DATA SHEET: TEMBREAK 2 E250-SF MCCB

MCCB Electrical Characteristics to IEC 60947-2, EN 60947-2, JIS C 8201-2-1 ANN.1, NEMA AB-1
Frame Reference Quantity Unit C ondition TB2 Lite 250
Max In (A ) of Frame 250
Model E250
Number of Poles 3, 4
Type SF

Nominal c urrent ratings


In (A) 50°C 125,150,175
200,225,
250

E lec tric al charac teris tic s


Rated operational voltage Ue (V) AC 50/60 Hz 525
DC 250
Rated insulation voltage Ui (V) 690
Rated impulse voltage U imp (kV) 8

Ultimate breaking capacity I cu (kA) 690V AC -


(IEC, JIS, AS/NZS) 525V AC 7.5
440V AC 15
400/415V AC 25
220/240V AC 35
250V DC 15

Service breaking capacity I cs (kA) 690V AC -


(IEC, JIS, AS/NZS) 525V AC 6
440V AC 12
400/415V AC 19
220/240V AC 27
250V DC 12

Rated breaking capacity (NEMA) (kA) 480V AC 10


240VAC 35

P rotec tion
Fixed thermal, fixed magnetic

Adjustable thermal, adjustable magnetic -


Utilisation category A

Ins tallation
Front connection (FC)
Extension bar (FB) •
Cable clamp (FW) •
Rear connection (RC) •
Plug-in (PM) -
DIN rail mounting (DA) -
Dimensions height (mm) 165
width (mm) 3 pole 105
4 pole 140
depth (mm) 68
Weight weight (kg) 3 pole 1.5
4 pole 1.9

Operation
Direct Opening Action
Toggle operation
Door mounted (HS) / Breaker mounted handle (HB) •
Motor operation •

Endurance Electrical cycles 415V AC 6,000


Mechanical cycles 18,000

Standard • Optional - Not Available

Page 1 of 3
DATA SHEET: TEMBREAK 2 E250-SF MCCB
Outline Dimensions E250-SF
ASL: Arrangement Standard Line HL: Handle Frame Centre Line CL: Handle Centre Line

Front connected ø9
Preparation of With extension bars Drilling plan

11(max.)
conductor (optional) (front view)
Interpole barrier Mounting hole
3P 4P 25(max.) 3P 4P
max.t7 HL (removable) HL
Interpole barrier Conductor
(removable) Conductor overlap, max
overlap, max 28
101

35 35 35 35 35 4 3P 4P

11.5

11.5
24 23 23
Mounting hole M8 screw
HL HL HL HL

30.5

30.5
19

19
98 98

C C C C C
144

102

L L L L L

126
165
50

50
22

46 7 M4 0.7

30.5
30.5
70 35 35 35

23
60 23
105 105 Tapped hole
68 23 23 6.8 23

11.5
11.5

140 10.5 95 97 48.5 48.5 48.5 Note: For the extension bars, Straight bars or
ø11 ø11
M4 0.7 120 169 Spread bars can be supplied.
Mounting screw

Rear connected
Drilling plan (front view) Panel cutout (front view)

Mounting plate 4P 4P
Detail of 3P 4P 3P
(max. t3.2) 3P
connecting part HL HL
ø24
HL 52.5
HL
6

R1
102

C Conductor C C
144

126

L L L

52
144
50

overlap, max
25 22
7

ø9
20

M4 0.7 M4 0.7
9

6 13 16 Stud can be turned Mounting screw 35 35 Tapped hole 50


45° or 90° 100
60 72 35 35 35 35 35 35 35 35
68 107 Panel cutout dimensions shown give an
allowance of 1.0mm around the handle
escutcheon.

Page 2 of 3
DATA SHEET: TEMBREAK 2 E250-SF MCCB
Time/Current Characteristic Curves
E250-SF

2
hour

1
125 1625 325
40
150 1950 390
30
175 2275 455
20
200 2600 520
225 2925 585
10 250 2750 550
minute

1
Max.
40
30
20

10

6
Tripping Time

2 Min.

0.6
second

0.4

0.2

0.1

0.06
0.04

0.02

0.01

0.005
100
125

200

300

400
500

700

1000

1500

2000

3000

4000
5000

8000

Percent Rated Current

Page 3 of 3