PROJECT HVAC Load Calculations FLOOR South Eest Section

LOCATION Karachi(Pakistan) SPACE REFERENCE NICU


AREA ( SqFt) (WxH) 3,580.00
Falce Ceiling Height (Ft) 7.80
126.00 Volume (CuFt) 27,924.00
Area or Sun Gain or Estimate for Summer
Item Factor (U) Btu/Hour Watts
Quantity Temp. Diff. Design Conditions DB (°F) WB (°F) RH (%) HR (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 100.00 82.00 47.00 136.50
ROOM SENSIBLE HEAT Room (InDoor) 75.00 63.00 59.00 145.00
Solar Gain - Glass Area ΔT U Difference Δ 25.00 19.00 12.00 8.50
Glass - N SqFt x x 0.00
Glass - NE SqFt x x 0.00
Glass - E SqFt x x 0.00 By Pass Factor (BF) = 0.12
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.88
Glass - S 120.00 SqFt x 26.00 x 0.59 1,834.56 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person No = = 0.00
Glass - W SqFt x x 0.00 CFM Per SqFt Sqft x = 0.00
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 2.00
Skylight SqFt x x 0.00 CFM Cu.ft 27,924.00 x 2.00 x1/60 = 930.80
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x F x 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.00 Open Doors x cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S 485.60 SqFt x 37.00 F x 0.23 4,132.46 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.96
Roof SqFt x F x 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (°F) =
All Glass 120.00 SqFt x 26.00 F x 0.59 1,834.56 Selected ADP (°F) = 54.60
Partition SqFt x F x 0.00 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 17.95
Floor SqFt x F x 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 2,880.24 CFM
Infiltration CFM x 25.00 T.Diff x 0.00 Dehumidified Rise x 1.08
Outside Air 930.80 CFM x 25.00 x 3,015.79
Internal Heat = 1,353.71 L/s
People 26.00 Nos. x 140.00 Btu/Hour Per Person 3,640.00 TOTAL HEAT CAPACITY
Lighting 3,580.00 SqFt x 0.88 W/SqFt x 3.41 10,742.86 Grand Total Heat = 6.62 TR
Equipments 1.00 6,850.00 Watts x 3.41 23,358.50
Power kW/Hp x 0.00
Sub Total 48,558.73
Factor 5-15% 7,283.81
Effective Room Sensible Heat 55,842.54 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 6.62 TR
Infiltration CFM x 8.50 Gr/Lb x 0.68 0.00 12,000.00
Outside Air 930.80 CFM x 8.50 Gr/Lb x BFx0.68 645.60
People 26.00 Nos. x 107.50 Btu/Hour Per Person 2,795.00
Sub Total 2,149.40
Factor 2.5 - 15% 322.41
Effective Room Latent Heat 2,471.81 2.00
EFFECTIVE ROOM TOTAL HEAT 58,314.35
OUTSIDE AIR HEAT
Sensible 930.80 CFM x 25.00 F(TD) x CF x 1.08 22,115.81 3.00
Latent 930.80 CFM x 8.50 Gr/Lb x CF x 0.68 4,734.42 4.00
OUTSIDE AIR TOTAL HEAT 17,381.39 Notes:
GRAND SUB-TOTAL HEAT 75,695.74
Factor 1 - 3% 3,784.79
GRAND TOTAL HEAT 79,480.52
TMBH 79.48
TKW 23.05
TSMBH 77,958.35
TSKW 22,607.92
TONS=GRAND TOTAL HEAT/12000 6.62