Professional Documents
Culture Documents
Protection of Boiler Feed Pomp Against Transient Suction Pressure Decay
Protection of Boiler Feed Pomp Against Transient Suction Pressure Decay
G. S. LIAO
Engineering Group Supervisor,
Transient Suction Pressure Decay
Los Angeles Power Division,
Bechtel Power Corp., In a previous paper [I],1 the analysis of pump suction pressure decay utilizing the
Los Angeles, Calif, Mem. ASME varying condensate temperature approach was first introduced. Although the paper
provided power plant engineers with an accurate analytical method for determining the
magnitude of feedwater pump suction pressure decay, no protective method to prevent
or alleviate the pressure decay under instant turbine load rejection was mentioned.
As unit size has rapidly increased in recent years, the power plant deaerator requires
not only a larger storage capacity but also must be elevated higher to protect the boiler
feed pumps against suction pressure decay under load rejection. Since this trend is
expected to continue, the cost of supporting the power plant deaerator may soon become
prohibitive. Several protective methods have been previously introduced. However, the
evaluation of the methods was invariably based on the constant-condensate-temperature
approach, which is not suitable for central station regenerative cycle units. This paper
reevaluates those methods in general and recommends the on-off type deaerator by-
pass system as the most effective and economical method. The use of this protective
method will not only reduce deaerator storage capacity to the absolute minimum
as required solely for surge, but will also largely preclude the provision of additional
static head for instant load reduction. As a result, enormous savings can be expected
both from the deaerator itself and its supporting structures. The magnitude of savings in
supporting structures alone may amount to more than a half million dollars for a 750
MW fossile unit. Based on the varying condensate temperature approach, mathe-
matical equations expressing the deaerator pressure decay as well as design parameters
required for designing the protective system have been derived. The paper also presents
a detailed description of the recommended protective system and discusses some ad-
vantages of this system over the others. Finally, a few engineering examples are in-
cluded to illustrate the application in system design.
Introduction suction pressure decay under instant turbine load rejection was
published recently [1]. The analysis revealed that the transient
L HE RAPID INCREASE in power generating unit ca- suction pressure decay increases as boiler feed pump size in-
pacity in recent years has necessitated the installation of corre- creases. In order to handle such an increasing transient suction
spondingly larger boiler feed pumps in central stations. Be- pressure decay, a deaerator not only requires a larger storage
cause of this growth in pump size, the provision of a sufficient volume but also must be elevated higher. However, raising a
static suction head to cope with the suction pressure decay under deaerator equipped with a large storage tank can be very costly
transient load reduction becomes increasingly difficult and in an earthquake area; it may also present the problem of freeze
costly. A thorough analysis of determining the boiler feed pump protection, if the deaerator is to be located above the power plant
enclosure in a locality with severely cold weather.
It is this ever-increasing transient suction pressure decay which
requires the introduction of some protective methods. The ideal
1 solution would be to prevent transient suction pressure decay, so
Numbers in brackets designate References at end of paper.
Contributed by the Power Division and presented at the Winter that the pump suction system could be designed only for maxi-
Annual Meeting, Detroit, Mich., November 11-15, 1973, of THE mum steady turbine load operation. If the provision of addi-
AMERICAN SOCIETY OF MECHANICAL ENGINEERS. Manuscript re-
ceived at ASME Headquarters, July 10, 1973. Paper No. 73- tional suction head for transient suction pressure decay is not
WA/Pwr-1. required, there are two immediate advantages: the reduction
.Nomenclature.
a = (ht — hi)/Mu = enthalpy hi' = enthalpy of saturated water pi = final deaerator pressure; pres-
gradient of warm conden- at pump suction after x lb sure at which deaerator is
sate, Btu/lb 2 of feedwater has entered pressurized by other source
1 Ms the boiler feed pump (with- of steam, psia
= e M = out bypass), Btu/lb = deaerator pressure after x lb
Pd
factor ha = enthalpy of saturated water of feedwater has entered
Hai = static suction head for boiler at pump suction after x lb the boiler feed pump, psia
of feedwater has entered
feed pumps, ft = vapor pressure at pump suc-
the, boiler feed pump (with V-
Hf = friction loss through pump tion after x lb of feedwater
bypass), Btu/lb
suction line, ft Ah =-h, - ta, Btu/lb has entered the boiler feed
AH = transient suction pressure de- Ahmax = maximum Ah during tran- pump, psia
cay, ft sient period, Btu/lb R = required bypass ratio; ratio
Affmax = maximum transient suction M = mass of water in deaerator of bypass flow to feed-
pressure decay, ft storage compartment, lb water flow required to pre-
h„ = enthalpy of condensate enter- M vent transient suction pres-
ing deaerator, Btu/lb M' = = adjusted mass of sure decay
h = enthalpy of saturated water 1 —R Rmxx = maximum required bypass
in deaerator at the instant water in deaerator storage ratio; maximum bypass
of load rejection (corre- compartment, lb ratio required during tran-
sponding to pi), Btu/lb M„, = mass of water in mixing zone, sient period
h% = enthalpy of saturated water lb
Ms = mass of water in pump suc- Vi = specific volume of saturated
in deaerator. at the end of water in deaerator (corre-
transient (corresponding to tion line, lb
M, sponding to pd), cu ft/lb
p>), Btu/lb
hi = enthalpy of warm condensate M„' = = adjusted mass of va = specific volume of saturated
entering deaerator at the 1 —R water at pump suction
water in pump suction line, (corresponding to ps), cu
time of load rejection, Btu/
lb ft/lb
lb
• Mw = mass of warm condensate x = cumulative mass of feed-
hs = enthalpy of hot-well con- :
contained in low-pressure
densate, Btu/lb water has entered boiler
heaters and interconnect- feed pump after load re-
hi = enthalpy of saturated water ing piping, lb
in deaerator after x lb of jection, lb
(NPSH)r. = required NPSH at pump
feedwater has entered the suction, ft Wb = bypass flow, lb/min
boiler feed pump, Btu/lb Pi = deaerator pressure at the in- Wf = feedwater flow, lb/min
stant of load rejection, psia
248 / JULY 1974 Transactions of the ASME
hi1
R = (S).
hd ho
where
M.'
LOW PRESSURE
It is also noted that the required bypass ratio increases as the CLOSED FEEDWATER
HEATERS
transient operation proceeds and finally reaches its maximum
required bypass ratio Rmax, when the cold condensate from the Fig. 2 On-off type deaerator bypass system
condenser hotwell is admitted to the pump suction, i.e., x =
M,' + Ma. R remains at Rmax thereafter until the completion
of deaerator pressure decay. sure to the deaerator will drop shortly, followed by deaerator
pressure decay. If another source of steam is used for deaera-
Recommended Protection System tor pegging at a lower pressure, a position switch on the pressure
regulator can be utilized to indicate that the valve is at the closed
The recommended on-off type deaerator bypass system is position. These two signals signify an inadequate steam supply;
shown in Fig. 2. The system should be provided with an auto- thereby, they can be used to initiate bypass valve opening. In
matic quick-opening valve of the on-off type to bypass a pre- order to cover the effect of resident capacity and to prevent the
determined quantity of low temperature condensate. valve from hunting, an adequate: time lag for closing of the by-
The valve should be sized to pass a flow not less than I — pass valve following the restoration of steam supply should bo
e ~ M'iM of the maximum feedwater flow. The available pressure provided.
drop for the valve is generally sufficient, even if the deaerator
level control valve is located upstream of the bypass takeoff. In order to prevent adverse chilling effect on the boiler feed
The minimum available pressure drop is the static head measured pumps, or localized flashing due to stratification, the bypass
between the condensate spray header in the deaerating section flow should not be introduced directly into the pump suction.
and the normal water level in the storage tank, plus pressure A liberal mixing zone between the point of bypass flow injection
drop across the spray nozzles. and the pump suction should be provided. It should be noted,
however, that the mixing zone which constitutes a suction pipe
The signals to initiate the opening of the bypass valve should resident capacity is a direct cause of transient suction pressure
be those that represent an inadequate steam supply to the de- decay. Therefore, the on-off type deaerator bypass system has
aerator. Fig. 2 shows one of several methods that can be used. A its maximum transient suction pressure decay at the end of the
turbine load reduction signal indicates that extraction steam pres- first replacement of the mixing zone.
As noted from the previous analysis, the maximum bypass
flow is required after a cumulative condensate mass of M,' + Mu
has been admitted to the deaerator; i.e., the cold hotwell con-
densate has reached the pump suction. Therefore, the use of
an on-off type bypass valve to introduce the maximum required
bypass flow from the instant of load rejection will suppress the
vapor pressure at the pump suction far below the deaerator
pressure during the earlier part of the transient operation. This
is advantageous because there is a possibility of an unsteady
condition immediately following turbine load rejection. The
introduction of an excess bypass flow during this period will en-
sure no deficiency in suction pressure. In addition, the required
bypass ratio throughout the transient period is fairly constant;
consequently, the low cost on-off type control is sufficient to pro-
tect transient suction pressure decay economically.
the transient period; therefore, the bypass factor defined in the 1 x < Mm
following is also constant.
From h, = hi, and equation (8),
1
6 = (7)
Ru Ah = h, — hd
Deaerator Pressure Decay. If M' is substituted by bM in equa- = (hi - hi) - a(bM - x) + (abM - h + ht)e -x'hM
tions (2) and (4), deaerator pressure decay equations are obtained
as follows: = (h - ht)(l - e-*'hM) + abM ( - j - - 1 + e-x'bM\
\oM )
1 x < M„
Then,
hd = a(bM - x) + hi - (abM - hi + ln)e-^bM (8)
dAh
Feedwater Enthalpy at Pump Suction Without Injection. Except for Both Ah and its first derivative ——- are positive; therefore, Ah
dx
the first replacement of the suction pipe volume, the enthalpy of
increases with an increase in x, and reaches its maximum at
feedwater at the pump suction without injection can be obtained
from equations (8) and (9) with a substitution of x — bMs for x, x = Mm.
and hd' replacing hd.
2 Mm < x < bM,
1 x < bM,
From equations (8) and (14),
hd' = hi (10)
From equations (1), (11), and (13), From equations (8) and (15),
x hM
K = a(M + M, - x) + hi - (abM - h + ht)e' ' (15) M\
Ah = -aM{eM-'M - 1 - <0
3 Ma < x < bM, + Ma
M)
From equations (3), (11), and (13), A negative Ah exists in this period and its magnitude remains
constant. However, owing to nonlinearity between saturated
M^ _ x\ liquid enthalpy and corresponding pressure, negative suction
M + M,+ b b/ pressure decay is not necessarily constant.
<
+ h - (abM - h + hi)e-x'bM (16) 4 Mu < x < bM, + M„
r/7?
2 The maximum required bypass ratio to prevent transient Since — is always positive for any x within this range, the
dx
suction pressure decay throughout the transient period can be
largest R is required when x ~ M/.
accurately determined and is expressed by 1 — e-Ms/M^ ^ i g j j j g
approximately t h e ratio of suction pipe capacity to deaerator
storage capacity. 2 M,' < x < Ma; from the first replacement of t h e suction
line to the first replacement of the low pressure heaters and inter-
3 Other parameters, such as deaerator operating pressure,
connecting pipings.
enthalpy and mass of warm condensate, deaerator pegging pres-
Both ha and h& are expressed by equation (2), except the latter
sure, etc., have no effect on the required bypass ratio.
lags b y Ms'.
4 The required bypass ratio throughout the transient period
is fairly constant. I t is slightly smaller in the beginning but in-
aM,' + (aM' ~ h + In) (1 - eMs'/M')e-x/M'
creases to its maximum when the hotwell condensate has been R =
admitted to t h e deaerator. I t remains a t t h e maximum there- a(M' + M,') - (aM' - hi + hi)eM-''M'e~'x'u'
after.
„MS'/M>
M{ ,-x/M'
a(aM' - hi + hi) 1 -
dR M'
References
dx [a(M' + M,') - (aM' - hi + ht)eM>'/M'e-x'M'\'
1 Liao, G. S., and Leung, P., "Analysis of Feedwater Pump
Suction Pressure Decay Under Instant Turbine Load Rejection,"
JOURNAL OF ENGINEERING FOR POWER, TRANS. ASME, Series A, dR ,
Vol. 34, Apr. 1972, pp, 83-90. Since — is always positive for any x within this range, the
2 Liao, G. S., and Leung, P., Authors' Closure to the foregoing dx
paper. largest R is required when x = Mu.
3 Karassik, I. J., "Certain Aspects of High-Pressure Centrifugal
Pumping Cycles," TRANS. ASME, Vol. 68, Jan. 1946, pp. 65-74. 3 Ma < x < M,' + Ma; the hot-well condensate entered the
4 Karassik, I. J., "Boiler Feed Pump Control," 17. S. Patent No. deaerator but has not yet reached the pump suction.
2,372,087, Mar. 20, 1945.
5 Baron, S., "Detect BF Pump Load-Drop Cavitation Mathe- Since ho and hd are expressed by equations (3) and (4), whereas
matically," Power Engineering, May 1954, pp. 69-72. h^ is expressed by equation (2) with a lag of M/,
! '/»„
S\
tr"
1/
/
* VAPOR PRESSURE
WITHOUT BYPASS
!
»4J
M
M * M e
Fig. 3 Deaerator pressure and pump suction vapor pressure under transient
dR
Let- 0. and solve for x.
dx
M.' + M„
This signifies t h a t maximum bypass ratio Rmax is required
when x = M.' + Ma.
Substituting x by M,' + Mw one obtains
Rn = 1 _ e-M,'/M' = i - e-M,/M
R = 1 - MJM
which is equal to Rw
APPENDIX B
Example Calculations
Data
pi = 150 psia, hi = 330.6 B t u / l b
=P2 20 psia, h = 196.27 B t u / l b
hi = 272 B t u / l b
hi = 82 B t u / l b
M = 470,000 lb (5 min storage)
Ma = 134,000 lb
M, = 20,000 lb (two 14-in. lines)
Mm = 10,000 lb
(NPSH) r = 52 ft at 100 percent load
Wf = 94,000 lb/min
CUMULATIVE FEEDWATER, 1000 LBS
Hsl = 95 ft
Hf = 14.0 ft at 14.3 fps Fig. 4 Transient suction pressure decay