Professional Documents
Culture Documents
Mevn - Mã L I Pucy Yka
Mevn - Mã L I Pucy Yka
Searched unit
Error
Remote controller
Prelimi-
(prelim-
Error nary
Outdoor unit
inary) Error code definition Notes
LOSSNAY
Indoor unit
Code error
detail
code
code
1
4300
5
0403 4305 Serial communication error/Panel communication error O O (page 177)
6
4306
(Note)
0404 - - Indoor unit EEPROM abnormality O (page 178)
0900 - - Test run O
1102 1202 - Discharge temperature fault O (page 179)
1301 - - Low pressure fault O (page 180)
4220 4320 [109] Abnormal bus voltage rise (Software detection) O (page 196)
4225 4325
[110] BUS voltage error (Hardware detection) O (page 197)
4226 4326
(Note) (Note) [111] Logic error O (page 197)
[112] Logic error O (page 197)
[131] Low bus voltage at startup O (page 198)
4230 4330 [125] Heatsink overheat protection O (page 198)
4240 4340 - Overload protection O (page 199)
HWE14110 - 173 - GB
[7-1 Error Code and Preliminary Error Code Lists ]
Searched unit
Error
Remote controller
Prelimi-
(prelim-
Error nary
Outdoor unit
inary) Error code definition Notes
LOSSNAY
Indoor unit
Code error
detail
code
code
HWE14110 - 174 - GB
[7-1 Error Code and Preliminary Error Code Lists ]
Searched unit
Error
Remote controller
Prelimi-
(prelim-
Error nary
Outdoor unit
inary) Error code definition Notes
LOSSNAY
Indoor unit
Code error
detail
code
code
HWE14110 - 175 - GB
[7-1 Error Code and Preliminary Error Code Lists ]
Searched unit
Error
Remote controller
Prelimi-
(prelim-
Error nary
Outdoor unit
inary) Error code definition Notes
LOSSNAY
Indoor unit
Code error
detail
code
code
The last digit in the check error codes in the 4000's and 5000's and two-digit detail codes indicate if the codes apply to com-
pressor inverter on fan inverter.
Example
Code 4225 (detail code 108): Bus voltage drop in the fan inverter system
Code 4230 : Heatsink overheat protection in the compressor inverter system
Temper-
Overload Current effective ature
Series Current peak value
INV board Outdoor units protection value error protec-
name error (Apeak)
Imax (Arms) (Arms) tion TOL
(°C)
PUHY-P200YKA 15 23 38 100
PUHY-P250YKA 15 23 38 100
PUHY-P300YKA 27 33 56 100
INV20Y Standard PUHY-P350YKA 27 33 56 100
PUHY-P400YKA 27 33 56 100
PUHY-P450YKA 27 33 56 100
PUHY-P500YKA 27 33 56 100
HWE14110 - 176 - GB