
270
15

P1 P2
KOKM 1 _ L _
18

Di = 33 42 60 70 85 90 100 120 155 180 200


M8 S2
A B D E F G H K N R S
S1
270
8 10 12 14 16 18 20

B = 80 100 120 140 160 180 200


KOKM 1 _ K _ C = 40 60 80 100 120 140 160
Di = 33 42 60 70 85 90 100 120 155
A B D E F G H K N

8 10 12 14 16 18 20
B = 80 100 120 140 160 180 200
C = 40 60 80 100 120 140 160

KOKM 1_M_ KOKM 1_P_

80

18,5
18,5

14 Cable current transformers


Overall dimensions

KOKM 1_T_ KOKM 1_W_

80 80

18,5 18,5

18,5
18,5

23
23

6
6
40 40

Note: Note:
Without base. Fix directly to Without base. Fix directly to

Table 9.
Standard parameters for KOKM 06 J_ (window type) f = 50 Hz
Type Window Primary Secondary Accuracy Burden
[mm] current current class [VA]
[A] [A]
KOKM 06 J2 300x500 50 1 10P10 1
KOKM 06 J2 300x500 50 5 10P10 0.5
KOKM 06 J2 300x500 100 1 10P10 2
KOKM 06 J2 300x500 100 5 10P10 1
KOKM 06 J2 300x500 150 1 10P10 2
KOKM 06 J2 300x500 300 5 10P10 1
KOKM 06 J2 300x500 500 1 5P10 10
KOKM 06 J2 300x500 600 5 10P10 5
KOKM 06 J2 300x500 800 5 0.5 15
KOKM 06 J21 150x500 50 1 10P10 1
KOKM 06 J21 150x500 100 5 10P10 1
KOKM 06 J21 150x500 700 1 5P10 3
KOKM 06 J21 150x500 2,000 1 1 5
KOKM 06 J22 300x200 50 1 10P10 1
KOKM 06 J22 300x200 100 1 10P10 2
KOKM 06 J22 300x200 300 1 5P10 3
KOKM 06 J22 300x200 1,200 5 5P10 30
KOKM 06 J22 300x200 2,000 5 5P10 50
KOKM 06 J23 600x200 50 1 10P10 1
KOKM 06 J23 600x200 50 5 10P10 0.5
KOKM 06 J23 600x200 100 1 10P10 3
KOKM 06 J23 600x200 200 1 10P10 2
KOKM 06 J24 300x200 50 1 10P10 1
KOKM 06 J24 300x250 150 1 10P10 2
KOKM 06 J29 450x650 50 1 10P10 1
KOKM 06 J29 450x650 50 5 10P10 0.5
KOKM 06 J29 450x650 100 1 10P10 2
KOKM 06 J29 450x650 400 1 5P10 7.5

If other electrical parameters other than those given in the tables are required please
contact our sales department.

Cable current transformers 15


Overall dimensions

KOKM 06 J2 KOKM 06 J21


113
80 113 80
M6
M6 M5 18,5 M5 18,5

18,5

18,5
15

23

23
15

6
40 40

462
300
370
10
4

0
R4

665
20

500 +30
573
613
4

+3
R1

500 0

20 573

613
80

P1 P2

0
R4
S1 S2

20
150

4
R1
20 220

260

P1 P2
S1 S2 80

KOKM 06 J22 KOKM 06 J23


113 113
80 80

M6 M5 18,5 M6 M5 18,5

18,5
18,5

23

23
15 15
6

6
40 40
462
300
370
410

0
R4
765
0
+3
600
673
713
20

4
R1

200

20 270

310

P1 P2
S1 S2
0
80

R4
20

4
R1 200

20 270

310
P1 P2
S1 S2
80

16 Cable current transformers


Overall dimensions

KOKM 06 J24 KOKM 06 J29


113 113
80 80
M6 M5
M6 M5 18,5 18,5

15

18,5
18,5

23
23
15

6
6
40 40

612
560
520
450
462
300
370
410

0
R4

0
R4

20

4
650+30

R1
20 720
760
20

P1 P2
S1 S2
4
R1

250

80
20 320

360

P1 P2
S1 S2
80

Cable current transformers 17


Indoor cable current transformers
type KOKM (for GIS type ZX)

KOKM 1 LH_ is the indoor, cable, low-voltage current transformer Table 10. Technical data
in resin insulation. These transformer types are suitable for the Type KOKM 1 LH_
measurement of phase currents. A busbar or low-voltage cable Max. number of windings 1
serves as the primary conductor. Current transformers from the Level of insulation 1/6/-
KOKM series can also be used to measure phase currents at vol- Highest permissible voltage of the current 1.2 kV
tages higher than 1.2 kV if the insulation of the high-voltage transformer U r
primary conductor fulfils the requirements of the relevant Rating test voltage of insulation 6 kV
standards related to the working voltage. (50 Hz, 1 min U p)
Rating frequency 50 Hz
Ordering data Rating thermal current 1.2 x I pn
The order should contain following data: Short-time withstand thermal current I th, 1 s 60 x I pn
– Type of current transformer Rating peak current I dyn 2.5 x I th
– Rated primary current/rated secondary current [A/A] Working temperature range -5 ... +40°C
– Rated burden and accuracy class for each winding [VA] Conformity with standards IEC, ANSI, PN-EN, CAN
– Short-time thermal current Ith
– Standard
– Quantity

Order example
KOKM 06 NN; 12 150/1 A/A, Ith = 60 x Ipn, 1 VA 10P10 – 3 Pcs.

18 Cable current transformers


Table 11. Standard parameters for KOKM 1 LH_
Primary Maximum permissible load [VA]
current Secondary current I sn = 1 [A] Secondary current I sn = 5 [A]
I pn [A] Measurement class Protection class Measurement class Protection class
FS Fa Fs Fa
0.5 1 10P10 10P20 5P10 5P20 0.5 1 10P10 10P20 5P10 5P20
50 – – 2 1 0.5 0.5 – – 1.5 1 0.5 0.5
60 – – 2 1 0.5 0.5 – – 2 1 1 0.5
70 – – 2.5 1 1.5 1 – – 2.5 1 1.5 1
75 – – 2.5 1 1.5 1 – – 2.5 1.5 2 1
100 – 1.5 3.5 1.5 3.5 1.5 – 1.5 3 1.5 3 1.5
110 – 3 4 1.5 4 1.5 – 2.5 3.5 1.5 3.5 1.5
120 – 3.5 4 1.5 4 1.5 – 3.5 3.5 1.5 3.5 1.5
140 – 6 5 1.5 5 2 – 7.5 4.5 2 4.5 2
150 – 8.5 5.5 2 5.5 2 – 8.5 5 2 5 2
200 4 20 7.5 2 7.5 3 2.5 11 7 2.5 7 2.5
240 9 30 8.5 3.5 8.5 3.5 9 29 8.5 3 8.5 3
250 10 32 9 3.5 9 3.5 10 33 9 3.5 9 3.5
300 17 50 11 4 11 4 19 50 10 4.5 10 4.5
350 29 60 12 4.5 12 4.5 29 60 12 5.5 12 5.5
400 60 90 12 3 12 3 39 60 14 6 14 6
500 60 90 15 4 15 4 50 90 18 8 18 8
600 60 90 18 5.5 18 5.5 60 90 21 8.5 21 8.5
630 60 90 19 5.5 19 5.5 60 90 21 8.5 21 8.5
800 90 90 20 5.5 20 5.5 90 90 26 9 26 9
1000 90 90 26 7 26 7 90 90 27 5.5 27 5.5
1200 90 90 31 8.5 31 8.5 90 90 30 6 30 6
1250 90 90 31 8 31 8 90 90 32 6.5 32 6.5

By special request current transformers with secondary current values different from those given in the table above (eg. 4.3 A), and current transformers for a frequency of 60 Hz
can be supplied.

Cable current transformers 19


Overall dimensions

KOKM 1 LH_ version 01 KOKM 1 LH_ version 02


126 126

60 70
26

2
14,5

19

37
37

90
235
30 Ø1
Ø1 30

117,5
M8
235

Ø11
117,5

Ø11 M8

37
37

10
90
126 B
10

90 180 A
126 B 200
180 A 200
200

200

58
40

37
30,5
12
40

24,5

M5 M5
M5 M3

Type Dimensions [ mm]


A B
KOKM 1 LH 6 60 30
KOKM 1 LH 9 90 60
KOKM 1 LH 12 120 90

KOKM 1 LH_ version 03

30
Ø1
245

secondary terminals, lenght 6 m,


cable 4 mm
112,5
117,5
105,5
2

55,5
145
170
200

fixing base Index of CT Description Code A B


rating plate
1YMA183183R0013 CT KOKM 1 LH 12 KOKM 1 LH 12-v3-P2 120 P2
170

seal wire pocket PG16

screw cap for bushing PG16


with cable and P2 from cable side
1YMA183183R0012 CT KOKM 1 LH 9 KOKM 1 LH 9-v3-P2 90 P2
15 with cable and P2 from cable side
1YMA183183R0011 CT KOKM 1 LH 6 KOKM 1 LH 6-v3-P2 60 P2
15
330 with cable and P2 from cable side
360
1YMA183183R0003 CT KOKM 1 LH 12 KOKM 1 LH 12-v3-P1 120 P1
with cable and P1 from cable side
1YMA183183R0002 CT KOKM 1 LH 9 KOKM 1 LH 9-v3-P1 90 P1
with cable and P1 from cable side
1YMA183183R0001 CT KOKM 1 LH 6 KOKM 1 LH 6-v3-P1 60 P1
with cable and P1 from cable side

20 Cable current transformers


KOKM 1 NJ_ is the indoor, cable, low-voltage current transformer be used to measure phase currents at voltages higher than 1.2 kV
in resin insulation. These transformer types are suitable for the if the insulation of the high-voltage primary conductor fulfils the
measurement of phase currents in low-voltage switchgears. requirements of the relevant standards related to the working volt-
A non-insulated busbar or low-voltage cable serves as the primary age.
conductor. Current transformers from the KOKM series can also

Table 12. Technical data


Type KOKM 1 NJ_
Max. number of windings 1
Highest permissible voltage of the current 1.2 kV
transformer U r
Rating test voltage of insulation (50 Hz, 1 min U p) 6 kV
Rating frequency 50 Hz
Rating thermal current 1.2 x I pn
Short-time withstand thermal current I th, 1 s 60 x I pn
Rating peak current Idyn 2.5 x I th
Working temperature range -5 ... +40°C

KOKM 1 NJ 8 version 01 Conformity with standards IEC, ANSI, PN-EN, CAN

Table 13. Standard parameters for KOKM 1 NJ_


Primary Maximum permissible load [VA]
current Secondary current I sn = 1 [A] Secondary current I sn = 5 [A]
I pn [A] Measurement class Protection class Measurement class Protection class
FS Fa FS Fa
0.5 1 10P10 10P20 5P10 5P20 0.5 1 10P10 10P20 5P10 5P20
50 – – 2 1 0.5 0.5 – 2 0.5 0.5 0.5
60 – – 2.5 1 0.5 1 – – 2.5 1.5 0.5 0.5
70 – – 3 1.5 1.5 1.5 – – 3 1.5 1 1
75 – – 3.5 1.5 2 1.5 – – 3 1.5 1.5 1
100 – 0.5 4.5 2 4 2 – 0.5 4 1.5 4 1.5
110 – 2 5 2.5 4.5 2.5 – 1.5 4.5 2 4.5 2
120 – 3.5 5.5 2.5 5.5 2.5 – 3 5 2 5 2
140 – 5 6.5 3 6.5 3 – 4.5 6 2.5 6 2.5
150 – 6.5 7 3 7 3 – 5 6.5 3 6.5 3
200 1.5 8 8 3.5 8 3.5 1 9 9 4 9 4
240 4.5 13.5 9.5 4.5 9.5 4.5 4.5 14 10 5 10 5
250 5 15 10 4.5 10 4.5 5 15 11 5 11 5
300 9 23 12 5.5 12 5.5 11 26 13 6 13 6
350 18 35 14 6.5 14 6.5 18 32 15 7 15 7
400 29 50 16 7.5 16 7.5 20 40 18 8 18 8
500 35 80 20 9 20 9 30 60 20 10 20 10
600 50 90 24 11 24 11 45 90 25 12 25 12
630 50 90 25 11 25 11 50 90 26 12 26 12
800 60 90 31 14 31 14 90 90 30 13 30 13
1000 90 90 38 16 38 16 90 90 38 14 38 14
1200 90 90 42 18 42 18 60 90 40 13 40 13
1250 90 90 45 18 45 19 60 90 40 12 40 12

By special request current transformers with secondary current values different from those given in the table above (eg. 4.3 A), and current transformers for a frequency of 60 Hz
can be supplied.

Cable current transformers 21


Overall dimensions

KOKM 1 NJ_ version 01 KOKM 1 NJ_ version 02


105 105
60 70

2
26

7
14,5
19

55
55

247
5
15 15

240
5

120
120

M8
11
11 M8

55
55

10
10

90 B
90
105 A
105
215 215

235 235

235
235

93
40
58

55

31
31

37
30,5
40

12

24,5

M5 M5
M5 M3

Type Dimensions [mm]


A B
KOKM 1 NJ 6 60 30
KOKM 1 NJ 9 90 60
KOKM 1 NJ 12 120 90
KOKM 1 NJ_ version 03
A

155
245

secondary terminals, lenght 6 mm


cable 4 mm
105,5
112,5
127,5
2

73
205
235

fixing plate

rating plate
205

seal wire pocket PG16

screw cap for bushing PG16

15 15

330
360

Index of CT Description Code A B


1YMA183182R0013 CT KOKM 1 NJ 12 with cable and P2 from cable side KOKM 1 NJ 12-v3-P2 120 P2
1YMA183182R0012 CT KOKM 1 NJ 9 with cable and P2 from cable side KOKM 1 NJ 9-v3-P2 90 P2
1YMA183182R0011 CT KOKM 1 NJ 6 with cable and P2 from cable side KOKM 1 NJ 6-v3-P2 60 P2
1YMA183182R0003 CT KOKM 1 NJ 12 with cable and P1 from cable side KOKM 1 NJ 12-v3-P1 120 P1
1YMA183182R0002 CT KOKM 1 NJ 9 with cable and P1 from cable side KOKM 1 NJ 9-v3-P1 90 P1
1YMA183182R0001 CT KOKM 1 NJ 6 with cable and P1 from cable side KOKM 1 NJ 6-v3-P1 60 P1

22 Cable current transformers


KOKM 1 EB_ and KOKM 1 ED_ are indoor, cable, low-voltage the KOKM series can also be used to measure phase currents at
current transformers in resin insulation. These transformer types voltages higher than 1.2 kV if the insulation of the high-voltage
are suitable for the measurement of phase currents. A busbar or primary conductor fulfils the requirements of the relevant
cable serves as the primary conductor. Current transformers from standards related to the working voltage.

Table 14. Technical data


Type KOKM 1 EB_, KOKM 1 ED_
Max. number of windings 3
Level of insulation 1/6/-
Highest permissible voltage of the current 1.2 kV
transformer U r
Rating test voltage of insulation 6 kV
(50 Hz, 1 min U p)
Rating frequency 50 Hz, 60 Hz
Rating thermal current 1.2 x I pn
Short-time withstand thermal current I th, 1 s 60 x I pn
Rating peak current I dyn 2.5 x I th
KOKM 1 EB version 03
Working temperature range -5 ... +40°C
Conformity with standards IEC, ANSI, PN-EN, CAN

Table 15. Standard parameters for KOKM 1 EB_


Primary Maximum permissible load [VA]
current Secondary current I sn = 1 [A] Secondary current I sn = 5 [A]
I pn [A] Measurement class Protection class Measurement class Protection class
FS Fa Fs Fa
0.5 1 10P10 5P10 5P20 0.5 1 10P10 5P10 5P20
50 – – 0.5 0.5 0.5 – – 0.5 – –
60 – – 0.5 0.5 0.5 – – 0.5 0.5 –
70 – 0.5 1 1 0.5 – 0.5 0.5 0.5 –
75 – 1 1 1 0.5 – 1 1 1 –
100 – 2.5 1.5 1.5 0.5 – 1.5 1 1 –
110 0.5 4 1.5 1.5 0.5 – 2.5 1 1 –
120 1 4.5 1.5 1.5 0.5 0.5 3 1.5 1.5 –
140 1 4.5 1.5 1.5 0.5 1.5 7 2 2 0.5
150 1.5 6 2 2 0.5 1.5 7 2 2 0.5
200 5.5 8.5 2.5 2.5 0.5 2.5 12 2.5 2.5 1
240 5.5 20 2.5 2.5 0.5 8 25 3.5 3.5 1
250 4.5 25 3 3 0.5 11 28 3.5 3.5 1
300 12 40 3 3 0.5 15 40 4.5 4.5 1.5
350 9 27 5 5 1 22 45 5 5 1.5
400 22 40 4.5 4.5 1.5 30 60 6 6 2
500 35 50 6 6 2 45 60 6 6 1.5
600 60 60 6 6 1 60 60 5.5 5.5 –
630 60 60 5 5 0.5 60 60 6 6 –
800 60 60 5 5 – 60 60 7 7 –
1000 60 60 6 6 – 60 60 – – –

By special request current transformers with secondary current values different from those given in the table above (eg. 4.3 A), and current transformers for a frequency of 60 Hz
can be supplied.

Cable current transformers 23


Overall dimensions

KOKM 1 EB_ version 01 KOKM 1 EB_ version 02


74 77
56
60

14,5

19
32

0,5°

70
205
72
170

72
~5m

70
M6
70

56 100
80
128 M6
A
100
B
128

58
2=S2
40
1=S1
M6
40

12

24,5

M5 M3

Type Dimensions [mm]


A B
KOKM 1 E ...8 56 80
KOKM 1 E ...10 76 100
KOKM 1 E ...12 96 120

KOKM 1 EB_ version 03 KOKM 1 ED_


8
8

ok. 50 0 0

ok 50 0 0

74 74

max 6
max 6

32
32

90
90

0,5°
170
0,5°
170

72
72

70
70

M6
M6

A
120
A B
100
B 148
128

3S

2S
130
90

130

1S
50

90
50

Type Dimensions [mm]


A B
KOKM 1 E ...8 56 80
KOKM 1 E ...10 76 100
KOKM 1 E ...12 96 120
KOKM 1 E ...14 116 140
KOKM 1 E ...16 136 160
KOKM 1 E ...18 156 180

24 Cable current transformers


KOKM 06 NN_ is the indoor, cable, low-voltage current trans- the KOKM series can also be used to measure phase currents at
former in resin insulation. These transformer types are suitable for voltages higher than 0.72 kV if the insulation of the high-voltage
the measurement of phase currents. A non-insulated busbar or primary conductor fulfils the requirements of the relevant stand-
cable serves as the primary conductor. Current transformers from ards related to the working voltage.

Table 16. Technical data


Type KOKM 06 NN_
Max. number of windings 2
Level of insulation 0.6/3/-
Highest permissible voltage of the current 0.72 kV
transformer U r
Rating test voltage of insulation 3 kV
(50 Hz, 1 min U p)
Rating frequency 50 Hz
Rating thermal current 1.2 x I pn
Short-time withstand thermal current I th, 1 s 60 x I pn
Rating peak current Idyn 2.5 x I th
Working temperature range -5 ... +40°C
KOKM 06 NN 12 Conformity with standards IEC, ANSI, PN-EN, CAN

Table 17. Standard parameters for KOKM 06 NN_


Primary Maximum permissible load [VA]
current Secondary current I sn = 1 [A] Secondary current I sn = 5 [A]
I pn [A] Measurement class Protection class Measurement class Protection class
FS Fa Fs Fa
0.5 1 10P10 10P20 5P10 5P20 0.5 1 10P10 10P20 5P10 5P20
50 – – 3.5 1.5 – – – – 3 1 – –
60 – – 4 2 – – – – 3.5 1.5 – –
70 – – 5 2.5 – – – – 4.5 1.5 – –
75 – – 5.5 2.5 – – – – 5 2 – –
100 – – 7 3.5 7 1 – – 6 2.5 6 1
110 – – 7.5 4 7.5 1.5 – – 7 3 7 1.5
120 – – 8 4 8 4 – – 7 2.5 7 2.5
140 – – 10 5 10 5 – – 9 3.5 9 3.5
150 – – 10 5 10 5 – – 9 4 9 4
200 – 8 14 7 14 7 – 9 13 5.5 13 5.5
240 – 15 17 8.5 17 8.5 – 16 15 6.5 15 6.5
250 – 19 18 9 18 9 – 19 16 7 16 7
300 – 31 21 10 21 10 – 31 20 8 20 8
350 0.5 50 25 12 25 12 – 50 22 10 22 10
400 15 60 28 13 28 13 15 55 25 11 25 11
500 35 90 34 16 34 16 35 60 31 14 31 14
600 60 90 41 17 41 17 60 90 38 15 38 15
630 60 90 42 18 42 18 60 90 39 16 39 16
800 90 90 52 23 52 23 90 90 49 21 49 21
1000 90 90 66 28 66 28 90 90 63 26 63 26
1200 90 90 80 34 80 34 90 90 77 32 77 32
1250 90 90 82 35 82 35 90 90 79 33 79 33
1500 90 90 90 40 90 40 90 90 90 40 90 40

By special request current transformers with secondary current values different from those given in the table above (eg. 4.3 A), and current transformers for a frequency of 60 Hz
can be supplied.

Cable current transformers 25


Overall dimensions

KOKM 06 NN_
95.5
M5 69
A 26.5

13
22
60

10

420
310
15
55

15
65
2 x brass pipe 12x1,5
235

30
20.5

Type Dimensions [mm]


A
KOKM 06 NN 6 60
KOKM 06 NN 9 90
KOKM 06 NN 12 120
KOKM 06 NN 14 140
KOKM 06 NN 16 160
KOKM 06 NN 18 180

26 Cable current transformers


KOKM 06 LM_ is the indoor, cable, low-voltage current transform- can also be used to measure phase currents at voltages higher
er in resin insulation. These transformer types are suitable for the than 0.72 kV if the insulation of the high-voltage primary conduc-
measurement of phase currents. A busbar or cable serve as the tor fulfils the requirements of the relevant standards related to the
primary conductor. Current transformers from the KOKM series working voltage.

Table 18. Technical data


Type KOKM 06 LM_
Max. number of windings 2
Level of insulation 0.6/3/-
Highest permissible voltage of the current 0.72 kV
transformer U r
Rating test voltage of insulation 3 kV
(50 Hz, 1 min U p)
Rating frequency 50 Hz
Rating thermal current 1.2 x I pn
Short-time withstand thermal current I th, 1 s 60 x I pn
Rating peak current I dyn 2.5 x I th
Working temperature range -5 ... +40°C
Conformity with standards IEC, ANSI, PN-EN, CAN
KOKM 06 NN_ versus KOKM 06 LM_

Table 19. Standards parameters for KOKM 06 LM_


Primary Maximum permissible load [VA]
current Secondary current I sn = 1 [A] Secondary current I sn = 5 [A]
I pn [A] Measurement class Protection class Measurement class Protection class
FS Fa Fs Fa
0.5 1 10P10 10P20 5P10 5P20 0.5 1 10P10 10P20 5P10 5P20
50 – – 3.5 1.5 – – – – 3 1 – –
60 – – 3.5 1.5 – – – – 3.5 1.5 – –
70 – – 5 2.5 – – – – 4.5 1.5 – –
75 – – 5 2.5 5 – – – 5 2 – –
100 – – 7 3.5 5 1.5 – – 6 2.5 6 1.5
110 – – 8 4 8 3.5 – – 7 3 7 2.5
120 – – 8 4 8 4 – – 7 3 7 3
140 – – 10 5 10 5 – – 9 3.5 9 3.5
150 – – 11 5 11 5 – – 9 4 9 4
200 – 11 13 7 13 7 – 11 13 5.5 13 5.5
240 – 20 16 8.5 16 8.5 – 20 15 6.5 15 6.5
250 – 23 18 9 18 9 – 23 16 7 16 7
300 – 35 21 10 21 10 – 35 20 8 20 8
350 12 55 25 12 25 12 12 55 22 10 22 10
400 20 60 28 13 28 13 20 60 25 11 25 11
500 40 90 34 16 34 16 40 90 31 14 31 14
600 60 90 41 17 47 17 60 90 38 15 38 15
630 60 90 42 18 42 18 60 90 39 16 39 16
800 90 90 52 23 52 23 90 90 49 21 49 21
1000 90 90 66 28 66 28 90 90 63 23 63 23
1200 90 90 80 34 80 34 90 90 77 32 77 32
1250 90 90 82 35 82 35 90 90 79 33 79 33
1500 90 90 90 40 90 40 90 90 90 40 90 40

By special request current transformers with secondary current values different from those given in the table above (eg. 4.3 A), and current transformers for a frequency of 60 Hz
can be supplied.

Cable current transformers 27


Overall dimensions

KOKM 06 LM_
95.5

A M5 69
26.5

17
22

400
280
130
15
55

65 15
210 2 x brass pipe 12x1,5

30
20.5

Type Dimensions [mm]


A
KOKM 06 LM 6 60
KOKM 06 LM 9 90
KOKM 06 LM 12 120
KOKM 06 LM 14 140
KOKM 06 LM 16 160
KOKM 06 LM 18 180

28 Cable current transformers


Indoor cable current transformers
type KOKM (for RMU)

KOKM 072 BA 10, CA 10 – These indoor ring core current trans- transport and storage of these transformers is in the range
former types supply metering and protection devices at a +5°C ... +40°C. Secondary circuits should be mounted using
maximum nominal voltage of 0.72 kV and nominal frequency of copper wires with a cross sectional area of at least 2.5 mm 2.
50 or 60 Hz. The transformers can be mounted inside the Connecting schemes for current and energy measurements are
switchgear. The nominal temperature recommended during the shown on pages 30 and 31.

Table 20. Electrical parameters


Type KOKM 072 BA 10 KOKM 072 CA 10 KOKM 072 CA 10 KOKM 072 CA 10 KOKM 072 CA 10 KOKM 072 CA 10
Number of windings 2 pcs. (terminals 2 pcs. (terminals 1 pcs. (terminals 1 pcs. (terminals 1 pcs. (terminals 1 pcs. (terminals
for measuring S0-S1-S2 S0-S1-S2) S1-S2 S1-S2 S1-S2 S1-S2
137 turns (48+89)) 1116 turns (391+725) 187 turns) 381 turns) 765 turns) 1535 turns)
Number of windings 1 pcs. (terminals 1 pcs. (terminals 1 pcs. (terminals 1 pcs. (terminals 1 pcs. (terminals 1 pcs. (terminals
for the test C-D 48 turns) C-D 391 turns) C-D 50 turns C-D 100 turns) C-D 200 turns) C-D 400 turns)
Rated insulation level 0.72/3/- 0.72/3/- 0.72/3/- 0.72/3/- 0.72/3/- 0.72/3/-
Highest voltage for equipment U m 0.72 kV 0.72 kV 0.72 kV 0.72 kV 0.72 kV 0.72 kV
Rated power-frequency withstand 3 kV 3 kV 3 kV 3 kV 3 kV 3 kV
voltage (r.m.s.)
Rated frequency f n 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Rated primary current I pn 14.4 – 41.1 A 117.4 - 335 A 14.4 A 28.8 A 57.6 A 115.2 A
Rated secondary current I sn 0.3 A 0.3 A 0.075 A 0.075 A 0.075 A 0.075 A
Test Winding 0.3 A 0.3 A 0.288 A 0.288 A 0.288 A 0.288 A
Accuracy class with relay type 5P30 5P30 10P80 5P80 5P80 5P80
MPRB / WIC1
Rated burden 0.1 VA 0.1 VA 0.1 VA 0.1 VA
Rated continuous thermal 4 x Ipn 4 x Ipn 10 x Ipn 10 x Ipn 10 x Ipn 10 x Ipn
current Icth (ext. 400%) (ext. 400%) (ext. 1000%) (ext. 1000%) (ext. 1000%) (ext. 1000%)
Rated short-time thermal current 100 x Ipn A 100 x I pn A 20 kA 20 kA 20 kA 20 kA
Ith 1 s
Rated dynamic current I dyn 2.5 x I th A 2.5 x I th A 62.5 kA 62.5 kA 62.5 kA 62.5 kA
Insulation class E E E E E E
Protection IP 20 IP 20 IP 20 IP 20 IP 20 IP 20
External dimensions DxdxLxH 100x42x100x124 100x50x100x124 100x50x100x124 100x50x100x124 100x50x100x124 100x50x100x124
Weight 3.3 2.8 2.27 1.9 1.4 1.7
Working temperature range -25 ... +70°C -25 ... +70°C -25 ... +70°C -25 ... +70°C -25 ... +70°C -25 ... +70°C
Conformity with standards IEC 60044-1 IEC 60044-1 IEC 60044-1 IEC 60044-1 IEC 60044-1 IEC 60044-1

Cable current transformers 29


Terminal marking

KOKM 072 BA 10 = MPTA 96-14-90


Terminals Ratio Class Number of windings
S0 – S1 14.4/0.3 A 5P30 48 P1 P2
S0 – S2 41.1/0.3 A 5P30 137 (48+89) S0 S1 S2 C D
C–D 0.3 A test winding 48

KOKM 072 CA 10 for REJ 603*


Terminals Ratio Burden Class Number of windings
S1 – S2 14.4/0.075 A 0.1 VA 10P80 187 P1 P2
C–D 0.288 A test winding 50 S1 S2 C D

KOKM 072 CA 10 for REJ 603*


Terminals Ratio Burden Class Number of windings
S1 – S2 28.8/0.075 A 0.1 VA 5P80 381 P1 P2
C–D 0.288 A test winding 100 S1 S2 C D

KOKM 072 CA 10 for REJ 603*


Terminals Ratio Burden Class Number of windings
S1 – S2 57.6/0.075 A 0.1 VA 5P80 765 P1 P2
C–D 0.288 A test winding 200 S1 S2 C D

KOKM 072 CA 10 for REJ 603*


Terminals Ratio Burden Class Number of windings
S1 – S2 115.2/0.075 A 0.1 VA 5P80 1535 P1 P2
C–D 0.288 A test winding 400 S1 S2 C D

KOKM 072 CA 10 = MPTA 96-117-737


Terminals Ratio Class Number of windings
S0 – S1 117.4/0.3 A 5P30 391 P1 P2
S0 – S2 335/0.3 A 5P30 1116 (391+725) C D
S0 S1 S2
C–D 0.3 A test winding 391

*or other non ABB relays e.g. WIC

30 Cable current transformers


Overall dimensions, connection diagram

CT outside dimensions for ratios of: 14.4/0.075 A, 28.8/0.075 A, 57.6/0.075 A, 115.2/0.075A

70 60

6.5
Ø

=
R50

50

143
124

100

115
133
4

80

=
18

L1 L3 L2

S1
1
S2
2 C
3 D
gn/ge
S1
1
S2
2 C
3 D
gn/ge
S1

S2
C
D

FI+
flag indicator
FI-
low energy TC+

TC-

230V
extrenal power source 115V
N
N

WIC1

Cable current transformers 31


Overall dimensions, connection diagram

CT outside dimensions for ratios of: 14.4 – 41.1/0.3 A, 117.4 – 335/0.3 A


70 60

6.5
Ø

=
R50

42

143
124

100

115
133
4

80

=
18

L1 L2 L3

remote
1
trip
230 V AC 2
3
4
5
S2
6
S1
S0 7
C S2 8
D
S1 9
S0 10
C S2 11
D
S1 12
S0 13
C
14
D
15
power
16
supply 17
230 V AC
18
MPRB

32 Cable current transformers


S1
REJ 603

S2
C L3

S1

S2
C L2

S1

S2
C L1

S1 N

S2 E

TC(+)
trip coil
TC(-)

BI
external input
BI

Product number Type of CT Primary current Secondary current


Ipn [A] Isn [A]
1YMA183190R0001 KOKM 072 CA 10 14.4 A 0.075 A for REJ 603 - CT2
1YMA183190R0002 KOKM 072 CA 10 28.8 A 0.075 A for REJ 603 - CT3
1YMA183190R0003 KOKM 072 CA 10 57.6 A 0.075 A for REJ 603 - CT4
1YMA183190R0004 KOKM 072 CA 10 115.2 A 0.075 A for REJ 603 - CT5
1YMA183190R0005 KOKM 072 CA 10 117.4 - 335 A 0.3 A
1YMA183190R0006 KOKM 072 BA 10 14.4 - 41.1 A 0.3 A

Order example
KOKM 072 CA 10 (1YMA183190R0003); 57.6/0.075 A/A; 0.1 VA; 5P80; Ith= 20 kA/1s; IEC 60044-1; 21 Pcs.

Cable current transformers 33


Indoor special current transformer
type KORI 072 GH 8

KORI 072 GH 8 – Low-voltage current instrument transformer,


without a primary conductor that can be assembled on the
switchgear bushing with its own insulation. Transformers of this
type enable protection and are designed for use in indoor instal-
lations. KORI072 GH 8 transformers are generally designed with
one transformer ratio. However, they can also have more ratios if
the possibility to reconnect them to the secondary side exists.
The transformer assembly procedure on the bushings
of a UniGear 550 switchgear panel is specified exactly.
All transformers meet the requirements of the relevant standard
i.e. the IEC 60044-1.

Table 21. Technical data


Type (low voltage current transformer for medium voltage application) KORI
Highest voltage for equipment Um [kV] 0.72
Power frequency test voltage U p (1 min) [kV] 3
Rated insulation level [kV] 0.72/3/–
Rating frequency fn [Hz] 50
Rated primary current Ipn [A] 1600 up to 2500
Rated secondary current Isn [A] 1 or 5
Rated short-time thermal current I th (3 s) [kA] 50.0
Rating peak current Idyn [kA] 125.0
Accuracy classes 5P20
Burden Sn [VA] 10, 15, 20, 25 or 30
Highest voltage of a system [kV] 12 – 17.5 kV by using CT ROD
Flammability class B
KORI 072 GH 8 current transformers are designed for ABB switchgear type Unigear 550.

Other parameters have to be agreed with the manufacturer and will be considered on an individual basis.
Reconnectable variants are also possible, but need to be examined on an individual basis (according to the customer’s requirements and the agreement with the manufacturer).

34 Cable current transformers


Overall dimensions

90

29
4x Ø 8.5
0

197
Ø 90

197
173

173
197
17
40
75

rating plate

Cable current transformers 35


Current transformers
type KOLT (for oil-immersed transformers)

KOLT – this transformer type has no housing and primary winding. parts to facilitate both transport and installation. Each individual
Under operating conditions, the bushing insulator, which is the part contains the following information: a serial number which
main current transformer insulation, also serves as the primary coincides with the one stated on the rating plate, and markings for
winding. The secondary windings are evenly wound on the primary and secondary winding terminals.
circumference of the toroidal core.
Secondary winding insulation is made of polyester tape (torlen).
Current transformers weighing 100 kg or more consist of several

Table 22. Technical data


Type KOLT
Primary current range I pn [A] 100 A - 15,000 A
Rated secondary current Isn [A] 1A ÷ 5A
Insulation level [kV] 0.72/3/-
Range of rated output Sn [VA] 1 VA -90 VA
Number of windings 1-4
Conformity with standards IEC, PN-EN, SEV, VDE, ANSI, BS, CAN, CSA, GOST
Accuracy class acc. to IEC 0.2s; 0.5s; 0.2; 0.5; 1; 3; 5; 5P; 10P; PX
FS 5; 10
ALF 5; 10; 15; 20; 25; 30
Rated frequency f [Hz] 50, 60
Short-time withstand thermal current Ith (1 s) [A] 100 x I pn max. 100 kA
Peak withstand current I dyn [A] 2.5 x I th max. 250 kA
Insulation class acc. to IEC B
Min. inside diameter ØA [mm] min. 30 mm depending on parameters
Max. outside diameter ØB [mm] max. 900 mm depending on parameters
Height h [mm] max. 900 mm depending on parameters
Length of leads D [mm] 1 m, other length at the client’s request

Transformers with other dimensions and parameters are available upon request.

36 Cable current transformers


Versions available – Incorrect transport
– Single phase – Incorrect storage
– With one or several windings – A failure to follow instructions correctly during installation and
– With one or several tappings operation
– Insulation – cotton tape + impregnating varnish – Incorrect selection of the transformer for the electric power
– Without housing system
– Without primary winding
Ordering
Aplication The order must contain the following:
KOLT type current transformers can be mounted inside power – Name and type of current transformer
transformers. They will operate in oil, and under moderate and – Rated primary current / rated secondary current Ipn/Isn [A]
tropical climate conditions. These current transformers are de- – Short-time thermal current, 1 s Ith [kA]
signed to supply measurement and protection circuits of power – Rated output power and accuracy class of each winding Sn [VA]
systems operating under a rated frequency of 50 Hz. – Limit transformer dimensions (min. inside diameter, max. outside
diameter, max. height)
Marking – Length of leads
Each current transformer is fitted with a rating plate in accordance – Standard
with the IEC 60044-1 Standard. Values of rated voltage and the – Quantity
rated power frequency test voltage of the insulation (stated on
the rating plate) refer to the insulation of the secondary windings. Order example
Primary and secondary terminals are directly marked on the Current transformer type KOLT
current transformer. 1200/5/1/1 A
Ith = 72 kA
Transport I. 15 VA, class 0.5 FS10
During transportation, current transformers must be protected II. 60 VA, class 5P15
against humidity and heavy shocks. Current transformers III. 60 VA, class 5P20
weighing more than 50 kg and which are especially sensitive to min. inside diameter A = ø150 mm
shocks are transported on wooden pallets. max. outside diameter B = ø300 mm
max. height h = 200 mm
Installation length of leads 1.5 m
During installation of current transformers the following instructions standard IEC 60044-1
should be observed: quantity – 9 Pcs.
– Secondary winding marked 1S1- 1S2 should be placed on the
top
– Keep the same polarization for all parts of the current transformer
(P1 – P2 – P1 – P2 markings)
– Avoid shocks

Compliance with standards


Current transformers meet the requirements of the following
standards: IEC 60044-1.
At the client’s request we manufacture current transformers that
meet the requirements of SEV, VDE, ANSI, BS, CAN, CSA, GOST
standards.

Warranty
A two-year warranty period is granted from the date the transfor-
mer starts to operate. However, a maximum warranty period of
three years is granted from the time of purchase. The warranty
only covers manufacturing defects and does not include defects
due to:

Cable current transformers 37


Overall dimensions

1S... 2S... ...S... 1S5 1S4 1S3 1S2 1S1

D
Rating plate
Rating plate

Rating plate ØA

ØB
P1

38 Cable current transformers


Cable current transformers 39
Contact us

ABB We reserve the right to make technical changes or modify

1VLC000519-rev2,en,2013.07.29
PPMV Brno the contents of this document without prior notice. With
Videnska 117 regard to purchase orders, the agreed particulars shall
prevail.
619 00 Brno, Czech Republic
ABB does not accept any responsibility whatsoever for
Phone: +420 547 152 602
potential errors or possible lack of information in this
+420 547 152 614
document.
Fax: +420 547 152 626
e-mail:info.ejf@cz.abb.com We reserve all rights in this document and in the subject
www.abb.com matter and illustrations contained therein. Any reproduction
– in whole or in parts – is forbidden without ABB’s prior
written consent.

© Copyright 2011 ABB


All rights reserved