EXTERNAL STATIC PRESSURE (ESP) CALCULATIONS SHEET

Project : Mr.Meqdad Eissa Villa Transmittal No :


PAU Location : Roof Floor Area Served : Ground Floor Date : 16-Aug-23
PAU Tag No. : PU-01 Supply Air : 4467 cfm Fresh Air : cfm ESP Design= 0.7 inch.w.g

A. Suction ESP Calculations


Velocity Velocity
Friction loss/
Node / pressure at pressure at Straight Duct
Type of Air 100 ft of No of Equivalent Fittings Loss
Location Duct Duct sizes (inches) Duct Length Air Velocity Reducer/Tee or Fittings in line. the higher the lower pressure loss Remarks
Duct Quantity equivalent fittings length (ft) (a)
Section side of the side of the (b)
length (in-wg)
duct ( hv1) duct ( hv2)
Width-1 Height-1 Width-2 Height-2 Cfm m ft Fpm (in wg) (in wg) (in wg) (in wg) (in wg)
32 18 4,467 3.40 11.2 1214 0.072 Straight 0.0081
32 18 4,467 1214 0.072 45 Degree Elbow 2 0.0300 0.0600 2. CR3-6
A-B
32 18 4,467 1214 0.072 90 Degree Elbow 1 0.0200 0.0200 1. CR3-1
Roof & Shaft
32 18 4,467 3.10 10.2 1214 0.072 Accoustic Linning 0.0097 20% of St Duct
Return 32 18 4,467 1.60 5.2 1214 0.072 Straight 0.0038
B-C
Air Duct 32 18 4,467 1214 0.072 90 Degree Elbow 1 0.0200 0.0200 1. CR3-1
32 18 4,467 2.40 7.9 1214 0.072 Straight 0.0057
Ground Floor C-D'
32 18 4,467 1214 0.072 90 Degree Elbow 1 0.0200 0.0200 1. CR3-1
32 18 4,467 5.00 16.4 1214 0.072 Straight 0.0119
Ground Floor C-D
32 18 4,467 1214 0.072 Wire mesh 1 0.0400 0.0400 2. (CR6-1)
SUB TOTAL 0.199

Calculated pressure drop for Return Air Duct = (a+b ) + 10 % safety factor = 0.219 in wg ..........(A)

B. Supply Air ESP Calculations


Velocity Velocity
Friction loss / Straight duct pressure
Node / pressure at pressure at
Type of Air 100 ft of No of Equivalent Fittings Loss loss
Location Duct Duct sizes (inches) Duct Length Air Velocity Duct Fittings. the higher the lower Remarks
Duct Quantity equivalent fittings length (ft) (a1)
Section side of the side of the
length (in-wg) (b1)
duct ( hv1) duct ( hv2)
Width-1 Height-1 Width-2 Height-2 Cfm m ft Fpm (in wg) (in wg) (in wg) (in wg) (in wg)
32 18 4,467 3.00 9.8 1214 0.072 Straight 0.0071
Supply 1-2 32 18 4,467 1214 0.072 90 Degree Elbow 1 0.0200 0.0200 1. CR3-1
Roof Floor & Shaft Air Duct 32 18 4,467 3.10 10.2 1214 0.072 Accoustic 0.0014 20% of St Duct
(SAD) 32 18 4,467 4.00 13.1 1214 0.072 Straight 0.0095 Ductulator
2-3
32 18 4,467 1214 0.072 90 Degree Elbow 1 0.0200 0.0200 1. CR3-1
32 18 4,467 2.40 7.9 1214 0.072 Straight 0.0057 Ductulator
3-3'
32 18 4,467 1214 0.072 90 Degree Elbow 1 0.0200 0.0200 1. CR3-1
32 18 4,467 5.00 16.4 1214 0.072 Straight 0.0119 Ductulator
3'-4
32 18 4,467 1214 0.072 90 Degree Elbow 1 0.0200 0.0200 1. CR3-1
32 18 4,467 4.20 13.8 1214 0.072 Straight 0.0100 Ductulator
4-5
32 18 28 14 3,116 847 0.038 Reducer 1 0.0200 0.0200 3. SR4-2
28 14 3,116 2.73 9.0 1256 0.098 Straight 0.0088 Ductulator
5-6
28 14 26 14 2,716 1095 0.076 Reducer 1 0.0100 0.0100 4. (SR4-2)
Supply 26 14 2,716 2.00 6.6 1172 0.090 Straight 0.0059 Ductulator
6-7
Ground Floor Air Duct 26 14 20 14 1,816 784 0.043 Reducer 1 0.0100 0.0100 5. (SR4-2)
(SAD) 20 14 1,816 3.72 12.2 1003 0.079 Straight 0.0096 Ductulator
7-8
20 14 16 14 1,316 727 0.044 Reducer 1 0.0100 0.0100 6. (SR4-2)
16 14 1,316 5.20 17.1 902 0.074 Straight 0.0126 Ductulator
8-9
16 14 18 8 658 451 0.021 Bullhead Tee 1 0.0300 0.0300 7. SR5-13
18 8 658 4.00 13.1 730 0.067 Straight 0.0089 Ductulator
9-10 18 8 658 730 0.067 90 Degree Elbow 1 0.0100 0.0100 CR3-1
15x15" SAD 658 0 SAD (15x15) 0.0720 DASCO

SUB TOTAL 0.3333

Calculated pressure drop for Supply Air Duct = (a1+b1) + 10 % safety factor = 0.367 in w.g ..........(B) ESP
Design 0.7
Summary SELECTED : 0.7 in w.g
PU-01(PNGC-130C2) ESP = A+B = 0.586 in w.g Calculated 0.586

Prepared by :AM Page 1 of 3


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 5. 00.00 Wednesday, August 16, 2023

(CR3-6) Elbow, Mitered (Idelchik 1986, Diagram 6-5)

INPUTS OUTPUTS

Width (W, in.) 38.0 Velocity (Vo, fpm) 1117


Height (H, in.) 16.0 Vel Pres at Vo (Pv, in. wg) 0.08
Angle (Theta, deg.) 45 Loss Coefficient (Co) 0.37
Flow Rate (Q, cfm) 4467 Pressure Loss (in. wg) 0.03
Density (lbm/ft^3) 0.075

08/16/2023 version: 5.00.00


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 5. 00.00 Monday, September 19, 2022

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, in.) 38.0 Velocity (Vo, fpm) 1117


Height (H, in.) 16.0 Vel Pres at Vo (Pv, in. wg) 0.08
Radius Ratio (r/W) 1.5 Loss Coefficient (Co) 0.20
Angle (Theta, deg.) 90 Pressure Loss (in. wg) 0.02
Flow Rate (Q, cfm) 4467
Density (lbm/ft^3) 0.075

09/19/2022 version: 5.00.00


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 5. 00.00 Monday, September 19, 2022

(CR6-1) Screen (Only) (Idelchik 1986, Diagrams 8-6 and 3-15)

INPUTS OUTPUTS

Height (Ho, in.) 16.0 Open Area (%) 50


Width (Wo, in.) 38.0 Velocity (Vo, fpm) 1117
Area Ratio (A1/Ao) 1.6 Vel Pres at Vo (Pv, in. wg) 0.08
Free Area Ratio (n) 0.50 Loss Coefficient (Co) 0.64
Flow Rate (Q, cfm) 4467 Pressure Loss (in. wg) 0.05
Density (lbm/ft^3) 0.075

09/19/2022 version: 5.00.00


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 5. 00.00 Monday, September 19, 2022

(SR4-2) Transition, Pyramidal, Supply Air Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, in.) 16.0 Angle (Theta1, deg.) 19


Width (Wo, in.) 38.0 Angle (Theta2, deg.) 19
Height (H1, in.) 14.0 Velocity (Vo, fpm) 779
Width (W1, in.) 28.0 Velocity (V1, fpm) 1145
Length (L, in.) 12.0 Vel Pres at Vo (Pvo, in. wg) 0.04
Flow Rate (Q, cfm) 3116 Vel Pres at V1 (Pv1, in. wg) 0.08
Density (lbm/ft^3) 0.075 Loss Coefficient (Co) 0.45
Pressure Loss (in. wg) 0.02

09/19/2022 version: 5.00.00


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 5. 00.00 Monday, September 19, 2022

(SR4-2) Transition, Pyramidal, Supply Air Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, in.) 14.0 Angle (Theta1, deg.) 0


Width (Wo, in.) 28.0 Angle (Theta2, deg.) 19
Height (H1, in.) 16.0 Velocity (Vo, fpm) 1074
Width (W1, in.) 28.0 Velocity (V1, fpm) 998
Length (L, in.) 6.0 Vel Pres at Vo (Pvo, in. wg) 0.07
Flow Rate (Q, cfm) 2716 Vel Pres at V1 (Pv1, in. wg) 0.06
Density (lbm/ft^3) 0.075 Loss Coefficient (Co) 0.01
Pressure Loss (in. wg) 0.00

09/19/2022 version: 5.00.00


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 5. 00.00 Monday, September 19, 2022

(SR4-2) Transition, Pyramidal, Supply Air Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, in.) 14.0 Angle (Theta1, deg.) 0


Width (Wo, in.) 20.0 Angle (Theta2, deg.) 14
Height (H1, in.) 14.0 Velocity (Vo, fpm) 934
Width (W1, in.) 28.0 Velocity (V1, fpm) 718
Length (L, in.) 24.0 Vel Pres at Vo (Pvo, in. wg) 0.05
Flow Rate (Q, cfm) 1816 Vel Pres at V1 (Pv1, in. wg) 0.03
Density (lbm/ft^3) 0.075 Loss Coefficient (Co) 0.03
Pressure Loss (in. wg) 0.00

09/19/2022 version: 5.00.00


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 5. 00.00 Monday, September 19, 2022

(SR4-2) Transition, Pyramidal, Supply Air Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, in.) 14.0 Angle (Theta1, deg.) 0


Width (Wo, in.) 16.0 Angle (Theta2, deg.) 19
Height (H1, in.) 14.0 Velocity (Vo, fpm) 846
Width (W1, in.) 20.0 Velocity (V1, fpm) 677
Length (L, in.) 12.0 Vel Pres at Vo (Pvo, in. wg) 0.04
Flow Rate (Q, cfm) 1316 Vel Pres at V1 (Pv1, in. wg) 0.03
Density (lbm/ft^3) 0.075 Loss Coefficient (Co) 0.03
Pressure Loss (in. wg) 0.00

09/19/2022 version: 5.00.00


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 5. 00.00 Monday, September 19, 2022

(SR5-13) Tee, 45 Degree Entry Branch, Diverging (Brooks 1993)

INPUTS OUTPUTS

Height (H, in.) 14.0 Branch


Width (W, in.) 16.0 Velocity (Vb, fpm) 658
Height (Hs, in.) 8.0 Vel Pres at Vb (Pvb, in. wg) 0.03
Width (Ws, in.) 18.0 Loss Coefficient (Cb) 1.20
Height (Hb, in.) 8.0 Branch Pressure Loss (in. wg) 0.03
Width (Wb, in.) 18.0 Main
Flow Rate (Qc, cfm) 1316 Velocity (Vs, fpm) 658
Flow Rate (Qb, cfm) 658 Velocity (Vc, fpm) 846
Density (lbm/ft^3) 0.075 Vel Pres at Vs (Pvs, in. wg) 0.03
Vel Pres at Vc (Pvc, in. wg) 0.04
Loss Coefficient (Cs) 0.16
Main Pressure Loss (in. wg) 0.00

09/19/2022 version: 5.00.00


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 5. 00.00 Monday, September 19, 2022

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, in.) 18.0 Velocity (Vo, fpm) 658


Height (H, in.) 8.0 Vel Pres at Vo (Pv, in. wg) 0.03
Radius Ratio (r/W) 1.5 Loss Coefficient (Co) 0.20
Angle (Theta, deg.) 90 Pressure Loss (in. wg) 0.01
Flow Rate (Q, cfm) 658
Density (lbm/ft^3) 0.075

09/19/2022 version: 5.00.00


BASIC PERFORMANCE DATA (Supply Air Ceiling Diffusers)

B SQUARE & RECTANGULAR NECK


A A NECK A B A B A B A B A B A B A B

VELOCITY 250 300 400 500 600 700 800

B $P(s) 0.018 0.026 0.046 0.072 0.104 0.142 0.186

www.dasco.com.kw
SIZE NECK PATTERN CFM 390 469 625 781 938 1095 1250 SIZE
AREA S.NC 19 22 28 33 37 44 49
SCFM 98 98 117 117 156 156 195 195 234 234 273 273 312 312
DD-64S
15 THROW 14 -18 16 - 19 18 - 22 19 - 24 20 - 27 21- 28 22 -29 15
SCFM 146 98 176 117 234 156 293 195 352 234 411 273 469 312
DD-63S
X X
SCFM - 195 - 235 - 313 - 391 - 469 - 548 - 625
DD-62S
15 THROW 19 - 24 20 - 27 22 - 29 22 - 31 23 - 33 24 - 35 26 - 39 15
SCFM - 390 - 469 - 625 - 781 - 938 - 1095 - 1250
DD-61S
THROW 22-31 23-33 26-39 27-42 29-46 30-48 32-51

SIZE NECK PATTERN CFM 562 675 900 1125 1350 1575 1800 SIZE
AREA S.NC <18 24 30 35 40 45 51
SCFM 141 141 168 168 225 225 281 281 337 337 394 394 450 450
DD-64S
18 THROW 17 - 22 20 - 23 22 - 27 23 - 29 25 - 31 26 - 32 28 - 33 18
SCFM 211 141 253 168 338 225 422 281 506 337 591 394 675 450
DD-63S
X X
SCFM - 281 - 338 - 450 - 563 -675 - 788 -900
DD-62S
18 THROW 23-29 25-31 28-33 28-34 30-36 31-38 32-40 18
SCFM - 562 - 675 - 900 - 1125 - 1350 - 1575 - 1800
DD-61S
THROW 28-34 30-36 32-40 33-43 35-47 36-50 38-54

SIZE NECK PATTERN CFM 765 919 1225 1530 1838 2144 2450 SIZE
AREA S.NC 22 25 30 36 42 48 54
SCFM 191 191 230 230 306 306 383 383 460 460 536 536 613 613
DD-64S
21 THROW 20 - 26 23 - 27 26 - 32 28 - 34 29 - 37 31 - 38 33 - 40 21
SCFM 287 191 345 230 459 306 574 383 690 460 804 536 919 613
DD-63S
X X
SCFM - 383 - 460 - 613 - 675 - 919 - 1072 - 1225
DD-62S
21 THROW 28-34 29-37 33-40 34-42 36-45 36-46 38-48 21
SCFM - 765 - 919 - 1225 - 1530 - 1838 - 2144 - 2450
DD-61S
THROW 34 - 42 36 - 45 38 - 48 39 - 50 41 - 53 42 - 55 44 - 58

Note
SIZE : Is the nominal neck size in inches. P(s) : Supply pressure drop in inches W.G.
NICK AREA : Is in square feet. SCFM : Side CFM.
PATTERN : Is flow pattern as detailed previously. THROW : IN feet corresponding to 100 & 50
FPM terminal velocity.
SNC : Room NC for supply based on 8 db
room effect.

11