For future Egypt SS S2 SWG

-Incomer
CT Ratio (600/5).
51 /STAGE - 1 51 /STAGE - 2 51N /STAGE - 1 51N /STAGE - 2
Setting 0.67 In = 402 A 1.33 In = 798 A 0.13 In = 78 A 0.27 In = 162 A
Time
450 ms 170 ms 350 ms 170 ms
Delay

-BUSCOUPLER
CT Ratio (1600/5)
51 /STAGE - 1 51 /STAGE - 2 51N /STAGE - 1 51N /STAGE - 2
Setting 0.5 In = 300 A 1 In = 600 A 0.085 In = 51 A 0.16 In = 96 A
Time Delay 300 ms 100 ms 250 ms 100 ms

-Outgoing
CT Ratio (400/5)
51N /STAGE -
51 /STAGE – 1 51 /STAGE - 2 51N /STAGE - 1
2
Setting .5 In = 200 A 1 In = 400 A 0.1 In = 40 A .2 In = 80 A
Time Delay 150 ms 50 ms 150 ms 50 ms