Cable Sizing Calculation Report

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 148

PROJECT NAME: COMMERCIAL COURT IN LUSAIL

DOCUMENT TITLE:

CABLE SIZING CALCULATION

DOCUMENT NO.: 3103-IFT-NN-CA-E-0002

ISSUED FOR TENDER


MAR,2022
Cable Sizing Calculation Report
Commercial & Trade Court Project

Project: 3103
3/30/2022
Table of Contents

Subject Page(s)

F-GEN 1
F-SMDB-1F-T 2
F-LP-1F 3
F-PP-1F-1 4
F-PP-1F-2 5
F-SMDB-2F-T 6
F-LP-2F 7
F-PP-2F-1 8
F-PP-2F-2 9
F-SMDB-3F-T 10
F-LP-3F 11
F-PP-3F-1 12
F-PP-3F-2 13
F-SMDB-4F-T 14
F-LP-4F 15
F-PP-4F-1 16
F-PP-4F-2 17
F-SMDB-5F-T 18
F-LP-5F 19
F-PP-5F-1 20
F-PP-5F-2 21
F-SMBE-B-2 22
F-UPP-B 23
F-UPP-G-1 24
F-UPS-2 25
F-UPP-4TH 26
F-UPP-5TH 27
F-UPP-8TH 28
F-BF6 29
F-BF6-TOB-01 30
F-UPP-11TH 31
F-BF6-TOB-02 32
F-UPP-15TH 33
F-BF6-TOB-03 34
F-UPP-22ND 35
F-UPS-3 36
F-UPP-G-2 37
F-UPP-6TH 38
F-UPP-13TH 39
F-UPP-21ST 40
F-EPP-G 41
F-EPP-7TH 42
F-EPP-12TH 43

Page 1
Subject Page(s)

F-EPP-17TH 44
F-EPP-22ND 45
F-CRAC-DX-01 46
F-VRFOU-L03-01 47
F-VRFOU-L04-01 48
F-VRFOU-L05-01 49
F-VRFOU-L05-02 50
F-VRFOU-RF-01 51
F-LVP-2 52
F-LP-G 53
F-PP-G-1 54
F-PP-G-2 55
F-LP-M 56
F-PP-M-1 57
F-PP-M-2 58
F-CRAC-CHW-01 59
F-SMDB-6F-T 60
F-LP-6F 61
F-PP-6F-1 62
F-PP-6F-2 63
F-SMDB-7F-T 64
F-LP-7F 65
F-PP-7F-1 66
F-PP-7F-2 67
F-SMDB-8F-T 68
F-LP-8F 69
F-PP-8F-1 70
F-PP-8F-2 71
F-SMDB-9F-T 72
F-LP-9F 73
F-PP-9F-1 74
F-PP-9F-2 75
F-SMDB-10F-T 76
F-LP-10F 77
F-PP-10F-1 78
F-PP-10F-2 79
F-SMDB-11F-T 80
F-LP-11F 81
F-PP-11F-1 82
F-PP-11F-2 83
F-SMDB-12F-T 84
F-LP-12F 85
F-PP-12F-1 86
F-PP-12F-2 87
F-SMDB-13F-T 88
F-LP-13F 89

Page 1
Subject Page(s)

F-PP-13F-1 90
F-PP-13F-2 91
F-SMDB-14F-T 92
F-LP-14F 93
F-PP-14F-1 94
F-PP-14F-2 95
F-SMDB-15F-T 96
F-LP-15F 97
F-PP-15F-1 98
F-PP-15F-2 99
F-SMDB-16F-T 100
F-LP-16F 101
F-PP-16F-1 102
F-PP-16F-2 103
F-SMDB-17F-T 104
F-LP-17F 105
F-PP-17F-1 106
F-PP-17F-2 107
F-SMDB-18F-T 108
F-LP-18F 109
F-PP-18F-1 110
F-PP-18F-2 111
F-SMDB-19F-T 112
F-LP-19F 113
F-PP-19F-1 114
F-PP-19F-2 115
F-SMDB-20F-T 116
F-LP-20F 117
F-PP-20F-1 118
F-PP-20F-2 119
F-SMDB-21F-T 120
F-LP-21F 121
F-PP-21F-1 122
F-PP-21F-2 123
F-SMDB-22F-T 124
F-LP-22F 125
F-PP-22F-1 126
F-PP-22F-2 127
F-SMDB-23F-T 128
F-LP-23F 129
F-PP-23F-1 130
F-PP-23F-2 131
F-SMDB-24F-T 132
F-LP-24F 133
F-PP-24F-1 134

Page 1
Subject Page(s)

F-PP-24F-2 135
F-SMDB-25F-T 136
F-LP-25F 137
F-PP-25F-1 138
F-PP-25F-2 139

Page 1
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-GEN BUSWAY

Feeder / Load Data


Supply From : GEN-1 Installation Method : AIR Voltage : 0.415 KV Generator Data

To : GEN Material : Copper M.D Load : 993.63 KW Rating 1675 KVA

Length (L) : 10.0 meter Power Factor : 0.85 ZGen 19.10 %

Circuit Breaker Sizing

𝑅𝑎𝑡𝑖𝑛𝑔 𝐾𝑉𝐴
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 2330.27 A
3 𝑋 𝐾𝑉
Safety Factor = 1
Rating , In = 2500 A Circuit Breaker Type : ACB
Circuit Breaker Rating :
Ampere Frame = 2500 A no. of Poles 4P
Busway Sizing
Selected Busway Size:

𝐵𝑢𝑠𝑤𝑎𝑦 𝑅𝑎𝑡𝑖𝑛𝑔 𝐴 ≥ 𝐼𝑛 Busway Rating (A) : 2500 A

R (Ω/m) = 0.00001400
Busway Impedence :
X (Ω/m) = 0.00001100

Short Circuit Criteria


𝑉2 𝑍𝐺𝑒𝑛
𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝐺𝑒𝑛 = × ZSending End 19.64 mΩ
𝐺𝑒𝑛 𝑅𝑎𝑡𝑖𝑛𝑔 (𝐾𝑉𝐴) 100

𝑍𝐵𝑢𝑠𝑤𝑎𝑦 = (R × L)2 + (X × L)2 Zbusway 1.78E-07 mΩ

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐵𝑢𝑠𝑤𝑎𝑦 ZReceiving End 19.64 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 12.2 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Voltage Drop Criteria

1 - Individual V.D. :

V.Dbusway = 0.4055 V V/A/m = 0.000017


𝑉. 𝐷𝑏𝑢𝑠𝑤𝑎𝑦 (𝑉) = 𝑉/𝐴/𝑚 × 𝐼𝑏 × 𝐿 →
V.Dbusway = 0.0977 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝐹𝑒𝑒𝑑𝑒𝑟

V.D busway V.D upstream Feeder 0.0977

0.0977 0 0.098 %

Check : Acc. V.D ≤ 0.5 SUCCEED

Page 2
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-DBE-B-CB CU/XLPE/SWA/LSZH

Cable / Load Data


Supply From : LVP-1 Installation Method : AIR Voltage : 0.415 KV

To : DBE-B-CB Insulation Type : XLPE M.D Load : 39.93 KW

Length (L) : 15.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 65.35 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 80 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑛
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 94.12 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 25 mm2 CU/XLPE/SWA/LSZH

Cable Type :
C.C.C = C.C.C X no. of Cables = 110 Cable Size (mm2) : 25 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 6.46 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 12.99 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 19.45 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 12.3 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 93.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 93.5 A ≥ 80.0 A SUCCEED

2. 𝐼𝑛 ≤ 1.45 𝐼𝑧 80.0 A ≤ 135.6 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 1.8000 V mV/A/m = 1.5


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑛 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.434 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.434

0.434 0.093 0.527 %

Check : Acc. V.D ≤ 3.0 SUCCEED


CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-1F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF1-TOB-01 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-1F-T Insulation Type : XLPE M.D Load : 26.06 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 42.66 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 50.19 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 10.50 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 24.36 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.8 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 42.7 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 1.0238 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.247 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.247

0.247 0.947 1.193 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 3
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-1F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-1F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-1F Insulation Type : XLPE M.D Load : 3.10 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 5.07 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 5.97 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 24.36 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 39.37 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 5.1 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1319 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.032 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.032

0.032 1.193 1.225 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 4
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-1F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-1F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-1F-1 Insulation Type : XLPE M.D Load : 11.04 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 18.07 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 21.26 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 24.36 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 39.37 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 18.1 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.4698 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.113 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.113

0.113 1.193 1.306 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 5
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-1F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-1F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-1F-2 Insulation Type : XLPE M.D Load : 11.93 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 19.52 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 22.96 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 24.36 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 39.37 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 19.5 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.5075 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.122 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.122

0.122 1.193 1.316 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 6
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-2F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF1-TOB-02 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-2F-T Insulation Type : XLPE M.D Load : 26.94 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 44.10 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 51.88 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 10.50 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 24.36 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.8 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 44.1 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 1.0583 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.255 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.255

0.255 1.058 1.313 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 7
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-2F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-2F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-2F Insulation Type : XLPE M.D Load : 2.91 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 4.77 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 5.61 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 24.36 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 39.37 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 4.8 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1239 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.030 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.030

0.030 1.313 1.342 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 8
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-2F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-2F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-2F-1 Insulation Type : XLPE M.D Load : 12.69 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 20.77 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 24.44 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 24.36 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 39.37 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 20.8 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.5400 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.130 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.130

0.130 1.313 1.443 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 9
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-2F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-2F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-2F-2 Insulation Type : XLPE M.D Load : 11.34 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 18.56 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 21.84 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 24.36 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 39.37 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 18.6 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.4826 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.116 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.116

0.116 1.313 1.429 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 10
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-3F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF1-TOB-03 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-3F-T Insulation Type : XLPE M.D Load : 32.13 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 52.59 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 61.87 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 10.50 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 24.36 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.8 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 52.6 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 1.2622 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.304 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.304

0.304 1.116 1.420 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 11
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-3F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-3F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-3F Insulation Type : XLPE M.D Load : 3.78 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 6.19 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 7.28 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 24.36 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 39.37 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 6.2 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1608 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.039 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.039

0.039 1.420 1.459 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 12
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-3F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-3F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-3F-1 Insulation Type : XLPE M.D Load : 14.66 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 23.99 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 28.22 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 24.36 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 39.37 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 24.0 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.6236 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.150 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.150

0.150 1.420 1.570 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 13
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-3F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-3F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-3F-2 Insulation Type : XLPE M.D Load : 13.70 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 22.42 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 26.38 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 24.36 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 39.37 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 22.4 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.5829 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.140 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.140

0.140 1.420 1.560 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 14
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-4F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF1-TOB-04 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-4F-T Insulation Type : XLPE M.D Load : 32.22 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 52.74 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 62.05 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 10.50 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 24.36 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.8 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 52.7 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 1.2658 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.305 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.305

0.305 1.135 1.440 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 15
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-4F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-4F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-4F Insulation Type : XLPE M.D Load : 3.78 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 6.19 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 7.28 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 24.36 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 39.37 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 6.2 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1608 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.039 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.039

0.039 1.440 1.479 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 16
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-4F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-4F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-4F-1 Insulation Type : XLPE M.D Load : 14.75 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 24.13 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 28.39 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 24.36 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 39.37 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 24.1 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.6275 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.151 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.151

0.151 1.440 1.591 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 17
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-4F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-4F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-4F-2 Insulation Type : XLPE M.D Load : 13.70 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 22.42 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 26.38 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 24.36 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 39.37 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 22.4 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.5829 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.140 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.140

0.140 1.440 1.581 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 18
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-5F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF1-TOB-05 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-5F-T Insulation Type : XLPE M.D Load : 34.55 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 56.55 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 66.53 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 10.50 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 24.36 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.8 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 56.6 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 1.3573 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.327 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.327

0.327 1.145 1.472 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 19
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-5F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-5F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-5F Insulation Type : XLPE M.D Load : 3.35 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 5.49 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 6.46 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 24.36 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 39.37 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 5.5 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1427 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.034 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.034

0.034 1.472 1.507 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 20
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-5F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-5F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-5F-1 Insulation Type : XLPE M.D Load : 18.99 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 31.08 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 36.57 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 24.36 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 39.37 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 31.1 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.8081 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.195 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.195

0.195 1.472 1.667 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 21
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-5F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-5F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-5F-2 Insulation Type : XLPE M.D Load : 12.21 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 19.98 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 23.51 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 24.36 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 39.37 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 20.0 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.5196 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.125 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.125

0.125 1.472 1.598 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 22
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMBE-B-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : LVP-1 Installation Method : AIR Voltage : 0.415 KV

To : SMBE-B-2 Insulation Type : XLPE M.D Load : 433.26 KW

Length (L) : 30.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 709.13 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 1000 A Circuit Breaker Type : ACB


Circuit Breaker Rating :
Ampere Frame = 1000 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑛
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 1176.47 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 3 // 4C X 185 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 1200 Cable Size (mm2) : 185 mm2 multicore

Number of Parallel Cables : 3 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 6.46 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 1.39 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 7.84 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 30.5 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 1020.0 A

1. 𝐼𝑧 ≥ 𝐼𝑛 1020.0 A ≥ 1000.0 A SUCCEED

2. 𝐼𝑛 ≤ 1.45 𝐼𝑧 1000.0 A ≤ 1479.0 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 2.4000 V mV/A/m = 0.24


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑛 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.578 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.578

0.578 0.093 0.672 %

Check : Acc. V.D ≤ 1.0 SUCCEED

Page 23
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-UPS-2 CU/PVC-FLEXIBLE CABLE

Cable / Load Data


Supply From : SMBE-B-2 Installation Method : AIR Voltage : 0.415 KV

To : UPS-2 Insulation Type : XLPE Rating : 400.0 KVA

Length (L) : 30.0 meter

Circuit Breaker Sizing

𝑅𝑎𝑡𝑖𝑛𝑔 𝐾𝑉𝐴
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 556.48 A
3 𝑋 𝐾𝑉

Rating , In = 800 A Circuit Breaker Type : ACB


Circuit Breaker Rating :
Ampere Frame = 800 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 654.68 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 2 // 4C X 240 mm2 CU/PVC-FLEXIBLE CABLE

Cable Type :
C.C.C = C.C.C X no. of Cables = 952 Cable Size (mm2) : 240 mm2 Single core

Number of Parallel Cables : 2 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 7.84 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 1.73 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 9.58 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 25.0 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 809.2 A

1. 𝐼𝑧 ≥ 𝐼𝑛 809.2 A ≥ 800.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 556.5 A ≤ 1173.3 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 1.6694 V mV/A/m = 0.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.402 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.402

0.402 0.672 1.074 %

Check : Acc. V.D ≤ 2.0 SUCCEED

Page 24
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-UDB-2 CU/PVC-FLEXIBLE CABLE

Cable / Load Data


Supply From : UPS-2 Installation Method : AIR Voltage : 0.415 KV

To : UDB-2 Insulation Type : XLPE M.D Load : 191.25 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 313.02 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 800 A Circuit Breaker Type : ACB


Circuit Breaker Rating :
Ampere Frame = 800 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 368.26 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 2 // 4C X 240 mm2 CU/PVC-FLEXIBLE CABLE

Cable Type :
C.C.C = C.C.C X no. of Cables = 952 Cable Size (mm2) : 240 mm2 multicore

Number of Parallel Cables : 2 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 9.58 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 0.58 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 10.15 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 23.6 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 809.2 A

1. 𝐼𝑧 ≥ 𝐼𝑛 809.2 A ≥ 800.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 313.0 A ≤ 1173.3 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.3130 V mV/A/m = 0.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.075 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.075

0.075 1.074 1.149 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 25
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-UPP-4TH CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : UDB-2 Installation Method : AIR Voltage : 0.415 KV

To : UPP-4TH Insulation Type : XLPE M.D Load : 47.00 KW

Length (L) : 90.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 76.93 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 80 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 90.50 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 50 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 170 Cable Size (mm2) : 50 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 10.15 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 45.21 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 55.36 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 4.3 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 144.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 144.5 A ≥ 80.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 76.9 A ≤ 209.5 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 6.0233 V mV/A/m = 0.87


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 1.451 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 1.451

1.451 1.149 2.601 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 26
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-UPP-5TH CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : UDB-2 Installation Method : AIR Voltage : 0.415 KV

To : UPP-5TH Insulation Type : XLPE M.D Load : 41.25 KW

Length (L) : 110.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 67.51 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 80 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 79.43 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 50 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 170 Cable Size (mm2) : 50 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 10.15 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 55.25 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 65.41 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 3.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 144.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 144.5 A ≥ 80.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 67.5 A ≤ 209.5 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 6.4611 V mV/A/m = 0.87


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 1.557 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 1.557

1.557 1.149 2.706 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 27
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-UPP-8TH CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : UDB-2 Installation Method : AIR Voltage : 0.415 KV

To : UPP-8TH Insulation Type : XLPE M.D Load : 14.50 KW

Length (L) : 180.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 23.73 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 27.92 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 25 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 110 Cable Size (mm2) : 25 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 10.15 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 155.88 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 166.04 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 1.4 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 93.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 93.5 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 23.7 A ≤ 135.6 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 6.4077 V mV/A/m = 1.5


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 1.544 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 1.544

1.544 1.149 2.693 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 28
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-UPP-B CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : UDB-2 Installation Method : AIR Voltage : 0.415 KV

To : UPP-B Insulation Type : XLPE M.D Load : 22.00 KW

Length (L) : 30.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 36.01 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 42.36 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 10.15 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 45.03 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 55.19 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 4.3 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 36.0 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 2.8086 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.677 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.677

0.677 1.149 1.826 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 29
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-UPP-G-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : UDB-2 Installation Method : AIR Voltage : 0.415 KV

To : UPP-G-1 Insulation Type : XLPE M.D Load : 76.00 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 124.39 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 125 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 160 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 146.34 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 10.15 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 6.93 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 17.08 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 14.0 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 125.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 124.4 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 1.4927 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.360 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.360

0.360 1.149 1.509 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 30
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-BF6 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : UDB-2 Installation Method : AIR Voltage : 0.415 KV

To : BF6 Insulation Type : XLPE M.D Load : 70.80 KW

Length (L) : 165.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 115.88 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 160 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 160 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 136.33 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 300 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 550 Cable Size (mm2) : 300 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 10.15 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 17.15 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 27.30 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 8.8 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 467.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 467.5 A ≥ 160.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 115.9 A ≤ 677.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 3.4416 V mV/A/m = 0.18


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.829 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.829

0.829 1.149 1.979 %

Check : Acc. V.D ≤ 2.0 SUCCEED

Page 31
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-BF6-TOB-01 BUSWAY

Feeder / Load Data


Supply From : BF6 Installation Method : AIR Voltage : 0.415 KV

To : BF6-TOB-01 Material : Copper M.D Load : 70.80 KW

Length (L) : 25.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 115.88 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓
Safety Factor = 1
Rating , In = 160 A Circuit Breaker Type : MCCB
Circuit Breaker Rating :
Ampere Frame = 160 A no. of Poles 3P
Busway Sizing
Selected Busway Size:

𝐵𝑢𝑠𝑤𝑎𝑦 𝑅𝑎𝑡𝑖𝑛𝑔 𝐴 ≥ 𝐼𝑛 Busway Rating (A) : 250 A

R (Ω/m) = 0.00023700
Busway Impedence :
X (Ω/m) = 0.00020500

Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 27.30 mΩ

𝑍𝐵𝑢𝑠𝑤𝑎𝑦 = (R × L)2 + (X × L)2 Zbusway 7.83E-06 mΩ

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐵𝑢𝑠𝑤𝑎𝑦 ZReceiving End 27.30 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 8.8 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Voltage Drop Criteria

1 - Individual V.D. :

V.Dbusway = 0.9473 V V/A/m = 0.000327


𝑉. 𝐷𝑏𝑢𝑠𝑤𝑎𝑦 (𝑉) = 𝑉/𝐴/𝑚 × 𝐼𝑏 × 𝐿 →
V.Dbusway = 0.2283 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝐹𝑒𝑒𝑑𝑒𝑟

V.D busway V.D upstream Feeder 0.2283

0.2283 1.979 2.207 %

Check : Acc. V.D ≤ 2.3 SUCCEED

Page 32
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-UPP-11TH CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF6-TOB-01 Installation Method : AIR Voltage : 0.415 KV

To : UPP-11TH Insulation Type : XLPE M.D Load : 22.75 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 37.24 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 80 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 43.81 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 25 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 110 Cable Size (mm2) : 25 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 27.30 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 8.66 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 35.96 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 93.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 93.5 A ≥ 80.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 37.2 A ≤ 135.6 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.5585 V mV/A/m = 1.5


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.135 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.135

0.135 2.207 2.342 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 33
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-BF6-TOB-02 BUSWAY

Feeder / Load Data


Supply From : BF6-TOB-01 Installation Method : AIR Voltage : 0.415 KV

To : BF6-TOB-02 Material : Copper M.D Load : 57.15 KW

Length (L) : 40.0 meter Power Factor : 0.85

Current Calculation

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 93.54 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓
Safety Factor = 1

Busway Sizing
Selected Busway Size:

Busway Rating (A) : 250 A

R (Ω/m) = 0.00023700
Busway Impedence :
X (Ω/m) = 0.00020500

Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 27.30 mΩ

𝑍𝐵𝑢𝑠𝑤𝑎𝑦 = (R × L)2 + (X × L)2 Zbusway 1.25E-05 mΩ

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐵𝑢𝑠𝑤𝑎𝑦 ZReceiving End 27.30 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 8.8 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Voltage Drop Criteria

1 - Individual V.D. :

V.Dbusway = 1.2235 V V/A/m = 0.000327


𝑉. 𝐷𝑏𝑢𝑠𝑤𝑎𝑦 (𝑉) = 𝑉/𝐴/𝑚 × 𝐼𝑏 × 𝐿 →
V.Dbusway = 0.2948 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝐹𝑒𝑒𝑑𝑒𝑟

V.D busway V.D upstream Feeder 0.2948

0.2948 2.207 2.502 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 34
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-UPP-15TH CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF6-TOB-02 Installation Method : AIR Voltage : 0.415 KV

To : UPP-15TH Insulation Type : XLPE M.D Load : 45.00 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 73.65 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 80 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 86.65 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 25 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 110 Cable Size (mm2) : 25 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 27.30 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 8.66 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 35.96 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 93.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 93.5 A ≥ 80.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 73.7 A ≤ 135.6 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 1.1048 V mV/A/m = 1.5


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.266 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.266

0.266 2.502 2.768 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 35
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-BF6-TOB-03 BUSWAY

Feeder / Load Data


Supply From : BF6-TOB-02 Installation Method : AIR Voltage : 0.415 KV

To : BF6-TOB-03 Material : Copper M.D Load : 30.15 KW

Length (L) : 40.0 meter Power Factor : 0.85

Current Calculation

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 49.35 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓
Safety Factor = 1

Busway Sizing
Selected Busway Size:

Busway Rating (A) : 250 A

R (Ω/m) = 0.00023700
Busway Impedence :
X (Ω/m) = 0.00020500

Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 27.30 mΩ

𝑍𝐵𝑢𝑠𝑤𝑎𝑦 = (R × L)2 + (X × L)2 Zbusway 1.25E-05 mΩ

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐵𝑢𝑠𝑤𝑎𝑦 ZReceiving End 27.30 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 8.8 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Voltage Drop Criteria

1 - Individual V.D. :

V.Dbusway = 0.6455 V V/A/m = 0.000327


𝑉. 𝐷𝑏𝑢𝑠𝑤𝑎𝑦 (𝑉) = 𝑉/𝐴/𝑚 × 𝐼𝑏 × 𝐿 →
V.Dbusway = 0.1555 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝐹𝑒𝑒𝑑𝑒𝑟

V.D busway V.D upstream Feeder 0.1555

0.1555 2.502 2.657 %

Check : Acc. V.D ≤ 2.8 SUCCEED

Page 36
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-UPP-22ND CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF6-TOB-03 Installation Method : AIR Voltage : 0.415 KV

To : UPP-22ND Insulation Type : XLPE M.D Load : 50.25 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 82.24 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 96.76 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 27.30 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 6.93 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 34.23 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 7.0 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 82.2 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.9869 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.238 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.238

0.238 2.657 2.895 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 37
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-UPS-3 CU/PVC-FLEXIBLE CABLE

Cable / Load Data


Supply From : SMBE-B-2 Installation Method : AIR Voltage : 0.415 KV

To : UPS-3 Insulation Type : XLPE Rating : 60.0 KVA

Length (L) : 30.0 meter

Circuit Breaker Sizing

𝑅𝑎𝑡𝑖𝑛𝑔 𝐾𝑉𝐴
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 83.47 A
3 𝑋 𝐾𝑉

Rating , In = 125 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 160 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 98.20 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/PVC-FLEXIBLE CABLE

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 Single core

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 7.84 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 20.78 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 28.63 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 8.4 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 125.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 83.5 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 3.0050 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.724 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.724

0.724 0.672 1.396 %

Check : Acc. V.D ≤ 2.5 SUCCEED

Page 38
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-UDB-3 CU/PVC-FLEXIBLE CABLE

Cable / Load Data


Supply From : UPS-3 Installation Method : AIR Voltage : 0.415 KV

To : UDB-3 Insulation Type : XLPE M.D Load : 18.60 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 30.44 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 125 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 160 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 35.82 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/PVC-FLEXIBLE CABLE

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 28.63 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 6.93 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 35.56 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 125.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 30.4 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.3653 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.088 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.088

0.088 1.396 1.484 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 39
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-UPP-G-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : UDB-3 Installation Method : AIR Voltage : 0.415 KV

To : UPP-G-2 Insulation Type : XLPE M.D Load : 10.50 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 17.19 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 20.22 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 35.56 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 50.57 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 4.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 17.2 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.4468 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.108 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.108

0.108 1.484 1.591 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 40
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-UPP-6TH CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : UDB-3 Installation Method : AIR Voltage : 0.415 KV

To : UPP-6TH Insulation Type : XLPE M.D Load : 10.50 KW

Length (L) : 135.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 17.19 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 20.22 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 35.56 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 202.65 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 238.21 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 1.0 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 17.2 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 6.0321 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 1.454 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 1.454

1.454 1.484 2.937 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 41
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-UPP-13TH CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : UDB-3 Installation Method : AIR Voltage : 0.415 KV

To : UPP-13TH Insulation Type : XLPE M.D Load : 5.00 KW

Length (L) : 210.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 8.18 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 9.63 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 35.56 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 315.23 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 350.79 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 0.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 8.2 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 4.4682 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 1.077 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 1.077

1.077 1.484 2.560 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 42
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-UPP-21ST CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : UDB-3 Installation Method : AIR Voltage : 0.415 KV

To : UPP-21ST Insulation Type : XLPE M.D Load : 5.00 KW

Length (L) : 250.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 8.18 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 9.63 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 35.56 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 375.28 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 410.83 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 0.6 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 8.2 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 5.3193 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 1.282 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 1.282

1.282 1.484 2.766 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 43
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-EPP-G CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMBE-B-2 Installation Method : AIR Voltage : 0.415 KV

To : EPP-G Insulation Type : XLPE M.D Load : 23.18 KW

Length (L) : 60.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 37.93 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 44.62 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 7.84 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 90.07 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 97.91 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 2.4 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 37.9 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 5.9172 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 1.426 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 1.426

1.426 0.672 2.097 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 44
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-EPP-7TH CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMBE-B-2 Installation Method : AIR Voltage : 0.415 KV

To : EPP-7TH Insulation Type : XLPE M.D Load : 0.22 KW

Length (L) : 170.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 0.35 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 0.42 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 7.84 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 255.19 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 263.03 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 0.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 0.4 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1563 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.038 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.038

0.038 0.672 0.709 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 45
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-EPP-12TH CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMBE-B-2 Installation Method : AIR Voltage : 0.415 KV

To : EPP-12TH Insulation Type : XLPE M.D Load : 0.22 KW

Length (L) : 210.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 0.35 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 0.42 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 7.84 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 315.23 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 323.08 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 0.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 0.4 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1930 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.047 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.047

0.047 0.672 0.718 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 46
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-EPP-17TH CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMBE-B-2 Installation Method : AIR Voltage : 0.415 KV

To : EPP-17TH Insulation Type : XLPE M.D Load : 0.22 KW

Length (L) : 230.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 0.35 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 0.42 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 7.84 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 345.26 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 353.10 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 0.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 0.4 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2114 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.051 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.051

0.051 0.672 0.723 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 47
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-EPP-22ND CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMBE-B-2 Installation Method : AIR Voltage : 0.415 KV

To : EPP-22ND Insulation Type : XLPE M.D Load : 0.18 KW

Length (L) : 255.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 0.29 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 0.35 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 7.84 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 382.78 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 390.63 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 0.6 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 0.3 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1953 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.047 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.047

0.047 0.672 0.719 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 48
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-CRAC-DX-01 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMBE-B-2 Installation Method : AIR Voltage : 0.415 KV

To : CRAC-DX-01 Insulation Type : XLPE M.D Load : 21.65 KW

Length (L) : 50.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 35.43 A Safety Factor = 1.5 I= 53.2 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 63 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 41.69 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 7.84 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 75.06 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 82.90 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 2.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 63.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 35.4 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 4.6065 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 1.110 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 1.110

1.110 0.672 1.782 %

Check : Acc. V.D ≤ 5.0 SUCCEED

Page 49
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-VRFOU-L03-01 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMBE-B-2 Installation Method : AIR Voltage : 0.415 KV

To : VRFOU-L03-01 Insulation Type : XLPE M.D Load : 25.60 KW

Length (L) : 115.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 41.90 A Safety Factor = 1.5 I= 62.8 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 80 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 49.29 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 25 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 110 Cable Size (mm2) : 25 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 7.84 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 99.59 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 107.44 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 2.2 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 93.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 93.5 A ≥ 80.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 41.9 A ≤ 135.6 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 7.2277 V mV/A/m = 1.5


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 1.742 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 1.742

1.742 0.672 2.413 %

Check : Acc. V.D ≤ 5.0 SUCCEED

Page 50
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-VRFOU-L04-01 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMBE-B-2 Installation Method : AIR Voltage : 0.415 KV

To : VRFOU-L04-01 Insulation Type : XLPE M.D Load : 25.60 KW

Length (L) : 135.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 41.90 A Safety Factor = 1.5 I= 62.8 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 80 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 49.29 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 25 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 110 Cable Size (mm2) : 25 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 7.84 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 116.91 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 124.76 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 1.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 93.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 93.5 A ≥ 80.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 41.9 A ≤ 135.6 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 8.4847 V mV/A/m = 1.5


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 2.045 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 2.045

2.045 0.672 2.716 %

Check : Acc. V.D ≤ 5.0 SUCCEED

Page 51
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-VRFOU-L05-01 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMBE-B-2 Installation Method : AIR Voltage : 0.415 KV

To : VRFOU-L05-01 Insulation Type : XLPE M.D Load : 18.81 KW

Length (L) : 140.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 30.79 A Safety Factor = 1.5 I= 46.2 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 63 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 36.22 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 7.84 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 210.16 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 218.00 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 1.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 63.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 30.8 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 11.2063 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 2.700 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 2.700

2.700 0.672 3.372 %

Check : Acc. V.D ≤ 5.0 SUCCEED

Page 52
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-VRFOU-L05-02 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMBE-B-2 Installation Method : AIR Voltage : 0.415 KV

To : VRFOU-L05-02 Insulation Type : XLPE M.D Load : 8.64 KW

Length (L) : 150.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 14.14 A Safety Factor = 1.5 I= 21.2 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 32 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 16.64 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 7.84 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 225.17 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 233.01 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 1.0 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 32.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 14.1 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 5.5151 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 1.329 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 1.329

1.329 0.672 2.001 %

Check : Acc. V.D ≤ 5.0 SUCCEED

Page 53
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-VRFOU-RF-01 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMBE-B-2 Installation Method : AIR Voltage : 0.415 KV

To : VRFOU-RF-01 Insulation Type : XLPE M.D Load : 25.60 KW

Length (L) : 300.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 41.90 A Safety Factor = 1.5 I= 62.8 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 80 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 49.29 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 7.84 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 207.85 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 215.69 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 1.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 80.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 41.9 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 15.0839 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 3.635 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 3.635

3.635 0.672 4.306 %

Check : Acc. V.D ≤ 5.0 SUCCEED

Page 54
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LVP-2 BUSWAY

Feeder / Load Data


Supply From : TR-1 Installation Method : AIR Voltage : 0.415 KV Transformer Data

To : LVP-2 Material : Copper M.D Load : 1009.43 KW Rating 1600 KVA

Length (L) : 10.0 meter Power Factor : 0.85 ZTR (S.C.) 6.00 %

Circuit Breaker Sizing

𝑅𝑎𝑡𝑖𝑛𝑔 𝐾𝑉𝐴
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 2225.93 A
3 𝑋 𝐾𝑉
Safety Factor = 1
Rating , In = 2500 A Circuit Breaker Type : ACB
Circuit Breaker Rating :
Ampere Frame = 2500 A no. of Poles 3P+N
Busway Sizing
Selected Busway Size:

𝐵𝑢𝑠𝑤𝑎𝑦 𝑅𝑎𝑡𝑖𝑛𝑔 𝐴 ≥ 𝐼𝑛 Busway Rating (A) : 2500 A

R (Ω/m) = 0.00001400
Busway Impedence :
X (Ω/m) = 0.00001100

Short Circuit Criteria


𝑉2 𝑍𝑇𝑅 (𝑠ℎ𝑜𝑟𝑡 𝑐𝑖𝑟𝑐𝑢𝑖𝑡 )
𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑇𝑅 = × ZSending End 6.46 mΩ
𝑇𝑅 𝑅𝑎𝑡𝑖𝑛𝑔 (𝐾𝑉𝐴) 100

𝑍𝐵𝑢𝑠𝑤𝑎𝑦 = (R × L)2 + (X × L)2 Zbusway 1.78E-07 mΩ

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐵𝑢𝑠𝑤𝑎𝑦 ZReceiving End 6.46 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 37.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Voltage Drop Criteria

1 - Individual V.D. :

V.Dbusway = 0.3873 V V/A/m = 0.000017


𝑉. 𝐷𝑏𝑢𝑠𝑤𝑎𝑦 (𝑉) = 𝑉/𝐴/𝑚 × 𝐼𝑏 × 𝐿 →
V.Dbusway = 0.0933 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝐹𝑒𝑒𝑑𝑒𝑟

V.D busway V.D upstream Feeder 0.0933

0.0933 0 0.093 %

Check : Acc. V.D ≤ 0.5 SUCCEED

Page 53
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-G CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-G-T Installation Method : AIR Voltage : 0.415 KV

To : LP-G Insulation Type : XLPE M.D Load : 4.26 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 6.98 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 8.21 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 18.93 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 33.94 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 7.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 7.0 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1814 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.044 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.044

0.044 0.926 0.970 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 54
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-G-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-G-T Installation Method : AIR Voltage : 0.415 KV

To : PP-G-1 Insulation Type : XLPE M.D Load : 28.07 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 45.93 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 63 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 54.04 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 18.93 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 33.94 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 7.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 63.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 45.9 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 1.1943 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.288 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.288

0.288 0.926 1.214 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 55
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-G-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-G-T Installation Method : AIR Voltage : 0.415 KV

To : PP-G-2 Insulation Type : XLPE M.D Load : 21.48 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 35.16 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 41.36 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 18.93 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 33.94 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 7.1 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 35.2 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.9141 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.220 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.220

0.220 0.926 1.146 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 56
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-M CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-M-T Installation Method : AIR Voltage : 0.415 KV

To : LP-M Insulation Type : XLPE M.D Load : 4.58 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 7.50 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 8.82 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 23.35 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 38.36 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.2 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 7.5 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1949 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.047 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.047

0.047 1.221 1.268 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 57
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-M-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-M-T Installation Method : AIR Voltage : 0.415 KV

To : PP-M-1 Insulation Type : XLPE M.D Load : 14.09 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 23.05 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 27.12 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 23.35 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 38.36 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.2 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 23.1 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.5994 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.144 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.144

0.144 1.221 1.365 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 58
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-M-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-M-T Installation Method : AIR Voltage : 0.415 KV

To : PP-M-2 Insulation Type : XLPE M.D Load : 11.76 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 19.25 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 22.64 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 23.35 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 38.36 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 6.2 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 19.2 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.5004 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.121 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.121

0.121 1.221 1.342 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 59
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-CRAC-CHW-01 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-M-T Installation Method : AIR Voltage : 0.415 KV

To : CRAC-CHW-01 Insulation Type : XLPE M.D Load : 9.00 KW

Length (L) : 55.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 14.73 A Safety Factor = 1.5 I= 22.1 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 25 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 17.33 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 23.35 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 82.56 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 105.91 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 2.3 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 25.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 14.7 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 2.1064 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.508 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.508

0.508 1.221 1.729 %

Check : Acc. V.D ≤ 5.0 SUCCEED

Page 60
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-6F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF2-TOB-01 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-6F-T Insulation Type : XLPE M.D Load : 22.70 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 37.16 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 43.72 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 11.65 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 25.51 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.4 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 37.2 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.8919 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.215 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.215

0.215 1.151 1.366 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 61
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-6F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-6F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-6F Insulation Type : XLPE M.D Load : 2.95 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 4.83 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 5.68 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 4.8 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1255 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.030 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.030

0.030 1.366 1.396 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 62
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-6F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-6F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-6F-1 Insulation Type : XLPE M.D Load : 9.65 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 15.79 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 18.57 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 15.8 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.4104 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.099 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.099

0.099 1.366 1.465 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 63
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-6F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-6F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-6F-2 Insulation Type : XLPE M.D Load : 10.11 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 16.55 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 19.47 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 16.5 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.4302 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.104 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.104

0.104 1.366 1.470 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 64
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-7F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF2-TOB-02 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-7F-T Insulation Type : XLPE M.D Load : 32.39 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 53.01 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 125 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 160 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 62.36 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 11.65 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 25.51 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.4 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 125.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 53.0 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 1.2721 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.307 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.307

0.307 1.274 1.581 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 65
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-7F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-7F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-7F Insulation Type : XLPE M.D Load : 3.44 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 5.62 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 6.61 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 5.6 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1462 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.035 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.035

0.035 1.581 1.616 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 66
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-7F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-7F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-7F-1 Insulation Type : XLPE M.D Load : 15.24 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 24.94 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 29.35 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 24.9 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.6485 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.156 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.156

0.156 1.581 1.737 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 67
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-7F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-7F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-7F-2 Insulation Type : XLPE M.D Load : 13.71 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 22.44 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 26.40 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 22.4 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.5834 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.141 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.141

0.141 1.581 1.721 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 68
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-8F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF2-TOB-03 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-8F-T Insulation Type : XLPE M.D Load : 36.98 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 60.53 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 71.21 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 11.65 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 25.51 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.4 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 60.5 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 1.4526 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.350 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.350

0.350 1.337 1.687 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 69
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-8F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-8F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-8F Insulation Type : XLPE M.D Load : 4.52 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 7.40 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 8.70 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 7.4 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1923 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.046 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.046

0.046 1.687 1.733 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 70
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-8F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-8F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-8F-1 Insulation Type : XLPE M.D Load : 12.29 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 20.11 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 23.66 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 20.1 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.5228 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.126 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.126

0.126 1.687 1.813 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 71
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-8F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-8F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-8F-2 Insulation Type : XLPE M.D Load : 20.18 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 33.02 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 38.85 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 33.0 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.8585 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.207 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.207

0.207 1.687 1.894 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 72
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-9F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF2-TOB-04 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-9F-T Insulation Type : XLPE M.D Load : 33.38 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 54.64 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 64.28 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 11.65 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 25.51 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.4 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 54.6 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 1.3113 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.316 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.316

0.316 1.357 1.673 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 73
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-9F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-9F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-9F Insulation Type : XLPE M.D Load : 4.12 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 6.74 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 7.93 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 6.7 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1752 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.042 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.042

0.042 1.673 1.716 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 74
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-9F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-9F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-9F-1 Insulation Type : XLPE M.D Load : 11.30 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 18.49 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 21.75 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 18.5 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.4807 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.116 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.116

0.116 1.673 1.789 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 75
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-9F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-9F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-9F-2 Insulation Type : XLPE M.D Load : 17.97 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 29.41 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 34.60 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 29.4 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.7647 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.184 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.184

0.184 1.673 1.858 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 76
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-10F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF2-TOB-05 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-10F-T Insulation Type : XLPE M.D Load : 36.56 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 59.84 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 70.39 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 11.65 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 25.51 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.4 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 59.8 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 1.4360 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.346 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.346

0.346 1.368 1.714 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 77
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-10F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-10F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-10F Insulation Type : XLPE M.D Load : 4.23 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 6.93 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 8.15 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 6.9 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1801 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.043 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.043

0.043 1.714 1.758 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 78
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-10F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-10F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-10F-1 Insulation Type : XLPE M.D Load : 12.50 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 20.45 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 24.06 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 20.5 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.5317 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.128 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.128

0.128 1.714 1.842 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 79
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-10F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-10F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-10F-2 Insulation Type : XLPE M.D Load : 19.83 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 32.46 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 38.18 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 32.5 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.8439 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.203 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.203

0.203 1.714 1.917 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 80
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-11F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF3-TOB-01 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-11F-T Insulation Type : XLPE M.D Load : 33.28 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 54.47 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 64.08 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 12.81 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 26.67 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.0 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 54.5 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 1.3072 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.315 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.315

0.315 1.332 1.647 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 81
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-11F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-11F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-11F Insulation Type : XLPE M.D Load : 4.12 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 6.74 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 7.93 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 6.7 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1753 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.042 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.042

0.042 1.647 1.690 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 82
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-11F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-11F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-11F-1 Insulation Type : XLPE M.D Load : 9.54 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 15.61 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 18.37 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 15.6 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.4060 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.098 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.098

0.098 1.647 1.745 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 83
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-11F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-11F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-11F-2 Insulation Type : XLPE M.D Load : 19.62 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 32.11 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 37.78 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 32.1 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.8349 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.201 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.201

0.201 1.647 1.848 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 84
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-12F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF3-TOB-02 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-12F-T Insulation Type : XLPE M.D Load : 36.69 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 60.06 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 70.66 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 12.81 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 26.67 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.0 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 60.1 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 1.4414 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.347 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.347

0.347 1.437 1.784 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 85
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-12F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-12F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-12F Insulation Type : XLPE M.D Load : 4.23 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 6.93 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 8.15 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 6.9 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1802 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.043 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.043

0.043 1.784 1.828 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 86
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-12F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-12F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-12F-1 Insulation Type : XLPE M.D Load : 12.29 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 20.11 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 23.66 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 20.1 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.5228 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.126 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.126

0.126 1.784 1.910 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 87
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-12F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-12F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-12F-2 Insulation Type : XLPE M.D Load : 20.18 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 33.02 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 38.85 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 33.0 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.8585 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.207 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.207

0.207 1.784 1.991 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 88
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-13F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF3-TOB-03 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-13F-T Insulation Type : XLPE M.D Load : 33.37 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 54.61 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 64.25 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 12.81 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 26.67 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.0 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 54.6 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 1.3106 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.316 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.316

0.316 1.485 1.801 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 89
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-13F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-13F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-13F Insulation Type : XLPE M.D Load : 4.10 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 6.71 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 7.90 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 6.7 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1745 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.042 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.042

0.042 1.801 1.843 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 90
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-13F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-13F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-13F-1 Insulation Type : XLPE M.D Load : 11.30 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 18.49 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 21.75 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 18.5 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.4807 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.116 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.116

0.116 1.801 1.917 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 91
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-13F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-13F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-13F-2 Insulation Type : XLPE M.D Load : 17.97 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 29.41 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 34.60 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 29.4 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.7647 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.184 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.184

0.184 1.801 1.985 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 92
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-14F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF3-TOB-04 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-14F-T Insulation Type : XLPE M.D Load : 33.23 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 54.39 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 63.98 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 12.81 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 26.67 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.0 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 54.4 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 1.3053 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.315 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.315

0.315 1.500 1.814 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 93
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-14F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-14F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-14F Insulation Type : XLPE M.D Load : 3.65 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 5.97 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 7.03 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 6.0 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1553 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.037 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.037

0.037 1.814 1.851 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 94
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-14F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-14F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-14F-1 Insulation Type : XLPE M.D Load : 13.95 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 22.83 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 26.86 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 22.8 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.5936 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.143 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.143

0.143 1.814 1.957 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 95
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-14F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-14F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-14F-2 Insulation Type : XLPE M.D Load : 15.63 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 25.58 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 30.10 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 25.6 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.6651 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.160 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.160

0.160 1.814 1.974 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 96
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-15F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF3-TOB-05 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-15F-T Insulation Type : XLPE M.D Load : 15.50 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 25.36 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 29.84 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 12.81 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 26.67 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.0 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 25.4 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.6087 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.147 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.147

0.147 1.504 1.651 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 97
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-15F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-15F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-15F Insulation Type : XLPE M.D Load : 2.97 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 4.86 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 5.72 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 4.9 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1264 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.030 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.030

0.030 1.651 1.681 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 98
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-15F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-15F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-15F-1 Insulation Type : XLPE M.D Load : 6.38 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 10.43 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 12.28 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 10.4 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2713 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.065 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.065

0.065 1.651 1.716 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 99
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-15F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-15F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-15F-2 Insulation Type : XLPE M.D Load : 6.15 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 10.07 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 11.84 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 10.1 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2617 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.063 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.063

0.063 1.651 1.714 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 100
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-16F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF4-TOB-01 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-16F-T Insulation Type : XLPE M.D Load : 15.92 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 26.06 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 30.65 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 11.65 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 25.51 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.4 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 26.1 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.6253 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.151 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.151

0.151 1.084 1.234 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 101
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-16F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-16F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-16F Insulation Type : XLPE M.D Load : 2.79 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 4.57 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 5.38 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 4.6 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1189 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.029 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.029

0.029 1.234 1.263 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 102
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-16F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-16F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-16F-1 Insulation Type : XLPE M.D Load : 6.68 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 10.93 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 12.85 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 10.9 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2841 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.068 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.068

0.068 1.234 1.303 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 103
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-16F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-16F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-16F-2 Insulation Type : XLPE M.D Load : 6.45 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 10.56 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 12.42 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 10.6 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2745 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.066 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.066

0.066 1.234 1.300 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 104
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-17F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF4-TOB-02 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-17F-T Insulation Type : XLPE M.D Load : 16.10 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 26.34 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 30.99 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 11.65 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 25.51 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.4 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 26.3 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.6323 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.152 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.152

0.152 1.162 1.314 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 105
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-17F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-17F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-17F Insulation Type : XLPE M.D Load : 2.97 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 4.86 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 5.72 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 4.9 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1264 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.030 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.030

0.030 1.314 1.344 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 106
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-17F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-17F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-17F-1 Insulation Type : XLPE M.D Load : 6.86 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 11.22 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 13.20 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 11.2 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2917 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.070 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.070

0.070 1.314 1.384 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 107
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-17F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-17F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-17F-2 Insulation Type : XLPE M.D Load : 6.27 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 10.26 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 12.07 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 10.3 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2668 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.064 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.064

0.064 1.314 1.378 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 108
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-18F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF4-TOB-03 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-18F-T Insulation Type : XLPE M.D Load : 24.81 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 40.60 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 47.76 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 11.65 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 25.51 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.4 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 40.6 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.9744 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.235 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.235

0.235 1.204 1.439 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 109
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-18F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-18F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-18F Insulation Type : XLPE M.D Load : 4.99 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 8.17 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 9.61 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 8.2 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2124 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.051 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.051

0.051 1.439 1.490 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 110
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-18F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-18F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-18F-1 Insulation Type : XLPE M.D Load : 12.14 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 19.86 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 23.37 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 19.9 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.5164 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.124 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.124

0.124 1.439 1.563 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 111
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-18F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-18F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-18F-2 Insulation Type : XLPE M.D Load : 7.68 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 12.57 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 14.79 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 12.6 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.3268 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.079 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.079

0.079 1.439 1.518 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 112
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-19F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF4-TOB-04 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-19F-T Insulation Type : XLPE M.D Load : 32.10 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 52.55 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 61.82 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 11.65 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 25.51 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.4 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 52.5 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 1.2611 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.304 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.304

0.304 1.218 1.522 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 113
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-19F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-19F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-19F Insulation Type : XLPE M.D Load : 3.96 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 6.49 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 7.63 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 6.5 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1687 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.041 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.041

0.041 1.522 1.563 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 114
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-19F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-19F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-19F-1 Insulation Type : XLPE M.D Load : 13.85 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 22.66 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 26.66 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 22.7 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.5892 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.142 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.142

0.142 1.522 1.664 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 115
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-19F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-19F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-19F-2 Insulation Type : XLPE M.D Load : 14.30 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 23.40 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 27.53 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 23.4 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.6083 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.147 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.147

0.147 1.522 1.669 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 116
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-20F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF4-TOB-05 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-20F-T Insulation Type : XLPE M.D Load : 15.50 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 25.36 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 29.84 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 11.65 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 25.51 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.4 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 25.4 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.6087 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.147 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.147

0.147 1.223 1.369 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 117
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-20F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-20F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-20F Insulation Type : XLPE M.D Load : 2.75 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 4.50 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 5.30 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 4.5 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1171 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.028 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.028

0.028 1.369 1.398 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 118
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-20F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-20F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-20F-1 Insulation Type : XLPE M.D Load : 6.63 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 10.85 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 12.77 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 10.9 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2821 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.068 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.068

0.068 1.369 1.437 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 119
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-20F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-20F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-20F-2 Insulation Type : XLPE M.D Load : 6.45 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 10.56 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 12.42 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 25.51 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 40.52 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.9 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 10.6 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2745 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.066 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.066

0.066 1.369 1.435 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 120
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-21F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF5-TOB-01 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-21F-T Insulation Type : XLPE M.D Load : 16.12 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 26.38 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 31.03 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 12.81 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 26.67 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.0 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 26.4 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.6331 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.153 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.153

0.153 1.269 1.421 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 121
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-21F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-21F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-21F Insulation Type : XLPE M.D Load : 2.99 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 4.90 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 5.76 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 4.9 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1273 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.031 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.031

0.031 1.421 1.452 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 122
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-21F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-21F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-21F-1 Insulation Type : XLPE M.D Load : 6.86 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 11.22 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 13.20 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 11.2 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2917 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.070 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.070

0.070 1.421 1.492 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 123
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-21F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-21F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-21F-2 Insulation Type : XLPE M.D Load : 6.27 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 10.26 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 12.07 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 10.3 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2668 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.064 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.064

0.064 1.421 1.486 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 124
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-22F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF5-TOB-02 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-22F-T Insulation Type : XLPE M.D Load : 16.35 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 26.76 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 31.49 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 12.81 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 26.67 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.0 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 26.8 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.6423 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.155 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.155

0.155 1.341 1.496 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 125
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-22F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-22F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-22F Insulation Type : XLPE M.D Load : 2.78 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 4.55 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 5.35 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 4.5 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1182 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.028 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.028

0.028 1.496 1.524 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 126
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-22F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-22F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-22F-1 Insulation Type : XLPE M.D Load : 6.84 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 11.20 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 13.17 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 11.2 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2911 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.070 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.070

0.070 1.496 1.566 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 127
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-22F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-22F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-22F-2 Insulation Type : XLPE M.D Load : 6.74 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 11.02 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 12.97 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 11.0 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2866 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.069 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.069

0.069 1.496 1.565 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 128
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-23F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF5-TOB-03 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-23F-T Insulation Type : XLPE M.D Load : 15.50 KW

Length (L) : 20.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 25.36 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 29.84 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 12.81 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 13.86 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 26.67 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 9.0 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 25.4 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.6087 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.147 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.147

0.147 1.379 1.526 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 129
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-23F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-23F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-23F Insulation Type : XLPE M.D Load : 2.97 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 4.86 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 5.72 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 4.9 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.1264 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.030 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.030

0.030 1.526 1.557 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 130
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-23F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-23F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-23F-1 Insulation Type : XLPE M.D Load : 6.38 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 10.43 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 12.28 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 10.4 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2713 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.065 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.065

0.065 1.526 1.591 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 131
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-23F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-23F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-23F-2 Insulation Type : XLPE M.D Load : 6.15 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 10.07 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 11.84 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 26.67 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 41.68 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 5.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 10.1 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2617 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.063 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.063

0.063 1.526 1.589 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 132
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-24F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF5-TOB-04 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-24F-T Insulation Type : XLPE M.D Load : 24.98 KW

Length (L) : 5.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 40.88 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 48.10 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 12.81 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 3.46 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 16.27 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 14.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 40.9 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2453 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.059 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.059

0.059 1.394 1.453 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 133
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-24F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-24F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-24F Insulation Type : XLPE M.D Load : 4.73 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 7.74 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 9.11 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 16.27 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 31.28 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 7.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 7.7 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2013 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.048 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.048

0.048 1.453 1.502 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 134
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-24F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-24F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-24F-1 Insulation Type : XLPE M.D Load : 7.70 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 12.59 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 14.82 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 16.27 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 31.28 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 7.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 12.6 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.3275 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.079 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.079

0.079 1.453 1.532 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 135
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-24F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-24F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-24F-2 Insulation Type : XLPE M.D Load : 12.56 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 20.55 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 24.18 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 16.27 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 31.28 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 7.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 20.5 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.5343 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.129 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.129

0.129 1.453 1.582 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 136
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-SMDB-25F-T CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : BF5-TOB-05 Installation Method : AIR Voltage : 0.415 KV

To : SMDB-25F-T Insulation Type : XLPE M.D Load : 25.03 KW

Length (L) : 5.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 40.97 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 100 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 48.21 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 35 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 150 Cable Size (mm2) : 35 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 12.81 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 3.46 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 16.27 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 14.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 127.5 A

1. 𝐼𝑧 ≥ 𝐼𝑛 127.5 A ≥ 100.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 41.0 A ≤ 184.9 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2458 V mV/A/m = 1.2


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.059 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.059

0.059 1.401 1.461 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 137
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-LP-25F CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-25F-T Installation Method : AIR Voltage : 0.415 KV

To : LP-25F Insulation Type : XLPE M.D Load : 5.25 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 8.59 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 10.11 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 16.27 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 31.28 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 7.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 8.6 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.2234 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.054 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.054

0.054 1.461 1.514 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 138
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-25F-1 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-25F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-25F-1 Insulation Type : XLPE M.D Load : 7.65 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 12.52 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 14.73 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 16.27 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 31.28 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 7.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 12.5 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.3255 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.078 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.078

0.078 1.461 1.539 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 139
CABLE / BREAKER SIZING SHEET
Proj.No. :
According to IEC, BS ,KAHRAMAA & QCS 2014 3103

Feeder No:. F-PP-25F-2 CU/XLPE/SWA/PVC

Cable / Load Data


Supply From : SMDB-25F-T Installation Method : AIR Voltage : 0.415 KV

To : PP-25F-2 Insulation Type : XLPE M.D Load : 12.14 KW

Length (L) : 10.0 meter Power Factor : 0.85

Circuit Breaker Sizing

𝑀𝑎𝑥. 𝐷𝑒𝑚. 𝐾𝑊
𝐼𝑏 𝐷𝑒𝑠𝑖𝑔𝑛 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = = 19.86 A
3 𝑋 𝐾𝑉 𝑋 𝑝. 𝑓

Rating , In = 40 A Circuit Breaker Type : MCCB


Circuit Breaker Rating :
Ampere Frame = 100 A no. of Poles 3P
Derating Factors
Ca = For Ambient Temprature Ca = 1
Cg = For Grouped Cables Cg = 0.85
Cr = For Burial depth Cr = 1 N/A
Cs = For Soil resistivity Cs = 1 N/A
𝐼𝑏
𝐶. 𝑓. (𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟) = 𝐶𝑎 × 𝐶𝑔 × 𝐶𝑟 × 𝐶𝑠= 0.85 𝐼𝑡 𝑇𝑎𝑟𝑔𝑒𝑡 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = = 23.37 A
𝐶. 𝑓.

Cable Sizing

𝐶. 𝐶. 𝐶 (𝐶𝑎𝑏𝑙𝑒 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐶𝑎𝑟𝑟𝑦𝑖𝑛𝑔 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦) ≥ 𝐼𝑡 1 // 4C X 16 mm2 CU/XLPE/SWA/PVC

Cable Type :
C.C.C = C.C.C X no. of Cables = 81 Cable Size (mm2) : 16 mm2 multicore

Number of Parallel Cables : 1 4C


Short Circuit Criteria

𝑍𝑆𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 ZSending End 16.27 mΩ

(𝑚𝑉/𝐴/𝑚)×L
𝑍𝐶𝑎𝑏𝑙𝑒 = ZCable 15.01 mΩ
3 𝑁𝑜.𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠

𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑 = 𝑍𝑠𝑒𝑛𝑑𝑖𝑛𝑔 𝐸𝑛𝑑 + 𝑍𝐶𝑎𝑏𝑙𝑒 ZReceiving End) 31.28 mΩ

V
𝐼𝑆.𝐶. (𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑) = (𝐾𝐴) IS.C. (Receiving End) 7.7 KA
3 × 𝑍𝑅𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝐸𝑛𝑑
Protection Criteria

𝐼𝑧 𝐷𝑒𝑟𝑎𝑡𝑒𝑑 𝐴𝑚𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐶. 𝐶. 𝐶 × 𝐶. 𝑓. → Iz = 68.9 A

1. 𝐼𝑧 ≥ 𝐼𝑛 68.9 A ≥ 40.0 A SUCCEED

2. 𝐼𝑏 ≤ 1.45 𝐼𝑧 19.9 A ≤ 99.8 A SUCCEED

Voltage Drop Criteria

1 - Individual V.D. :

𝑉/𝐴/𝑚 V.Dcable = 0.5164 V mV/A/m = 2.6


𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 (𝑉) = × 𝐼𝑏 × 𝐿 →
𝑁𝑜. 𝑜𝑓 𝐶𝑎𝑏𝑙𝑒𝑠 V.Dcable = 0.124 %

2 - Accumulated V.D. :

𝐴𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝑉. 𝐷 = 𝑉. 𝐷𝑐𝑎𝑏𝑙𝑒 + 𝑉. 𝐷𝑢𝑝𝑠𝑡𝑟𝑒𝑎𝑚 𝑐𝑎𝑏𝑙𝑒

V.D cable V.D upstream cable 0.124

0.124 1.461 1.585 %

Check : Acc. V.D ≤ 3.0 SUCCEED

Page 140