Scroll compressors
Fitters Notes (Part 9)
Stephan Bachmann, The “Fitters Notes” series provides useful practical information for
Danfoss Refrigeration & the everyday work of fitters. The previous article dealt with electronic
Air Conditioning,
Offenbach expansion valves. In this article (Part 9), we examine another main
component of refrigeration systems: the compressor, and in particular
scroll compressors.
The compressor is a key element of Construction and operation The situation is different with the black-
every compression refrigeration system. Danfoss scroll compressors have a painted Danfoss scroll compressors,
It raises the pressure of a refrigerant in vertical crankshaft, with the scroll set which operate on the “compliance
the vapour state from a low level (low- located above the crankshaft. principle”.
pressure or suction side) to a high level
(high-pressure or discharge side). The scroll set consists of a fixed spiral This means that one of the two spirals
and an orbiting spiral. The two spirals is pressed against the other spiral by
There are various types of compressors are interleaved, and they compress the moderate pressure from the “pockets” in
available, with different operating refrigerant by transporting it from the the scroll set where the full compression
principles. outer edge of the scroll set to the centre level has not been reached.
with an orbital motion.
They include:
• Scroll compressors With this operating principle, gas at
• Screw compressors various compression levels is present at
• Rolling piston compressors any given time during the compression
• Turbo compressors process, due to the different-sized
• Reciprocating compressors “pockets” where compression occurs. As
a result, in comparison with reciprocating
This article concentrates on scroll compressors they expel smaller portions
compressors. Scroll compressors are of refrigerant, but more frequently, which
used very extensively in refrigeration reduce the pulsation level.
systems, traditionally in chillers. They are
also gaining more market share in other For fitters, this means that a muffler to As a result, the two spirals are “run in”
areas, especially heat pumps. dampen pulsation does not have to together, in a manner of speaking. The
be fitted as often. Noise problems and run-in phase lasts up to 72 hours after the
However, scroll compressors are generally pressure switch malfunctions due to compressor is first put into service.
available for use in ordinary refrigeration pulsation are also unlikely with a scroll
systems as well, and even in freezer compressor system.
systems.
at the suction side and are not hot to in the right direction when it is running. If compressor contactor (ahead of “A1”).
the touch. The discharge temperature you hear loud mechanical noises and the There is yet another type of motor
is always a critical aspect with scroll service pressure gauge does not show protection available with the blue
compressors. For example, the discharge the usual pressure difference between “Performer” compressors: the SZ240,
temperature of a scroll compressor used the high-pressure and low-pressure SZ300 and SZ380 models have a Kriwan
in an air conditioning or heat pump sides, the compressor is most likely INT69 thermistor motor protection
system is not especially high if it is running in the wrong direction. To correct unit.
operated with a customary evaporation this, swap two of the phase connections
temperature of 0 °C or 10 °C. on the compressor terminal strip. The M1/M2 contact of the INT69 is
potential-free (floating) and should be
This means that the temperature is rarely You can use a voltage checker to check wired into the protection circuit ahead
higher than 100 °C, which does not that the electrical power supply at of the compressor contactor (ahead of
present a problem for the compressor, the junction box is OK. The voltage “A1”). This is similar to the connection
bearings, scroll set, or refrigerating- between any two phases should always arrangement with a bimetallic cut-out
machine oil. However, if this sort of be around 400 V. To provide additional switch. These INT69 requires a supply
compressor is operated for a relatively protection against overheating and voltage of 230 V or 24 V, depending on
long time with a suction pressure well excessive power consumption, some the model. This information is important
below its operating limit, for example blue compressor models (SZ/SM84-110 for the fitter, since it means that in
due to persistent strong throttling of and SZ/SM84-120) have a bimetallic cut- addition to installing the usual power
the evaporation pressure regulator or out switch at the wye point of the motor cable to the compressor (with the three
for some other reason, the discharge windings. This means that if you measure phase conductors and protective earth
temperature can quickly rise to an a nearly infinite resistance between the conductor); the fitter must also install
excessively high level. three motor leads of the compressor the neutral wire for the motor protection
(disconnect the supply voltage first!); module supply voltage and a pair of
For this reason, it is strongly recommen- you can assume that the internal motor conductors for the safety circuit of the
ded to install some form of compressed- protection switch has tripped. The compressor contactor. When the scroll
gas discharge temperature monitoring bimetallic switch returns to the closed compressor is operating, the motor
in a system with a scroll compressor or state after the motor cools down. When protection unit constantly monitors the
retrofit it in existing systems if it is not the motor is ready for use, the resistances thermistors fitted in the compressor to
already present. This task can be handled measured between each pair of leads check whether the temperatures in the
by a simple mechanical thermostat with are nearly identical. Depending on the compressor are OK. If an overheating
a remote sensor, such as the Danfoss capacity of the compressor, they should condition occurs, the contact between
KP 81. It is not necessary to adjust the lie in the range of 0.4 ohms to less than M1 and M2 opens and de-energises the
thermostat setting extremely close 10 ohms. motor contactor.
to the operating point; a good rule of
thumb here is 120 °C, with a maximum However, you still have to be careful even The rotation speed of these compressors
of 135 °C. if the compressor has internal motor is approximately 2900 rpm with a 50-Hz
protection. Other compressor models, supply, since the motor is wound with
Electrical connection
You should fit a crankcase strip heater to
the compressor for outdoor installation
or in situations where the compressor can
be exposed to low ambient temperatures.
It should always be switched opposite to
the compressor (strip heater off when the
compressor is running, strip heater on
when the compressor is not running).
Information
The “Fitters Notes” series is based on the handbook of the same name produced by Danfoss,
which discusses the basic principles of commercial refrigeration systems and the associated basic
components.
You can view the Fitters Notes handbook from here:
http://www.danfoss.com/BusinessAreas/RefrigerationAndAirConditioning/EducationAndTraining/Fitters+Notes.htm
This “Fitters Notes” series is aimed at refrigeration fitters in servicing, system construction, people
entering refrigeration engineering from other disciplines, trainee refrigeration fitters and anyone who
would like to gain a basic practical knowledge of refrigeration in a series of articles.
The discussion avoids formulae as far as possible and only a small amount of prior technical knowledge is necessary.
Fitters like using rules of thumb and so we will provide plenty of them, even if this sometimes makes it necessary to
accept generalisations that are not always entirely accurate from an academic viewpoint. Unless otherwise stated, this
series always refers to refrigeration systems using fluorinated hydrocarbons, such as R134a, R404A/R507 and R407C (i.e.
not ammonia refrigeration systems).