Quick Guide
Issue: 01
Date: 2018-08-10
1
2 Overview
Dimensions of the PDU5000 (H x W x D): 131.85 mm x 482.60 mm x 502.70 mm
2
4 Installing the PDU5000
Plan the installation position for the PDU5000 based on the following figure.
3
6 Check Before Power-On
No. Check Item Check Result
1 All cables are correctly connected based on the Schematic Diagram. □Passed □Failed
2 Ground cables are securely connected. □Passed □Failed
Redundant parts of the ground cables and power cables are cut off
3 □Passed □Failed
instead of coiled.
Power cables and ground cables are routed and bundled separately from
4 □Passed □Failed
other types of cables.
5 All circuit breakers are OFF. □Passed □Failed
6 The appearance is intact without any damage. □Passed □Failed
7 All labels are correct, clear, and complete. □Passed □Failed
The surrounding area of the cabinet contains no waste tape, cable ties,
8 □Passed □Failed
paper, or packing materials.
All bolts are tightened, especially the bolts used for electrical connection.
9 Flat washers and spring washers are installed properly in the correct □Passed □Failed
sequence.
Cables are bundled neatly, and cable ties are secured evenly and
10 □Passed □Failed
properly in the same direction.
11 Cables are routed for ease of future maintenance and expansion. □Passed □Failed
12 There is no unnecessary adhesive tape or cable tie on the cables. □Passed □Failed
Exposed parts near the wiring terminals and lugs are wrapped in PVC
13 □Passed □Failed
insulation tape or heat shrinking tubing.
Flat and spring washers are properly installed on each bolt of a wiring
14 □Passed □Failed
terminal.
The power and signal cables are routed in accordance with the weak-
15 □Passed □Failed
and strong-current cable routing specifications and the cable routing plan.
7 Power-On Commissioning
1. Turn on the SPD circuit breaker.
2. Turn on the external power input circuit breaker.
3. Turn on the UPS input switch.
4. Set UPS parameters after UPS startup, then start the inverter, and turn on the UPS output switch.
5. Turn on all output circuit breakers of the PDU5000 in sequence and check that the output voltage
is normal by using a multimeter.
6. After checking that the parameters are normal, turn off all the circuit breakers one by one and
disconnect the power supply.
NOTE
When switching on the circuit breakers, observe whether there is any abnormal phenomenon, such
as sparks or unsmooth switching on/off.
4
Elementary diagram of the PDU5000
XT1 XT2
QFS-2 1 L QF7-1 1 L
Main Input QF7
QF2-4 2 N N 2 N
QF1-1 3 L QF6-1 3 L
UPS Input QF6
QFBP-4 4 N N 4 N
QF2-1 5 L QF5-1 5 L
UPS Output QF5
N 6 N N 6 N
QF4-1 7 L
QF4
N 8 N
XT3 QF3-1 9 L
QF3
FS-COM 1 N/A N 10 N
SPD:DO
QFS-11 2 N/A
SM-COM 3 COM
UPS:MBS
SM-NC 4 NC
5
8 Routine Maintenance
Operation
Item Interval Reference Standard Troubleshooting
Guide
1. The cables are not
Connections of damaged.
Visual Take measures
input and output Monthly 2. The terminals are intact,
observation depending on the severity.
power cables secure, and free from
spark signs and rust.
Appearance of
Visual Take measures
power distribution Quarterly The appearance is intact.
observation depending on the severity.
components
Measure the Check that the air
Operating temperature: –
Operating temperature conditioner and
5°C to +40°C
temperature and Quarterly and humidity dehumidifier in the
Relative humidity: 5%–
humidity using a point equipment room function
95% RH
thermometer. properly.
Dust on the Check The white paper that you
If the white paper is dirty,
surface of the Yearly whether there use to wipe the equipment
clean the PDU5000.
PDU5000 is dust. is clean.
9 Troubleshooting
Symptom Possible Causes Troubleshooting Measures
• The SPD circuit breaker is
not turned on.
• Check that the SPD circuit breaker is turned
The surge • The SPD ground cable is
on.
protection function not connected.
• Check that the SPD ground cable is connected.
fails. • The surge protection
• Replace the surge protection module
module is abnormal. The
SPD window is red.
• Use a multimeter to check whether there is a
The rear-end
• The switch trips abnormally. short circuit. Turn on the switch again, and
device power input
• The UPS is faulty. check whether the system is overloaded.
is abnormal.
• Restart the UPS. If the UPS is faulty, replace it.
The UPS does not • The output power cable is
report faults, but not securely connected. • Check the output power cable connection.
has no output • The output circuit breaker • Replace the circuit breaker.
voltage. is abnormal.
10 Parts Replacement
NOTICE
Only engineers certified by Huawei or its agents are allowed to perform operations. Otherwise,
personal injury or equipment damage may occur, and the device faults caused are beyond the
warranty scope of Huawei.
6
10.1 Replacing a Circuit Breaker
Prerequisites:
• Tools: electroprobe, insulation gloves, flat-head screwdriver, Phillips screwdriver, multimeter
• A spare circuit breaker of the same model is available and functional.
NOTICE
Procedure:
Step 1 Turn off the upstream user switch. Remove the input power cable, UPS input and output
power cables, cabinet power cable, and signal cable from the rear of the PDU5000, and mark the
connection positions.
NOTICE
After removing cables, wrap exposed terminals with insulation tape and do not block cable
labels. If cable labels are blocked, cables may be connected incorrectly later.
Step 2 Remove the PDU5000, and remove the top and front covers of the PDU5000.
Step 3 (Optional) Remove the copper bar of the circuit breaker on PDU5000.
7
10.2 Replacing a Surge Protection Module
DANGER
• Do not replace a surge protection module during a thunderstorm.
• Before replacing a surge protection module, wear protective insulation gloves.
Prerequisites:
• Tools: protective insulation gloves, electroprobe
• Material: A spare surge protection module of the same model is
available and functional.
Procedure:
Step 1 Switch the SPD circuit breaker to OFF.
Step 2 Remove the protective panel of the SPD.
Step 3 Detect the L1, L2, L3, and N voltages to
the PE using an electrical tester pen to check
whether there is voltage, as shown in the right
figure, and verify that the faulty SPD has no
voltage before replacing the faulty surge protection
module.
Step 4 Hold the faulty surge protection module Measuring the voltage
and pull it out, as shown in the following figure.
DANGER
8
11 Technical Specifications
Item Specifications
Operating temperature –5°C to +40°C
Storage temperature –40°C to +70°C
Relative humidity 5%–95% RH (non-condensing)
Altitude ≤ 4000 m
Rated operating frequency 50 Hz
Rated operating voltage 220 V AC
Installation mode Installed inside a cabinet
Protection level IP20