YSM AIR HANDLING UNIT

ACOUSTIC PERFORMANCE SPECIFICATION

Project Name : LEGEND BAY-HA LONG


Order number :
Project Date :
Software Name&Ver/Date: YSM V3.6.4.GW/2023-06-21
Prepared By :
Unit Tag General Info. Qty Air Flow (m3/h) ESP (Pa) TSP (Pa)
PAU-14F-01 YSM50P-1730-D-L 1 43416 500 1762.7
Sound Data Summary

Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYQ-710K
Lw1 99 95 105 97 97 93 85 78 107.4 dB
LwA1 73 79 96 94 97 94 86 77 101.6 dB(A)
Fan sound power level OUT: SYQ-710K
Lw1 99 95 105 97 97 93 85 78 107.4 dB
LwA1 73 79 96 94 97 94 86 77 101.6 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 97.5 93 99 90 88 82 74 59 102.4 dB
LwA3 71.3 76.9 90.4 86.8 88 83.2 75 57.9 94 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 99 95 105 97 97 93 85 78 107.4 dB
LwA4 72.8 78.9 96.4 93.8 97 94.2 86 76.9 101.7 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.

Lw2 90.7 80.5 91.8 82.6 83.3 74.9 51.5 39.4 95.1 dB
LwA2 64.5 64.4 83.2 79.4 83.3 76.1 52.5 38.3 87.5 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.

Distance: 1000mm Cladding surface: 160m²

Lp2 68.6 58.4 69.7 60.5 61.2 52.8 29.4 17.3 73 dB


LpA2 42.4 42.3 61.1 57.3 61.2 54 30.4 16.2 65.4 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with GB/T 9068, on a block-shaped
measurement surface that envelops the unit casing.

Distance: 1000mm Cladding surface: 160m²

Lp2 77.3 73.3 83.3 75.3 75.3 71.3 63.3 56.3 85.7 dB
LpA2 51.1 57.2 74.7 72.1 75.3 72.5 64.3 55.2 80 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.

Page 1,Total 2 Pages Print Date:7/25/2023


YSM AIR HANDLING UNIT
ACOUSTIC PERFORMANCE SPECIFICATION

Project Name : LEGEND BAY-HA LONG


Order number :
Project Date :
Software Name&Ver/Date: YSM V3.6.4.GW/2023-06-21
Prepared By :
Unit Tag General Info. Qty Air Flow (m3/h) ESP (Pa) TSP (Pa)
PAU-14F-01 YSM50P-1730-D-L 1 43416 500 1007.2
Sound Data Summary

Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-710K
Lw1 93 94 89 92 86 85 83 78 99 dB
LwA1 66 77 80 89 86 86 84 77 93.1 dB(A)
Fan sound power level OUT: SYD-710K
Lw1 93 94 89 92 86 85 83 78 99 dB
LwA1 66 77 80 89 86 86 84 77 93.1 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 92.5 93.5 87 90 83.5 82 80 71 97.8 dB
LwA3 66.3 77.4 78.4 86.8 83.5 83.2 81 69.9 90.7 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 93 94 89 92 86 85 83 78 99 dB
LwA4 66.8 77.9 80.4 88.8 86 86.2 84 76.9 93.1 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.

Lw2 80.4 74.2 72.8 74.3 69.3 64.3 46.9 38.5 82.9 dB
LwA2 54.2 58.1 64.2 71.1 69.3 65.5 47.9 37.4 74.6 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.

Distance: 1000mm Cladding surface: 160m²

Lp2 58.3 52.1 50.7 52.2 47.2 42.2 24.8 16.4 60.8 dB
LpA2 32.1 36 42.1 49 47.2 43.4 25.8 15.3 52.5 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with GB/T 9068, on a block-shaped
measurement surface that envelops the unit casing.

Distance: 1000mm Cladding surface: 160m²

Lp2 71.3 72.3 67.3 70.3 64.3 63.3 61.3 56.3 77.3 dB
LpA2 45.1 56.2 58.7 67.1 64.3 64.5 62.3 55.2 71.4 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.

Page 2,Total 2 Pages Print Date:7/25/2023