Single Zone Fresh Air Ventilation Calculation

For EQ. Pr -1 : Minimum IAQ Performance


Minimum ASHRAE 62.1-2007 Requirements

Fresh air
Breathing PROVIDE Meeting
Zone air
Zone Zone D to the Minimum
People Area distributio REQUIRE
Max. Zone Zone Floor Outdoor Outdoor zone (must Standard
Outdoor Outdoor n D
LEVEL ROOM NAME Population Area (sq.ft) Air flow Air Flow meet Requireme
Air Air Rate, effectivene AIRFLOW
Pz Az (Vbz= (Voz = values in nt
Rate,Rp Ra ss (Vot)
RpPz+RaA Vbz/Ez) drawing)
Ez (CFM)
z) (cfm)

Ground Floor
G.AC-1 DASIA SECURITY FIREARM VAULT 4 20.0 90.76 0.12 91 1 91 91 100 YES
G.AC-2 DASIA FORCE FIREARM VAULT 4 20.0 87.50 0.12 91 1 91 91 100 YES
G.AC-3 DASIA INC FIREARM VAULT 4 20.0 92.17 0.12 91 1 91 91 100 YES
G.AC-4 KADSIA FIREARM VAULT 4 20.0 84.16 0.12 90 1 90 90 100 YES
G.AC-5 METROGUARD FIREARM VAULT 4 20.0 88.17 0.12 91 1 91 91 100 YES
G.AC-6 GENESIS 88 FIREARM VAULT 4 20.0 92.17 0.12 91 1 91 91 100 YES
Second Floor
2F.AC-1 RECORDS ROOM 4 20.0 1268.78 0.12 232 1 232 232 300 YES
2F.AC-1 FINANCE RECORDS VAULT 4 20.0 160.62 0.12 99 1 99 99 200 YES
2F.AC-1 MAIN VAULT 4 20.0 296.51 0.12 116 1 116 116 200 YES
36 2260.84 991 1300
EXHAUST VENTILATION CFM SCHEDULE

LEVEL SERVED BY ROOM NAME


Ground Floor
2 TOILETS
G.CR-1 CR 1
1 URINALS
1 TOILET
G.CR-2 PWD CR 1
1 URINAL
Second Floor
3 TOILETS
2F.CR-1 CR 1
2 URINALS
1 TOILET
2F.CR2 PWD CR 1
1 URINAL
Third Floor
3 TOILETS
3F.CR-1 CR 1
2 URINALS
1 TOILET
3F.CR-2 PWD CR 1
1 URINAL
Fourth Floor
3 TOILETS
4F.CR-1 CR 1
2 URINALS
1 TOILET
4F.CR-2 PWD CR 1
1 URINAL
Fifth Floor
1 TOILETS
5F.AC-1 G1 CR
1 URINAL
1 TOILET
5F.AC-2 V5 CR
1 TOILET
5F.AC-3 G2 CR
EXHAUST VENTILATION CFM SCHEDULE

VOLUME FLOW RATE PER UNIT TOTAL VOLUME FLOW RATE


NO. OF UNITS (CFM/UNIT) (CFM)

500.00
5 100.0
200.00
2 100.0

500.00
5 100.0
200.00
2 100.0

500.00
5 100.0
200.00
2 100.0

500.00
5 100.0
200.00
2 100.0

200.00
2 100.0
100.00
1 100.0
100.00
1 100.0
TOTAL 1100.0 3200.00
Single Zone Exhaust Air Ventilation Calculation
For EQ. Pr -1 : Minimum IAQ Performance

LEVEL Served By ROOM NAME

Ground Floor
2 TOILETS
G.AC-1 CR 1
1 URINALS
1 TOILET
G.AC-2 PWD CR 1
1 URINAL
Second Floor
3 TOILETS
2F.AC-1 CR 1
2 URINALS
1 TOILET
2F.AC-2 PWD CR 1
1 URINAL
Third Floor
3 TOILETS
3F.AC-1 CR 1
2 URINALS
1 TOILET
3F.AC-2 PWD CR 1
1 URINAL
Fourth Floor
3 TOILETS
4F.AC-1 CR 1
2 URINALS
1 TOILET
4F.AC-2 PWD CR 1
1 URINAL
Fifth Floor
1 TOILETS
5F.AC-1 G1 CR
1 URINAL
1 TOILET
5F.AC-2 V5 CR
1 TOILET
5F.AC-3 G2 CR
e Exhaust Air Ventilation Calculation
Pr -1 : Minimum IAQ Performance
Minimum ASHRAE 62.1-2007 Requirements
TOTAL
NO OF UNITS CFM PER UNIT
EXHAUST AIR

300.00
5 100.0

200.00
2 100.0

500.00
5 100.0
200.00
2 100.0

500.00
5 100.0
200.00
2 100.0

500.00
5 100.0
200.00
2 100.0

200.00
2 100.0

1 100.0 100.00

1 100.0 100.00
1100.0 3000.00