Manhole notes:

1) 225mm (unless otherwise stated) thick C12/15 Mass Concrete Foundations.

10 FLEXIBLE
11,22 10 2) Preformed half circle channel pipes. The pipeline may, where practicable, be
FLEXIBLE JOINT, 12 laid through the manhole and the crown cut out to half diameter, provided flexible
JOINT, 12 joints are situated on each side no further than 600mm from the inner face of
manhole wall.

21, 23 HANDHOLDS, 17 3) Manhole Construction.


HANDHOLDS For Surface Water Manholes high-density blocks to CI.S10 of IS.20 Part 1:1987 or

min.
C25/30 insitu concrete.

max.
Block work shall be bedded and jointed using mortar to IS406. Beds and vertical
21,23 CONCRETE PLATFORM SHALL BE joints shall be completely filled with
7,17,22 LEVEL WITH THE TOP OF THE PIPE. mortar as the blocks are laid.
Joints shall be flush pointed as the work proceeds.

FLOW
All Foul Manholes must be faced in Solid Engineering Brick (min. Class A or B), or
DIA. insitu consrete for 1m above Benching Level.
Brick to be bonded to block work using English Garden Wall Bond.
24 4) Relieving arch formed by 215x103x65 solid engineering brick Class A or B as
per drawing. Relieving arches used in brick or block work manholes extend over full
thickness of wall. A Double Arch is to be formed for pipe diameters greater than
SHAFT SECTION 600mm.
CONCRETE PLATFORM SHALL BE
5) Benching and pipe channel pipe surround - C16/20 concrete.
LEVEL WITH THE TOP OF THE PIPE.
HANDHOLD, 17 TAPER SECTION (OR 6) Benching finishes in 2:1 sand-cement mortar with a smooth trowel finish, at 1
REDUCING SLAB) FLEXIBLE in 30 slope towards channel.

FLEXIBLE JOINTS, 12 7) Standard rungs at 300c/c vertically and galvanized to the latest version of B.S

min.
JOINTS, 12 729 or equivalent. Note: Steps Iron are not acceptable.

FLOW 13 15, 16, 17, 22 8) 600mm square ope in roof slab.

9) Precast R.C Roof Slab shall be 225mm (unless otherwise stated) thick in Class
2 C25/30, with 40mm cover to steel.

24 10) 1 to 2 courses of solid engineering bricks CI.B to I.S.91:1983 set in 1:3


(cement and mortar).
18 DIA. 11) Class D400 or E600 manhole cover and frame to IS/EN 124. 150mm deep
frame for roads and 100mm deep for footpaths and green areas. Non-rock design,
closed keyways, manufactured from spheroidal graphite cast iron (ductile cast
iron), 600 x 600 (600 diam.) clear opening cover and frame coated in bitumen or
other approved material, cover to have a minimum mass of 140kg/m², frame
SECTION X-X MAIN CHAMBER PLAN ON STRAIGHT INVERT bearing area shall be 80,000mm² min, frames shall be designed to prevent covers
PLAN ON STRAIGHT INVERT SECTION (WITHOUT COVER SLAB) falling into manhole. Frames shall be bedded on approval mortar to manufactures
13 instructions.
(WITHOUT COVER SLAB)
HANDHOLD 17 12) Short length pipe and pipe joint external to manhole shall not exceed 600mm
INTEGRAL IN-SITU 20N/20mm CONCRETE BASE WALLS, BENCHING AND BASE from the inner face of manhole wall.
SLAB WITH PRECAST CHANNEL AS SHOWN OR IN-SITU FORMED INVERT AS
13) Toe holes of 230mm minimum in depth and galvanized steel safety railings to
ALTERNATIVE. WALLS TO EXTEND 150mm BEYOND OUTER FACES OF ALTERNATIVE DETAIL be provided in benching of sewers greater than 525mm diameter and depth to

W
CHAMBER RING. ALTERNATIVELY PRECAST CONCRETE CHAMBER RINGS

FLO
invert >3m for access to invert.
(REDUCING SLAB INSTEAD OF TAPER SECTION)

FLO
MAY BE BEDDED IN MORTAR OR ON IN-SITU 20N/20mm CONCRETE BASE FLOW
14) A safety chain is to be provided on pipes that exceed 450mm in diameter. Mild

W
SLAB 300mm GREATER IN DIAMETER THAN CHAMBER RINGS. safety chain shall be 10mm nominal size grade M(H) non-calibrated chain, type 1,
2 complying with B.S.4942 Part 2 or equivalent.
12
15) When depth of manholes to invert is greater than 3.0m ladders shall be used
instead of rungs to B.S.4211 or equivalent except that stringers should be not less
than 65 x 12mm in section and rungs 25mm in diameter. Fixed ladders should
5, 6 HANDHOLDS 18
12 meet the dimensional requirements of B.S.4211 or equivalent.

SECTION X-X 16) Ladder stringers should be adequately supported from the manhole wall at
1 intervals of not more than 2.0m stringers should be bolted to cleats to facilitate
renewal.

75 RAD 17) All ladders, rungs, handrails, safety chains, etc. shall be hot dip galvanized to
B.S.729 or equivalent.
IN-SITU GRADE 20N/20mm CONCRETE BASE WALLS, BENCHING AND BASE SLAB WITH
PLATFORM PRECAST CHANNEL AS SHOWN OR IN-SITU FORMED INVERT AS ALTERNATIVE. WALLS TO 18) Pipe should be cut flush with the inside surface of the manhole wall so that the
13 14, 17 EXTEND 150mm BEYOND OUTER FACES OF CHAMBER RING. ALTERNATIVELY PRECAST channel extends the full length of the manhole (except for pre-cast manholes).

CONCRETE CHAMBER RINGS MAY BE BEDDED IN MORTAR OR ON AN IN-SITU 20N/20mm PLATFORM 19) Position of 910 square ope in intermediate roof slab.
2 All manholes shall be watertight to the satisfaction of the Engineer.
CONCRETE BASE SLAB 300mm GREATER IN DIAMETER THAN CHAMBER RINGS. Formwork to Reinforced concrete and Mass concrete shall comply with Class 2,
ONE OR MORE PIPE BENDS Section 6.2.7, B.S.8110: Part 1: 1997.
(IF REQUIRED) AS GIVEN 12 Finish to the top of slabs shall comply with Type A, Section 6.2.7,B.S.8110: Part 1:
1997.
IN THE PIPE SCHEDULE. Plan dimensions of manholes are based on block work having a co-ordinating size
of 450 x 225 x 100.
ONE OR MORE PIPE BENDS
SECTION Y-Y 12 5, 6 Manholes are designed to B.S.8005 and wall thickness to LS.325 block work design
(IF REQUIRED) code taking granular fill pressure and H.B. surcharge.
Reinforcement to slabs to Engineers details.

20) For manholes >3m depth to invert use C25/30 insitu concrete. Reinforcing
mesh ref. A393 @ 6.16kg/m to be fixed at mid point of wall. Additional
PLAN ON CURVED INVERT 12
75 RAD reinforcement to be supplied over pipe crown.
(WITHOUT COVER SLAB)
21) For Pre cast manholes, chamber walls & cover slab to be constructed to IS EN
1917 and IS 420 2004.
MANHOLE TYPE J (PRECAST CONCRETE MANHOLES) PLAN ON CURVED INVERT
13 14, 17 22) Manhole openings to be situated furthest from the nearest Carriageway.
(WITHOUT COVER SLAB)
DEPTH TO INVERT 1m TO 3m 2
Manhole steps / access to be positioned to allow viewing of oncoming traffic.

23) For bedding and sealing of Chamber rings, the top ring (to Pre-cast cover slab)
and bottom ring to be bedded with cement mortar. For intermediate rings, joints to
be sealed with approved pre-formed jointing strip.

24) Pre cast manholes to be surrounded with a minimum of 150mm thick Grade
C16/20 concrete.

SECTION Y-Y General Notes

i) All brick to be Solid Engineering Brick Class A or B.


MANHOLE TYPE K (PRECAST CONCRETE MANHOLES) ii) For pipe diameter >750mm use manhole with internal diameter size = pipe size
+ 1 metre + 300mm.
DEPTH TO INVERT 3m TO 6m
iii) Distance from the top rung of the ladder to ground level must be a maximum of
500mm.

25) This drawing to be read in conjunction with all other relevant engineer's
drawings and the Great Dublin Regional Code of Practice V6.0.

26) Any queries or discrepancies are to be referred to the engineer immediately.

27) Figured dimensions only to be read. All dimensions to be checked on site.

INITIAL ISSUE SW 15.03.21 P01


Description: Drawn Date: Rev.:

Client:

DATA AND POWER HUB SERVICES LTD


MANHOLE TYPE A
Project:

GIS SUBSTATION COMPOUND AND


TRANSFORMERS / MV SWITCH ROOM
COMPOUND AT GRANGE CASTLE

Clients Representative:

J. B. Barry and Partners Limited


Consulting Engineers
Classon House
Dundrum Business Park Tel: +353 1 485 1400
Dundrum Road email: info@jbbarry.ie
Dublin 14 web: www.jbbarry.ie

Drawn By: Date:


SW JAN 2021

Checked By: Date: Approved By: Date:


SW JAN 2021 GF JAN 2021

Internal Project Ref: Stage: Suit:


19229 PLANNING S3

Drawing Title:

TYPICAL SURFACE WATER


Table of Concrete Compressive Strength Classes
DRAINAGE DETAILS
MANHOLE TYPE C Required Grade
(Characteristic cube strength, N/mm²)
Compressive Strength Class
Cylinder/Cube

15 C12/15

20 C16/20
Scales:
MANHOLE TYPE B 25
30
C20/25
C25/30
1:40 @ A1

Drawing. No.: Rev:

19229-JBB-00-XX-DR-C-01503 P1

You might also like