IF SEPARATE TRANSFORMERS CANNOT BE INSTALLED, THE CUSTOMER MUST PROPERLY SET UP THE
MACHINE BEARING IN MIND THAT, WITH A SINGLE TRANSFORMER, THE REMAINING LOADS RUN ON THE FOLLOWING CABLES ARE RECOMMENDED FOR SUPPLYING ELECTRICAL POWER TO THE DRIVE MOTOR
DEFORMED VOLTAGE WAVEFORMS. (1 x 250kW):
- 2 SCREENED RUBBER-INSULATED THREE-CORE CABLES 2x(3x120mm2 +S) + GND (1x120mm2) OUT-OF-
SCREEN
TRANSFORMER SPECIFICATIONS FOR OPERATING ON DEFORMED CURRENT AND VOLTAGE
WAVEFORMS.
USE 2" TIE CABLES WITH FLEXIBLE METAL CONDUITS TO LINK THE MOTOR SIDE
THE TRANSFORMER MUST BE SUITABLY RATED REMEMBERING THAT IT IS USED TO OPERATE FREQUENCY
CONVERTERS. IN ADDITION, PROVIDE FOR 4 VOLTAGE TAPS ON THE PRIMARY COIL; I.E. 2x (+2.5%) AND 2x (-
2.5%) AND 1 Vcc TAP (5-7%).
THE TRANSFORMER MUST BE SUITABLY SET UP FOR HANDLING HARMONIC WAVE CURRENTS TYPICAL OF
INVERTERS.
AN ELECTROSTATIC SCREEN, FITTED WITH GROUND TERMINAL, MUST BE PROVIDED FOR BETWEEN THE
PRIMARY AND SECONDARY COILS. THE MMC-MODULE ELECTRIC CONTROL PANELS (SACMI SUPPLIED) DO SACMI CANNOT ACCEPT RESPONSIBILITY FOR MALFUNCTIONS OR FAULTS DUE TO NON-OBSERVANCE OF
NOT NEED NEUTRAL WIRES. THE ABOVE SPECIFICATIONS
SACMI DISCOURAGES CUSTOMERS FROM PLACING THE TRANSFORMER ON THE MILL SERVICE PLATFORM.
IF THE CUSTOMER HOWEVER INTENDS TO INSTALL THE TRANSFORMER ON THE SERVICE PLATFORM IN
SPITE OF SACMI RECOMMENDATIONS, TAKE CARE TO ADOPT ALL THE SAFETY MEASURES RECOMMENDED
BY SAFETY REGULATIONS CURRENTLY IN FORCE. IN ANY CASE, NEVER INSTALL THE TRANSFORMER
BELOW THE WATER STORAGE TANK.
FOR FURTHER INFORMATION ON THE ELECTRICAL WIRING, REFER TO MANUAL SMC08510408.
AS FAR AS THE POWER LINE TO THE ELECTRICAL CABINETS IS CONCERNED, ALWAYS USE A RUBBER-
INSULATED COPPER CORE CABLE FOR EACH CABINET (2x3x1x150mm2 ) (TWO UNIPOLAR AND PARALLEL
CONNECTED 150 mm2 CORDS FOR EACH PHASELINE) + GROUND. CONSIDER A POWER LINE THAT CAN BE UP
TO 100m IN LENGTH AND RUNNING ON A 380/400/415V 50Hz ELECTRICITY SUPPLY. CORRECT PHASE
COINCIDENCE ALONG THE ENTIRE PATH SO AS TO COMPENSATE FOR ANY INDUCTANCE OR MUTUAL
INDUCTANCE IN THE CABLES THEMSELVES (UNIFORM VOLTAGE DROP). AS AN ALTERNATIVE, USE A 700-
AMP COPPER BUS BAR (FOR EACH CABINET) TO SUPPLY THE ELECTRICAL POWER. COPPER BUS BAR IS
PREFERABLE TO ALUMINUM ONES IS AS IT ENSURES HIGHER RESISTANCE AND IMPROVED FLOW OF
CURRENTS
REMEMBER THAT WHEN TWO OR MORE UNIPOLAR CABLES ARE LAID IN PARALLEL IN A THREE-PHASE MAXIMUM EXTERNAL TEMPERATURE +40°C
SYSTEM, THE CONDUCTORS FOR ONE PHASE MUST BE ARRANGED IN STAGGERED ORDER IN RELATION TO
THOSE OF THE OTHER PHASELINES SO AS TO COMPENSATE FOR ANY INDUCTANCE OR MUTUAL
INDUCTANCE PRESENT (CABLES STAGGERED)
NOTE: WITH ELECTRONIC CONVERTERS INSTALLED, ALWAYS CHECK THAT THE GROUND FAULT CIRCUIT
INTERRUPTERS PROVIDED ALONG THE POWER LINE ARE OF THE TYPE "B" (IF USED IN THE MAIN LOW-
VOLTAGE CABINET, MANUFACTURED AT CUSTOMER EXPENSES) IN COMPLIANCE WITH CEI EN 60947-2