Vector Group

You might also like

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 3

Q1) Why is vector group important?

A1) Because it determines the phase angle displacement between the primary (HV) and
secondary (LV) windings.

Q2) If the vector-group is changed from Yd11 to Yd1, how will it affect generator
synchronization?
A2) The Yd11 has an HV to LV phase angle displacement of plus 30°, while that of the
Yd1 is minus 30°. Synchronization could be done if the HV and LV configurations were
reversed, i.e., Yd11 and Dy1 in parallel. But, it is not possible if the Yd1 were to be
paralleled with a Yd11 if the primary of both transformers were supplied from the same
source.

The response might be different if you could furnish additional system detail! I may have
misinterpreted your system layout regarding the number of gensets!

Winding connection designations :

High Voltage Always capital letters


Delta - D
Star - Y
Interconnected star - Z
Neutral brought out - N

Low voltage Always small letters


Delta - d
Star - y
Interconnected star - z
Neutral brought out - n
for auto transformer - a

Phase displacement:
Phase rotation is always anti-clockwise. (international adopted convention)
Use the hour indicator as the indicating phase displacement angle. Because there are 12
hours on a clock, and a circle consists out of 360°, each hour represents 30°.
Thus 1 = 30°, 2 = 60°, 3 = 90°, 6 = 180° and 12 = 0° or 360°.
The minute hand is set on 12 o'clock and replaces the line to neutral voltage (sometimes
imaginary) of the HV winding. This position is always the reference point.
Because rotation is anti-clockwise, 1 = 30° lagging (LV lags HV with 30°)and 11 = 330°
lagging or 30° leading (LV leads HV with 30°)

To summarise:
Dd0
Delta connected HV winding, delta connected LV winding, no phase shift between HV
and LV.
Dyn11
Delta connected HV winding, star connected LV winding with neutral brought out, LV is
leading HV with 30°
YNd5
Star connected HV winding with neutral brought out, delta connected LV winding, LV
lags HV with 150°
YNa0d11
Star connected HV winding with neutral brought out, auto transformer with 0°
displacement. LV winding delta conected leading HV by 30°

The phase-bushings on a three phase transformer are marked either ABC, UVW or 123
(HV-side capital, LV-side small letters)
Two winding, three phase transformers can be devided into four main categories (Clock
hour number and phase displacement of those most frequently encountered in practice in
brackets)

Group I - (0 o'clock, 0°) - delta/delta, star/star


Group II - (6 o'clock, 180°) - delta/delta, star/star
Group III - (1 o'clock, -30°) - star/delta, delta/star
Group IV - (11 o'clock, +30°) - star/delta, delta/star

(Minus indicates LV lagging HV, plus indicates LV leading HV)

Group I
Example: Dd0 (no phase displacement between HV and LV)
The conventional method is to connect the red phase on A/a, Yellow phase on B/b, and
the Blue phase on C/c. Other phase displacements are possible with unconventional
connections (for instance red on b, yellow on c and blue on a) By doing some
unconventional connections externally on one side of the trsf, an internal connected Dd0
transformer can be changed either to a Dd4(-120°) or Dd8(+120°) connection. The same
is true for internal connected Dd4 or Dd8 transformers.
Group II
Example: Dd6 (180° displacement between HV and LV)
By doing some unconventional connections externally on one side of the trsf, an internal
connected Dd6 transformer can be changed either to a Dd2(-60°) or Dd10(+60°)
connection.
Group III
Example: Dyn1 (-30° displacement between HV and LV)
By doing some unconventional connections externally on one side of the trsf, an internal
connected Dyn1 transformer can be changed either to a Dyn5(-150°) or Dyn9(+90°)
connection.
Group IV
Example: Dyn11 (+30° displacement between HV and LV)
By doing some unconventional connections externally on one side of the trsf, an internal
connected Dyn11 transformer can be changed either to a Dyn7(+150°) or Dyn3(-90°)
connection.
Additional Note:
By doing some unconventional connections externally on both sides of the trsf, an
internal connected groupIII or groupIV transformer can be changed to any of these two
groups. Thus, an internal connected Dyn1 transformer can be changed to either a: Dyn3,
Dyn5, Dyn7, Dyn9 or Dyn11 transformer, by doing external changes on both sides of the
trsf. This is just true for star/delta or delta/star connections.
Changes for delta/delta or star/star transformers between groupI and groupII can just be
done internally.

You might also like