SOLAR PV
Computation & Design
Internal
Daily
Load Qty. Power Total Power Hrs. used Consumption
LED
Step1 LIGHTS 8 7W 56W 8 HRS 448WH
WASHING
MACHINE 1 180W 180W 3 HRS 540WH
Internal
Losses
(constant)
Total Daily
PV Power = Consumption x 1.3
Sun Peak Hrs.
Step2 10,528wh
= x 1.3 = 3421 .6w
SIZING OF PV 4 hrs
(average peak
PANELS sunlight hours perday)
PV power
USE: 9 pcs - 400w No. of PV Panels =
Rating of PV
JA Solar
Monocrystalline
Solar Panels 3421 .6 w
= = 8.554 ≈ 9pcs
400 w
Will vary depending on
Solar panel type and size.
(JA Solar)
Internal
ALL MOTOR LOADS MULTIPLY BY 2 OR 3
EFAN : 180w x 2 = 360w
REF : 300w x 3 = 900w
AIRCON : 1000w x 3 = 3000w
Step3
WASHING = 540w
SIZING OF 180w x 3
MACHINE :
INVERTER ALL NON-MOTOR LOADS MULTIPLY BY 1.3
Internal
Total Daily Consumption
Battery
= D.O.D x Efficiency x System
Capacity
voltage
10,528wh
= = 516.08 Ah
Step4 .5 x .85 x48v
SIZING OF (50% level before the battery
capacity drops) Lead-Acid Battery
BATTERY BATTERY CONNECTION:
516.08 Ah
= = 2.58 ≈3
200 Ah
Indicated on specs.
Internal
BATTERY CONNECTION:
Step4 516.08 Ah
= = 2.58 ≈3
200 Ah
SIZING OF
BATTERY
No. of System Voltage
=
Series Voltage Rating ofBattery
3 strings of 4
Parallel Series
Internal
MPPT- Maximum PowerPoint Tracking
Step5
Total PV power
SIZING OF Icc =
System Voltage
SOLAR
CHARGE 400w/pc x 9 pcs
=
CONTROLLER 48v
USE:1-FANG- = 75A
FLEX-150V80A
Internal
PV CONNECTION :
9
= = 3
3
Parallel
3 strings of 3
Series
Internal
BREAKER AND
WIRE SIZING
Internal
BREAKER SIZING SOLAR PANEL TO SCC
Formula : I = I x 125%
1pcs – 400w JA solar
Voc = 49.5v
DC MCB Rating (I) = (I) PV Total Imp x 125% Safety
Isc = 10.28A factor or continuous duty
Vmp = 41.17v
Imp = 9.72A
Total Vmp = 123.51v
Total Imp = 29.16A
Formula : I = I x 125%
Internal
WIRE SIZING SOLAR PANEL TO SCC VDI Method (voltage drop index)
1pcs – 400w JA solar current x distance (ft)
3pcs – 400w JA solar
+ - + - Vmp = 123.51v Vdi =
Voc = 49.5v Imp = 9.72A %voltage Drop x voltage
Isc = 10.28A VDI AWG
Vmp = 41.17v 1 16
3pcs – 400w JA solar
%voltage drop = 2 (DC)
Imp = 9.72A 2 14 + - + - + - Vmp = 123.51v
%voltage drop = 1 (AC)
Imp = 9.72A
3 12
1m = 3.28ft.
5 10 3pcs – 400w JA solar
8 8 + - + - + - Vmp = 123.51v
Imp = 9.72A
Current: 29.16A
12 6 voltage: 123.51v
20 4 distance: 10m(32.8ft)
34 2 vd%: 2
49 1/0
62 2/0 9pcs – 400w JA solar 29.16A x 32.8 (ft)
78 3/0
Vmp = 123.51v Vdi = = 3.87
Imp = 29.16A
2x 123.51V
99 4/0
Internal
BREAKER SIZING SCC TO BATTERY BANK
Formula : I = ( P / V )
DC MCB Rating (I) = (P) Total PV wattage / V System
Nominal Voltage
48v 600Ah
Internal
BREAKER SIZING BATTERY BANK TO INVERTER
Formula : I = ( P / V )
Lead Acid DC MCB Rating (I) = (P) Inverter wattage / V System
Battery
Nominal Voltage
48v 600Ah
Inverter 6KW
DC MCB (I) = 125A DC Breaker
48V
Internal
VDI AWG
Battery Bank to inverter
WIRE SIZING 1 16
2 14 P (Invertet wattage) Power Law
3 12 I=
V (System nominal voltage)
5 10
6000watts
8 8
I= = 125A P
12 6 48volts
20 4
34 2 125A x 6.56 (ft) I V
Vdi = = 8.54A
49 1/0 2x 48V
62 2/0
P = watts P=IxV
78 3/0
I = current I=P/V
99 4/0
V = volts V=P/I
Internal
BREAKER SIZING INVERTER TO AC LOADS
1. Based on the Inverter Wattage
2. Based on the Load Wattage
Internal
VDI AWG
Battery Bank to inverter
WIRE SIZING 1 16
2 14 P (Inverter wattage) Power Law
3 12 I=
V (DU AC Voltage)
5 10
6000watts
8 8
I= = 27.27A P
12 6
Inverter 220volts AC
20 1KW4 12V
34 2 27.27A x 32.8 (ft) I V
Vdi = = 4.06A
49 1/0 1x 220V
62 2/0
P = watts P=IxV
78 3/0
I = current I=P/V
99 4/0
V = volts V=P/I
AC LOADS
Internal
Materials:
Solar Panel: 9pcs (400w Monocrystalline)
Inverter: 1-SNADI- 48V6000watts
Battery: 12pcs (12v 200Ah) Lead Acid
wiring for
OFF-GRID SCC: 1-FANG-FLEX 150V80A
SYSTEM
Internal
Computation for
ON-GRID
SYSTEM
Internal
Based on average
monthly electric bill,
= 15,000wh
Internal
Losses
(constant)
Total Daily
PV Power = Consumption x 1.3
Sun Peak Hrs.
Step2 15,000wh
= x 1.3 = 4875 w
SIZING OF PV 4 hrs
(average peak
PANELS sunlight hours per day)
PV power
USE: 14 pcs - 340w JA No. of PV Panels =
Rating of PV
Solar Polycrystalline
Solar Panels
4875 w
= = 14.33 ≈ 14pcs
340 w
Will vary depending on
Solar panel type and size.
(JA Solar)
Internal
Note:
The Size of the on grid inverter depends on the total PV power
Step3
Total PV Power = Rating of PV x No. of PV Panels
SIZING OF
INVERTER
= 340w/pc x 14pcs
USE: 1- 5.0kw -
= 4760w or 4.76 Kw
SOLIS-4G ON GRID
INVERTER
Internal
Computation for
HYBRID
SYSTEM
Internal
Based on average
monthly electric bill,
Internal
Losses
(constant)
Total Daily
PV Power = Consumption x 1.3
Sun Peak Hrs.
Step2 10,000wh
x 1.3 = 3250 w
4 hrs
SIZING OF PV
(average peak
PANELS sunlight hours per day)
PV power
USE: 10 pcs - 340w JA No. of PV Panels =
Rating of PV
Solar Polycrystalline
Solar Panels
3250 w
= 9.96 ≈ 10pcs
340 w
Will vary depending on
Solar panel type and size.
(JA Solar)
Internal
Note:
The Size of the on-grid inverter depends on the total PV power
Step3
Total PV Power = Rating of PV x No. of PV Panels
SIZING OF
INVERTER
= 340w/pc x 10pcs
USE: 1-EAST-
HYBRID-
= 3400 w or 3.4 Kw
48V3600w
Internal
PV CONNECTION :
Step3 PV SPECS : (340 w poly)
Solar PV Voc = 46.13v Inverter specs:
Isc = 9.38A Vmax = 500v
Connection 10
No. of Series = Vmax 500v
= = 10.84 ≈ 11
(PV) Voc 46.13v 11 x 46.13v = 507.43v
(Should not exceedto
Vmax: 500v)
1 strings of 10
Parallel Series
Internal
Daily
Load Qty. Power Total Power Hrs. used
Consumption
LED
5 7W 35W 8 HRS 280wh
LIGHT
S
3880 wh
= = 190.2 Ah
.5 x .85 x48v
(50% level before the battery
capacity drops) Lead-Acid Battery
Internal
Total Daily Consumption
Battery
= D.O.D x Efficiency x System
Capacity
voltage
3880 wh
= = 190.2 Ah
Step4 .5 x .85 x48v
SIZING OF
BATTERY BATTERY CONNECTION:
190.2 Ah
= = .95 ≈ 1
200 Ah
(Indicated on specs)
Internal
BATTERY CONNECTION:
Step4 190.2 Ah
= = .95 ≈ 1
200 Ah
SIZING OF
BATTERY
No. of System Voltage
=
Series Voltage Rating ofBattery
USE: 4 pcs -12V 48V
200 Ah Batt. = = 4
12V
1 strings of 4
Parallel Series
Internal