Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

DES C R IPTION Sure-Lites

The APELSQ is an UL 924 listed emergency light with a minimum of 90 Type


Catalog #
minutes of run time. Key features include LED heads, a no maintenance
nickel cadmium battery and a five year fixture warranty. The square
LED heads are fully adjustable to maximize design flexibility while the Project
compact form factor optimizes aesthetics. The universal j-box mounting
pattern and snap fit housing construction significantly reduce installation Date
Comments
time.

Prepared by

SP EC IFIC A TION FEA T U R E S

E le c t r i c a l - Suitable for wall or ceiling Cod e Co mplian ce


- Dual Voltage Input 120/277VAC, mount applications - Not for sale in California
60Hz - Universal J-box mounting - UL 924 Damp Location Listed
- Line-latching pattern - Life Safety NFPA 101
- Brownout circuit - Keyhole mounting slots - NEC/OSHA
- Low Voltage Disconnect - Available in white - Most State and Local Codes
- Overload/Short Circuit Protection - Operating temperature
- Test Switch/Power connector Ba tte ry range 10 °C to 40 °C
facilitates installation - Sealed nickel cadmium
- 3.6V, 1.0W DC Long Lasting LED - Maintenance-free, long-life
Heads - Full recharge time: 24 hrs (max.) Head/Lamp Data
- Long Life LED Emergency Heads
H ou s i n g C o n s t r u cti on - Two heads standard
- All components are injection- - Fully adjustable AP2SQLED
molded, color stable, high impact - High impact thermoplastic
thermoplastic material - Matches housing finish SERIES
- Designer textured finish
standard Warranty
- Five-year warranty
- Seven-year prorated battery SEALED NICKEL CADMIUM
warranty BATTERY
EMERGENCY LIGHTING
5⅜” LED

2½” 1¾”

49/16” 311/16”
-20˚to40˚C
10˚to 50˚C
operating
temperature
range

OR D ER ING INFOR M A T I O N 101/16”


12”
SAMPLE NUMBER: AP2SQLED

Series Battery Heads Source Catalog number

AP = All Pro _ = Nickel cadmium battery 2SQ = Two square heads LED = LED AP2SQLED ENERGY DATA

Model AP2SQLED
Input watts:
120V = 1.8W
277V = 1.8W
Input amps:
120V = 0.02
277V = 0.01

TD505057EN
December 10, 2020 7:58 AM
AP2SQLED SERIES

TEC H NIC A L D A TA

LE D H e a d s L i ne - L a tch ed Lo w Vo ltage Discon n ect


The Long Life LED Emergency Heads are the All Pro Emergency’s line-latched electronic When the battery’s terminal voltage falls below
most economical Emergency Light solution circuitry makes installation easy and 80% of the rated voltage, the low voltage
for general purpose applications. Designed economical. A labor efficient AC-activated circuitry disconnects the lighting load. The
specifically for emergency lighting applications load switch prevents the lamps from turning disconnect remains in effect until normal utility
with horizontal and vertical adjustment by on during installation to a non-energized AC power is restored, preventing deep battery
rotating the LED Emergency Heads to desired circuit. Linelatching eliminates the need for a discharge.
direction. contractor’s return to a job site to connect the
batteries when the building’s main power is T est S witch /P ower In d ica t o r Lig h t
H o u sin g C o n s t r u c t i o n permanently turned on. A test switch permits the activation of the
Rugged, durable, injection molded emergency circuit for a complete operational
thermoplastic materials are used throughout Sol i d- State Charg er system check. The Power Indicator Light
the All Pro Series Emergency Lighting Units. Supplied with a 120/277 VAC, voltage regulated provides assurance that the AC power is on.
All structural components are designed with solid-state charger. Upon restoration of AC
reinforcing ribs to add additional rigidity and to current after a power failure, the charger S ealed Nickel Cadmiu m B at t er y
maximize structural integrity. These materials provides a high charge rate. The charge circuit All Pro Emergency sealed nickel cadmium
are impact and scratch resistant, and they have reacts to the condition of the battery and alters batteries are maintenance free with a life
been UV stabilized to resist discoloration due the rate of charge in order to maintain peak expactancy of 10 years.
to age and ultraviolet radiation. All components battery capacity and maximize battery life.
are designed to be of snap-fit construction - no Solid-state construction recharges the battery Warranty
mechanical fasteners - to facilitate installation following a power failure in accordance with All-Pro Emergency products are backed by a
in under 5-minutes. The mounting plate UL 924. five-year warranty.
has keyhole mounting slots and a universal
mounting pattern for quick, efficient installation. Brownou t Circuit
Any components required for installation The brownout circuit in All Pro Emergency units
(wirenuts, wire leads, etc.) are all included with monitor the flow of AC current to the unit and
each unit. AP2SQLED is suitable for activates the emergency lighting system when
wall or ceiling mount applications. Housings are a predetermined reduction of AC power occurs.
available in white. This dip in voltage will cause most ballasted
fixtures to extinguish causing loss of normal
lighting even though a total power failure has
not occurred.

Cooper Lighting Solutions © 2020 Cooper Lighting Solutions


1121 Highway 74 South All Rights Reserved.
Peachtree City, GA 30269 TD505057EN
P: 770-486-4800 Specifications and dimensions December 10, 2020 7:58 AM
www.cooperlighting.com subject to change without notice.

You might also like