Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

[7-1 Error Code and Preliminary Error Code Lists ]

7 Troubleshooting Using Error Codes

7-1 Error Code and Preliminary Error Code Lists

Searched unit

Error

Remote controller
Prelimi-
(prelim-
Error nary

Outdoor unit
inary) Error code definition Notes

LOSSNAY
Indoor unit
Code error
detail
code
code

1
4300
5
0403 4305 Serial communication error/Panel communication error O O (page 177)
6
4306
(Note)
0404 - - Indoor unit EEPROM abnormality O (page 178)
0900 - - Test run O
1102 1202 - Discharge temperature fault O (page 179)
1301 - - Low pressure fault O (page 180)

7 Troubleshooting Using Error Codes


1302 1402 - High pressure fault O (page 181)
1500 1600 - Refrigerant overcharge O (page 182)
- 1605 - Preliminary suction pressure fault O
2500 - - Drain sensor submergence O (page 183)
2502 - - Drain pump fault O (page 185)
2503 - - Drain sensor (Thd) fault O O (page 187)
2600 - - Water leakage O (page 188)
2601 - - Water supply cutoff O (page 188)
3121 - - Out-of-range outside air temperature O (page 189)
4102 4152 - Open phase O (page 190)
4106 - - Transmission power supply fault O (page 191)
4109 - - Fan operation status detection error O (page 191)
4115 - - Power supply signal sync error O (page 192)
4116 - - RPM error/Motor error O O (page 192)
4121 4171 í Function setting error O (page 193)
4124 - í Electric system not operate due to damper abnormality O (page 194)
[0] Backup operation O
[108] Abnormal bus voltage drop (Software detection) O (page 195)

4220 4320 [109] Abnormal bus voltage rise (Software detection) O (page 196)
4225 4325
[110] BUS voltage error (Hardware detection) O (page 197)
4226 4326
(Note) (Note) [111] Logic error O (page 197)
[112] Logic error O (page 197)
[131] Low bus voltage at startup O (page 198)
4230 4330 [125] Heatsink overheat protection O (page 198)
4240 4340 - Overload protection O (page 199)

HWE14110 - 173 - GB
[7-1 Error Code and Preliminary Error Code Lists ]

Searched unit

Error

Remote controller
Prelimi-
(prelim-
Error nary

Outdoor unit
inary) Error code definition Notes

LOSSNAY
Indoor unit
Code error
detail
code
code

[0] Backup operation O


[101] IPM error O (page 200)
4250 4350
4255 4355 [104] Short-circuited IPM/Ground fault O (page 201)
4256 4356 [105] Overcurrent error due to short-circuited motor O (page 202)
(Note) (Note)
[106] Instantaneous overcurrent (S/W detection) O (page 202)
[107] Overcurrent (effective value)(S/W detection) O (page 202)
4260 - - Heatsink overheat protection at startup O (page 203)
Return air temperature
O (page 204)
(TH21)
5101 1202 - Temperature sensor fault
OA processing unit inlet
O (page 204)
temperature (TH4)
Indoor unit pipe tempera-
O (page 204)
ture (TH22)
OA processing unit pipe
5102 1217 - Temperature sensor fault O (page 204)
temperature (TH2)
HIC bypass circuit outlet
O (page 205)
temperature (TH2)
Indoor unit gas-side pipe
O (page 204)
temperature (TH23)
OA processing unit gas-side
5103 1205 00 Temperature sensor fault O (page 204)
pipe temperature (TH3)
Pipe temperature at heatex-
O (page 205)
changer outlet (TH3)
OA processing unit intake
O (page 204)
air temperature (TH1)
(page 204)
Detectable
Outside temperature
5104 1202 - Temperature sensor fault O only by the All-
(TH24)
Fresh type in-
door units
Outdoor unit discharge tem-
O (page 205)
perature (TH4)
Accumulator inlet tempera-
5105 1204 - Temperature sensor fault O (page 205)
ture (TH5)
HIC circuit outlet tempera-
5106 1216 - Temperature sensor fault O (page 205)
ture (TH6)
5107 1221 - Temperature sensor fault Outside temperature (TH7) O (page 205)
[0] Backup operation O
5110 1214 Heatsink temperature
01 Temperature sensor fault O (page 206)
(THHS)
5201 - - High-pressure sensor fault (63HS1) O (page 206)

HWE14110 - 174 - GB
[7-1 Error Code and Preliminary Error Code Lists ]

Searched unit

Error

Remote controller
Prelimi-
(prelim-
Error nary

Outdoor unit
inary) Error code definition Notes

LOSSNAY
Indoor unit
Code error
detail
code
code

[0] Backup operation O


[115] ACCT sensor fault O (page 207)
5301 4300 [117] ACCT sensor circuit fault O (page 207)
[119] Open-circuited IPM/Loose ACCT connector O (page 208)
[120] Faulty ACCT wiring O (page 208)
[0] Backup operation O

5305 4305 [132] Position detection error at startup O (page 209)


5306 4306 [133] Position detection error during operation O (page 209)

7 Troubleshooting Using Error Codes


[134] RPM error before startup O (page 210)
5701 - - Loose float switch connector O (page 210)
6201 - - Remote controller board fault (nonvolatile memory error) O (page 211)
6202 - - Remote controller board fault (clock IC error) O (page 211)
6600 - - Address overlap O O O O (page 212)
6601 - - Polarity setting error O (page 212)
6602 - - Transmission processor hardware error O O O O (page 213)
6603 - - Transmission line bus busy error O O O O (page 214)
Communication error between device and transmission
6606 - - O O O O (page 214)
processors
6607 - - No ACK error O O O O (page 215)
6608 - - No response error O O O O (page 222)
6831 - - MA controller signal reception error (No signal reception) O O (page 223)
MA remote controller signal transmission error (Synchro-
6832 - - O O (page 224)
nization error)
MA remote controller signal transmission error (Hard-
6833 - - O O (page 225)
ware error)
MA controller signal reception error (Start bit detection
6834 - - O O (page 226)
error)
6840 - - A control communication reception error O (page 227)
6841 - - A control communication synchronism not recover O (page 227)
A control communication transmission/reception hard-
6842 - - O (page 228)
ware trouble
6843 - - A control communication start bit detection error O (page 229)
6846 - - Start-up time over O (page 230)
7100 - - Total capacity error O (page 231)
7101 - - Capacity code setting error O O O (page 232)
7102 - - Wrong number of connected units O (page 233)
7105 - - Address setting error O (page 234)
7106 - - Attribute setting error O (page 234)
Connection information signal transmission/reception er-
7110 - - O (page 235)
ror

HWE14110 - 175 - GB
[7-1 Error Code and Preliminary Error Code Lists ]

Searched unit

Error

Remote controller
Prelimi-
(prelim-
Error nary

Outdoor unit
inary) Error code definition Notes

LOSSNAY
Indoor unit
Code error
detail
code
code

7111 - - Remote controller sensor fault O O (page 235)


7113 - - Function setting error (improper connection of CNTYP) O (page 236)
7117 - - Model setting error O (page 237)
7130 - - Incompatible unit combination O (page 238)

The last digit in the check error codes in the 4000's and 5000's and two-digit detail codes indicate if the codes apply to com-
pressor inverter on fan inverter.
Example
Code 4225 (detail code 108): Bus voltage drop in the fan inverter system
Code 4230 : Heatsink overheat protection in the compressor inverter system

The last digit Inverter system


0 or 1 Compressor inverter system
5 or 6 Fan inverter system

Temper-
Overload Current effective ature
Series Current peak value
INV board Outdoor units protection value error protec-
name error (Apeak)
Imax (Arms) (Arms) tion TOL
(°C)
PUHY-P200YKA 15 23 38 100
PUHY-P250YKA 15 23 38 100
PUHY-P300YKA 27 33 56 100
INV20Y Standard PUHY-P350YKA 27 33 56 100
PUHY-P400YKA 27 33 56 100
PUHY-P450YKA 27 33 56 100
PUHY-P500YKA 27 33 56 100

HWE14110 - 176 - GB