Professional Documents
Culture Documents
02PMS0010 Rindam Siantar TB
02PMS0010 Rindam Siantar TB
SITE ID : 02PMS0010
CITY : MEDAN
AREA : NSRO
Approved By,
INDOSAT OOREDOO- PROJECT INDOSAT OOREDOO- ID INDOSAT OOREDOO
VENDOR
1. GENERAL INFORMATION
1 ZXCTN 6120H-S NEW 43.6 mm × 264 mm × 270 mm 200 2 PCS X 16A (DC)
SITE NAME TOMHAWK PROJECT CITY 02PMS0010
SITE IE RINDAM_SIANTAR_TB AREA MEDAN
Type site TYPE SITE ROOF TOP/ GREEN FIELD/ INDOOR BUILDING GREEN FIELD
PERANGKAT ZXCTN 6120H-S-NEW
SPACE OK LOKASI Proposed New ZXCTN 6120H-S At Rack OUTDOOR
2 OTB/ODP OK LOKASI ODP READY AT POLE
3 MCB PDU A NONE PROP. MCB NEW (A)= X PCS LOAD (A) = 0
3 MCB PSU 1 NONE PROP. MCB NEW (A)= X PCS LOAD (A) =
4 MCB PSU 2 NONE PROP. MCB NEW (A)= X PCS LOAD (A) =
3 MCB PDU B NONE PROP. MCB NEW (A)= X PCS LOAD (A) = 0
5 MCB PSU 3 NONE PROP. MCB NEW (A)= X PCS LOAD (A) =
6 MCB PSU 4 NONE PROP. MCB NEW (A)= X PCS LOAD (A) =
7 PLN OK 6600VA UPGRADE KE 0
8 GENSET N/A N/A - N/A VA UPGRADE KE 0 VA
9 RECTIFIER 1 ADD MODULE OUTDOOR -HUAWEI-R4850N-2 Utilisasi (%) 124%
BUT ADD BATTERY BUT 2.0
Remarks
10 RECTIFIER 2 #DIV/0! --- Utilisasi (%) #DIV/0!
BUT #DIV/0! BUT #DIV/0!
Remarks
11 RECTIFIER 3 #DIV/0! --- Utilisasi (%) #DIV/0!
BUT #DIV/0! BUT #DIV/0!
Remarks
12 RECTIFIER 4 #DIV/0! --- Utilisasi (%) #DIV/0!
BUT #DIV/0! BUT #DIV/0!
Remarks
13 MCB OK Propose USE MCB Existing 2 x 16 A
14 SINGLE/DUAL Single Koneksi Single Source Dual Feed, Main&Redundant Koneksi Ke Power System 1 -HUAWEI R4850N
PLN OK
Type 6FMX-100B
YEAR OF INSTALLATION
Charge Coefficient % 10% 10% 10% 10% 10% 10%
Capacity Ah 100
Qty of Banks Banks 1
Total Battery Capacity Ah 100 0 0 0 0 0
DC POWER CALUCATION
Existing Load Watt 2204 0 0 0 0 0 2755 VA
Battery Charging Watt 560 0 0 0 0 0 700 VA
Proposed Equipment
ZXCTN 6120H-S Watt 200
Watt
Watt
Total Proposed Equipment Watt 200 0 0 0 0 0 250 VA
Total Load Watt 2964 0 0 0 0 0 3705 VA
Capacity Rectifier 80% with redudancy (n-1) Watt 2400 0 0 0 0 0
Rectifier Existing Utilization % 115% #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
Rectifier Existing + New Load Utilization % 124% #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
Remain Power Watt -564 0 0 0 0 0
RESULT
THRESHOLD CAPACITY RECTIFIER 100% 80% 90% 90% 90% 90% 90%
STATUS RECTIFIER OK/ADD ADD MODULE #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
TYPE MODULE R4850N 0 0 Dec-99 0 0
ADD MODULE Pcs -1 0 0 0 0 0
AVAILABLE SLOT Pcs 2 0 0 0 0 0
NEW CAPACITY 80% WITH REDUDANCY (N-1) Watt 5400 0 0 0 0 0
RECTIFIER ULITIZATION AFTER EXPANSION % 55% #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
BATTERY CALUCATION
Battery Backup Time Load Existing hours 2.2 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
Battery Backup Time Load Existing + New :oad hours 2.0 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
RESULT
THRESHOLD BACKUP TIME 2 hrs 2 2 2 2 2 2
TOTAL LOAD Ampere 62 0 0 0 0 0
STATUS BATTERY ADD BATTERY #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
MEREK SHOTO 0 0 0 0 0
TYPE BATTERY 6FMX-100B 0 0 0 0 0
CAPACITY Ah 100 0 0 0 0 0
ADD BATTERY Banks 1 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
BACKUP TIME AFTER ADD BATTERY hours 4.0 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
COONECTION POWER Main / Main &Redundant
Redundant
NOTE FROM CORE INRASTRUCTURE DESIGN & SOLUTION
POWER Single Koneksi Single Source Dual Feed, Main&Redundant Koneksi Ke Power System 1 -HUAWEI R4850N
AC SPLIT
Location / Room / Shelter
Dimension Room Length (m)
Width (m)
Area (m²)
LAMP UNIT
MEREK
CAPACITY PK
YEAR OF INSTALLATION
TEMPERATURE INSIDE °C
QUANTITY Pcs
TOTAL LOAD PLN Watt 0 0 0 0 0
CAPACITY COOLING Watt 0 0 0 0 0 0 0
COOLING CALCULATION
EQUIPMENT Watt 0 0 0 0 0 0
LAMP Watt 0 0 0 0 0 0
AIR CONDITION EXISTING Watt - - - - - -
COOLING EXISTING UTILIZATION %
Watt 200 200
NEW LOAD
Watt 200.00 200.00 200.00 200.00
COOLING EXISTING + NEW LOAD %
UTILIZATION
RESULT
THRESHOLD COOLING % 80% 80% 80% 80% 80% 80%
STATUS COOLING OK/ADD
CAPACITY PK 0 0 0 0 0 0
REMAIN CAPACITY COOLING Watt (200.00) (200.00) (200.00) (200.00) - -
QUANTITY Unit
REMARKS
SITE OUTDOOR
6. UPS POWER CALCULATION
Site Name RINDAM_SIANTAR_TB CITY MEDAN
TOTAL LOAD VA 0
RESULT
TOTAL REQUIREMENT (EXITING + NEW) VA 0 0
REMAINING POWER VA 0 0
UPS Usage from 80% total capacity 100% #DIV/0! #DIV/0!
STATUS OK/ Need Upgrade #DIV/0! #DIV/0!
Capacity kVA 0 0
Unit #DIV/0! #DIV/0!
Utilization after Upgrade % #DIV/0! #DIV/0!
BATTERY UNIT UPS 1 UPS 2
Brand
Model
Voltage
Capacity
Qty
BACK UP TIME (existing) Hrs #DIV/0! #DIV/0!
RESULT
Treshold hrs 0.5 0.5
BACK UP TIME (Existing + New) Hrs #DIV/0! #DIV/0!
STATUS OK/ Need Upgrade #DIV/0! #DIV/0!
CAPACITY AH 0 0
Qty Bank #DIV/0! #DIV/0!
BACK UP TIME AFTER UGRADE hrs #DIV/0! #DIV/0!
REMARKS
Site Name RINDAM_SIANTAR_TB City MEDAN
Site ID 02PMS0010 Area NSRO
N/A
ID PELANGGAN KWH
N/A N/A
N/A
N/A NA
N/A
NA NA
NA NA
NA NA
N/A NA
N/A N/A
Voltage Measurement at ATS Panel R-N 219.2V Voltage Measurement at ATS Panel S-N 213.3 V
N/A N/A
Voltage Measurement at ATS Panel T-N 207.9V Voltage Measurement at ATS Panel PE-N 115 V
EXTERIOR PHOTOS
Site Name RINDAM_SIANTAR_TB City MEDAN
Site ID 02PMS0010 Area NSRO
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
NA
NA NA
NO AC AVILIABLE N/A
AC SPLIT 1 AC SPLIT 2
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
NA NA
NEW ME NEW ME
NEW ME NEW ME
NEW ME NEW ME
NA NA
NA NA
NA NA
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
PROP. ZXCTN 6120H-S PROP. MCB ZXCTN 6120H-S (USE EXISTING MCB
2 X 16 A)
N/A