Calculation Notes:
1. Design is in accordance to NFPA 2001, Latest edition.
2. Design is for a total flooding system.
3. Calculation is for Class C Fire which is for energised electrical equipment.
`
Room Specific Design
Room Name & 2 Volume t Design Agent Weight Total Discharge
Level Area (m ) Height (m) Temperature, t Volume, s Concentration,
Room No. (m3) Factor (%) Required (kg) Flow Rate (kg/s)
(oC) (m3/kg) C (%)
COMMUNICATION
OL PLATFORM LEVEL 22.67 3.38 76.62 20 0.071882 4.5 4.5 52.49 5.25
CLOSET [PL30-1]
Total agent required 52.49
say 55.00 kg
Overall 121.00 lbs