Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Protection of Boiler Feed Pomp Against

G. S. LIAO
Engineering Group Supervisor,
Transient Suction Pressure Decay
Los Angeles Power Division,
Bechtel Power Corp., In a previous paper [I],1 the analysis of pump suction pressure decay utilizing the
Los Angeles, Calif, Mem. ASME varying condensate temperature approach was first introduced. Although the paper
provided power plant engineers with an accurate analytical method for determining the
magnitude of feedwater pump suction pressure decay, no protective method to prevent
or alleviate the pressure decay under instant turbine load rejection was mentioned.
As unit size has rapidly increased in recent years, the power plant deaerator requires
not only a larger storage capacity but also must be elevated higher to protect the boiler
feed pumps against suction pressure decay under load rejection. Since this trend is
expected to continue, the cost of supporting the power plant deaerator may soon become
prohibitive. Several protective methods have been previously introduced. However, the
evaluation of the methods was invariably based on the constant-condensate-temperature
approach, which is not suitable for central station regenerative cycle units. This paper
reevaluates those methods in general and recommends the on-off type deaerator by-
pass system as the most effective and economical method. The use of this protective
method will not only reduce deaerator storage capacity to the absolute minimum
as required solely for surge, but will also largely preclude the provision of additional
static head for instant load reduction. As a result, enormous savings can be expected
both from the deaerator itself and its supporting structures. The magnitude of savings in
supporting structures alone may amount to more than a half million dollars for a 750
MW fossile unit. Based on the varying condensate temperature approach, mathe-
matical equations expressing the deaerator pressure decay as well as design parameters
required for designing the protective system have been derived. The paper also presents
a detailed description of the recommended protective system and discusses some ad-
vantages of this system over the others. Finally, a few engineering examples are in-
cluded to illustrate the application in system design.

Introduction suction pressure decay under instant turbine load rejection was
published recently [1]. The analysis revealed that the transient
L HE RAPID INCREASE in power generating unit ca- suction pressure decay increases as boiler feed pump size in-
pacity in recent years has necessitated the installation of corre- creases. In order to handle such an increasing transient suction
spondingly larger boiler feed pumps in central stations. Be- pressure decay, a deaerator not only requires a larger storage
cause of this growth in pump size, the provision of a sufficient volume but also must be elevated higher. However, raising a
static suction head to cope with the suction pressure decay under deaerator equipped with a large storage tank can be very costly
transient load reduction becomes increasingly difficult and in an earthquake area; it may also present the problem of freeze
costly. A thorough analysis of determining the boiler feed pump protection, if the deaerator is to be located above the power plant
enclosure in a locality with severely cold weather.
It is this ever-increasing transient suction pressure decay which
requires the introduction of some protective methods. The ideal
1 solution would be to prevent transient suction pressure decay, so
Numbers in brackets designate References at end of paper.
Contributed by the Power Division and presented at the Winter that the pump suction system could be designed only for maxi-
Annual Meeting, Detroit, Mich., November 11-15, 1973, of THE mum steady turbine load operation. If the provision of addi-
AMERICAN SOCIETY OF MECHANICAL ENGINEERS. Manuscript re-
ceived at ASME Headquarters, July 10, 1973. Paper No. 73- tional suction head for transient suction pressure decay is not
WA/Pwr-1. required, there are two immediate advantages: the reduction

Journal of Engineering for Power JULY 1974 / 247


Copyright © 1974 by ASME

Downloaded From: http://gasturbinespower.asmedigitalcollection.asme.org/ on 01/29/2016 Terms of Use: http://www.asme.org/about-asme/terms-of-use


in deaerator height equal to the magnitude of transient suction with some example calculations to illustrate the application and
pressure decay, and the use of a smaller deaerator storage tank to substantiate the merits of the system in actual design.
sized merely for system surge.
Several approaches for protecting boiler feed pumps against
transient suction pressure decay were offered previously [3-15]. Protection Against Transient Suction Pressure Decay
However, the quantitative analysis justifying these approaches The available approaches and methods, as well as pump suc-
was generally limited, and was conducted invariably on the basis tion system parameters, for protecting boiler feed pumps from
of assuming the temperature of condensate entering the deaerator transient suction pressure decay are summarized in the following:
to be constant. Since this constant-condensate-temperature
assumption deviates considerably from the actual transient 1 Increasing static suction head by raising deaerator;
conditions of regenerative cycle units, the direct application of 2 Increasing deaerator storage capacity; '
the existing quantitative analysis in system design may result in 3 Reducing suction pipe resident capacity;
significant error. 4 Increasing low pressure heater and interconnecting piping
It is the purpose of this paper to determine the optimum pro- volume;
tective method, which is not only fully substantiated by technical 5 Lowering deaerator operating pressure;
analysis but also applicable to regenerative,cycle power generat- 6 Reducing .temperature rise of condensate in deaerator
ing units. Following the reappraisal of those existing processes relative to temperature rise in low pressure heaters under normal
and approaches, on-off type deaerator bypass system has been operation; r
determined to be the most effective and inexpensive method. 7>; Adding antiflash baffle in deaerator;
Since bypassing large quantities of cold and nondeaerated con- 8 Increasing feedwater flow by recirculation;
densate across the deaerator is objectionable, the bypass flow 9 Injecting steam into, deaerator;
should be carefully determined and limited to a minimum. Ac- 10 Injecting cold water into pump suction.
cordingly, a comprehensive analysis for the on-off type deaerator
bypass system was conducted on the basis of varying temperature Of the foregoing 10 methods, only approaches 9 and 10 are
of condensate entering the deaerator. From this analysis, mathe- capable of effectively preventing transient suction pressure decay,
matical equations expressing deaerator pressure, pump suction whereas the other approaches merely accommodate or alleviate
vapor pressure, required bypass flow, and maximum transient it. Since approaches 1 and 2 require heavier supporting struc-
suction pressure decay were derived. This paper also presents tures,, a larger deaerator storage tank, or both, these are con-
a description of the recommended protective system, together sidered to be the most expensive methods. Although it can

.Nomenclature.

a = (ht — hi)/Mu = enthalpy hi' = enthalpy of saturated water pi = final deaerator pressure; pres-
gradient of warm conden- at pump suction after x lb sure at which deaerator is
sate, Btu/lb 2 of feedwater has entered pressurized by other source
1 Ms the boiler feed pump (with- of steam, psia
= e M = out bypass), Btu/lb = deaerator pressure after x lb
Pd
factor ha = enthalpy of saturated water of feedwater has entered
Hai = static suction head for boiler at pump suction after x lb the boiler feed pump, psia
of feedwater has entered
feed pumps, ft = vapor pressure at pump suc-
the, boiler feed pump (with V-
Hf = friction loss through pump tion after x lb of feedwater
bypass), Btu/lb
suction line, ft Ah =-h, - ta, Btu/lb has entered the boiler feed
AH = transient suction pressure de- Ahmax = maximum Ah during tran- pump, psia
cay, ft sient period, Btu/lb R = required bypass ratio; ratio
Affmax = maximum transient suction M = mass of water in deaerator of bypass flow to feed-
pressure decay, ft storage compartment, lb water flow required to pre-
h„ = enthalpy of condensate enter- M vent transient suction pres-
ing deaerator, Btu/lb M' = = adjusted mass of sure decay
h = enthalpy of saturated water 1 —R Rmxx = maximum required bypass
in deaerator at the instant water in deaerator storage ratio; maximum bypass
of load rejection (corre- compartment, lb ratio required during tran-
sponding to pi), Btu/lb M„, = mass of water in mixing zone, sient period
h% = enthalpy of saturated water lb
Ms = mass of water in pump suc- Vi = specific volume of saturated
in deaerator. at the end of water in deaerator (corre-
transient (corresponding to tion line, lb
M, sponding to pd), cu ft/lb
p>), Btu/lb
hi = enthalpy of warm condensate M„' = = adjusted mass of va = specific volume of saturated
entering deaerator at the 1 —R water at pump suction
water in pump suction line, (corresponding to ps), cu
time of load rejection, Btu/
lb ft/lb
lb
• Mw = mass of warm condensate x = cumulative mass of feed-
hs = enthalpy of hot-well con- :
contained in low-pressure
densate, Btu/lb water has entered boiler
heaters and interconnect- feed pump after load re-
hi = enthalpy of saturated water ing piping, lb
in deaerator after x lb of jection, lb
(NPSH)r. = required NPSH at pump
feedwater has entered the suction, ft Wb = bypass flow, lb/min
boiler feed pump, Btu/lb Pi = deaerator pressure at the in- Wf = feedwater flow, lb/min
stant of load rejection, psia
248 / JULY 1974 Transactions of the ASME

Downloaded From: http://gasturbinespower.asmedigitalcollection.asme.org/ on 01/29/2016 Terms of Use: http://www.asme.org/about-asme/terms-of-use


alleviate transient suction pressure decay, approach 3 is not an pass flow is generally high when deaerator pressure is high and
effective solution because the pipe resident capacity cannot be decreases as deaerator pressure decays. This minimizes the tem-
completely eliminated. Approaches 4, 5, 6, and 7 are either perature difference between the deaerator water and bypass
ineffective or uncontrollable by power plant engineers. flow, thereby not only keeping the bypass flow throughout the
Contrary to the foregoing, approach 8 is one of the positive transient period fairly constant but also reducing the volume.of
solutions for alleviating transient suction pressure decay. Boiler the required mixing zone in the suction line.
feed pump recirculation, based on a numerical case study apply-
ing the constant-condensate-temperature assumption to each Concerning the actuation of deaerator bypass, an on-off type
subdivided step, was found to be an effective measure many control is considered to be the most effective and inexpensive
years ago, although no general quantitative conclusion was method for protecting boiler feed pumps against transient suc-
reached [6]. It was not determined until recently that the maxi- tion pressure decay. The "on-off type deaerator bypass system"
mum transient suction pressure decay with a constant storage recommended in this paper is to bypass just sufficient flow to
capacity will vary directly proportional to the effective suction suppress the vapor pressure entering the pumps equal to or below
pipe resident capacity which, in turn, varies in proportion to the the deaerator pressure, thereby preventing suction pressure decay
ratio of condensate flow to feedwater flow [2], Therefore, the under load rejection. Karassik introduced an excellent elaborate
magnitude of the suction pressure decay can be reduced propor- control system to protect boiler feed pumps from N P S H defi-
tionally, if the ratio of condensate flow to feedwater flow is in- ciency [4, 15]. The major difference is that Karassik's method
tentionally reduced by feedwater recirculation. For example, uses a continuous modulating control of bypass flow to satisfy
if feedwater flow is increased 25 percent by recirculation, the the pump required N P S H under any conditions, whereas the
ratio of condensate flow to feedwater flow reduces to 80 percent, method recommended in this paper is an on-off type actuated
as does the maximum suction pressure decay. If the boiler feed under rapid load reduction to prevent transient suction pressure
pump minimum flow is being returned to the deaerator, a recircu- decay. The signals to actuate the bypass valve are entirely
lation can be readily achieved by overriding the minimum flow different; Karassik uses the actually measured N P S H at the pump
control to have the valve opened under load rejection. How- suction, whereas this method utilizes signals indicating turbine
ever, the same objective can be achieved with the provision of a load reduction and cutoff of outside steam supply.
separate control valve or an independent line with a valve. A similar on-off type deaerator bypass system has been used
before [15]; it diverts most of the condensate flow to the boiler
Approach 9 is one of the two most effective methods, but has
feed pump suction. This system has the following disadvan-
the following disadvantages:
tages :
1 A large quantity of auxiliary steam, which is not available
from the main unit under load rejection, must be supplied from 1 It requires an oversized bypass valve and line and is,
other sources. therefore, costly.
2 Since deaerator pressure must be reduced to the pressure 2 It can cause a chilling effect on the pump.
corresponding to a new load after a sudden load reduction, the 3 Since most of condensate flow is being bypassed, the de-
steam injection.system must allow deaerator pressure to decay, aerator receives only a small portion of condensate flow, resulting
and is thereby unable to avoid transient suction pressure decay. in a very slow deaerator pressure decay. This system un-
3 This method must rely on the other systems which supply necessarily prolongs the transient operation and thereby intro-
auxiliary steam and, therefore, is less reliable. duces a relatively large quantity of nondeaerated water into the
• 4 Both initial cost and operating cost of the steam injection boiler.
system could be higher. •' • ' 4 It cannot protect the pump from suction pressure decay
under gradual turbine load reduction.
Approach 10, the injection of cold water into the pump suction,
has been known for many years [3, 4], and is a very, effective The on-off type deaerator bypass system in connection with a
method for protecting, boiler feed pumps, against transient suc- precise determination of the bypass flow presented herein will
tion pressure decay. In addition, this is the only method t h a t is eliminate the foregoing problems.
capable of almost completely preventing transient suction pres-
sure decay. However,, there are two disadvantages associated Maximum Required Bypass Ratio
with this method; i.e., the introduction of nondeaerated water In order to simplify the analysis, it is assumed that the tem-
into the boiler, and the possibility of chilling the pumps. In perature of the bypass flow injected into the pump suction is
order to avoid or minimize the foregoing adverse effects, an ac- equal to the temperature of the condensate entering the deaerator.
curate determination of bypass, flow is essential. Since it is
If R represents required bypass ratio, condensate admitted to the
generally less.than .10 percent of total feedwater flow, the injec-
deaerator can be expressed by a ratio 1 — R as shown in Fig. 1.
tion of cold water is not considered detrimental to boilers, es-
The enthalpy of condensate entering the deaerator together with
pecially when the injection is so infrequent and for such a short
deaerator pressure decay equations for the bypass system can be
duration: An abrupt change in feedwater temperature at the
derived in a similar manner as (1):
pump suction can also, be minimized, if the quantity of bypass
flow is precisely determined and held to a minimum, and an ade- 1. x < M„
quate mixing zone ahead of the pump suction, is provided to avoid
stratification. I t should .be noted, however, that this.mixing ha = hi — ax (1)
zone, due to its resident capacity, will result in a suction pressure
decay, which must be compensated for by an additional static h„ = o ( M ' - x) + h - {aW - h + hi)e-*'M' (2)
head.
2. x > Ma
Although cold injection water can be obtained from, several
sources, bypassing a portion of the condensate flow across the ho = h (3)
deaerator is considered superior for the following reasons:
hi = h + [aM'(eM»/M' - 1) + (/>, ~ hi)]e-*'M' (4)
1 The deaerator bypass flow is the most reliable source of
cold injection water supply; it is available whenever the deaerator where
is being fed with the condensate causing transient suction pressure
decay.
2 With regenerative cycle units; the temperature of the by-

Journal of Engineering for Power JULY 1974 / 249

Downloaded From: http://gasturbinespower.asmedigitalcollection.asme.org/ on 01/29/2016 Terms of Use: http://www.asme.org/about-asme/terms-of-use


In order to prevent suction pressure decay under instant tur-
bine load rejection, the temperature of feedwater at the pump
suction should be suppressed to that corresponding to the de-
aerator. If the enthalpies of water inside the deaerator and at
the pump suction before mixing with bypass flow are hd and hd',
respectively, the required bypass ratio R to reduce hd to hd at
the pump suction can be obtained from mass and energy balance
as follows:

hi1
R = (S).
hd ho

The analysis presented in Appendix A concludes that the maxi-


mum required bypass ratio throughout the transient operation
can be expressed as
•M.'/M'
Rm 1 - e =_ 1 -M,/M (6)

where

M.'

LOW PRESSURE
It is also noted that the required bypass ratio increases as the CLOSED FEEDWATER
HEATERS
transient operation proceeds and finally reaches its maximum
required bypass ratio Rmax, when the cold condensate from the Fig. 2 On-off type deaerator bypass system
condenser hotwell is admitted to the pump suction, i.e., x =
M,' + Ma. R remains at Rmax thereafter until the completion
of deaerator pressure decay. sure to the deaerator will drop shortly, followed by deaerator
pressure decay. If another source of steam is used for deaera-
Recommended Protection System tor pegging at a lower pressure, a position switch on the pressure
regulator can be utilized to indicate that the valve is at the closed
The recommended on-off type deaerator bypass system is position. These two signals signify an inadequate steam supply;
shown in Fig. 2. The system should be provided with an auto- thereby, they can be used to initiate bypass valve opening. In
matic quick-opening valve of the on-off type to bypass a pre- order to cover the effect of resident capacity and to prevent the
determined quantity of low temperature condensate. valve from hunting, an adequate: time lag for closing of the by-
The valve should be sized to pass a flow not less than I — pass valve following the restoration of steam supply should bo
e ~ M'iM of the maximum feedwater flow. The available pressure provided.
drop for the valve is generally sufficient, even if the deaerator
level control valve is located upstream of the bypass takeoff. In order to prevent adverse chilling effect on the boiler feed
The minimum available pressure drop is the static head measured pumps, or localized flashing due to stratification, the bypass
between the condensate spray header in the deaerating section flow should not be introduced directly into the pump suction.
and the normal water level in the storage tank, plus pressure A liberal mixing zone between the point of bypass flow injection
drop across the spray nozzles. and the pump suction should be provided. It should be noted,
however, that the mixing zone which constitutes a suction pipe
The signals to initiate the opening of the bypass valve should resident capacity is a direct cause of transient suction pressure
be those that represent an inadequate steam supply to the de- decay. Therefore, the on-off type deaerator bypass system has
aerator. Fig. 2 shows one of several methods that can be used. A its maximum transient suction pressure decay at the end of the
turbine load reduction signal indicates that extraction steam pres- first replacement of the mixing zone.
As noted from the previous analysis, the maximum bypass
flow is required after a cumulative condensate mass of M,' + Mu
has been admitted to the deaerator; i.e., the cold hotwell con-
densate has reached the pump suction. Therefore, the use of
an on-off type bypass valve to introduce the maximum required
bypass flow from the instant of load rejection will suppress the
vapor pressure at the pump suction far below the deaerator
pressure during the earlier part of the transient operation. This
is advantageous because there is a possibility of an unsteady
condition immediately following turbine load rejection. The
introduction of an excess bypass flow during this period will en-
sure no deficiency in suction pressure. In addition, the required
bypass ratio throughout the transient period is fairly constant;
consequently, the low cost on-off type control is sufficient to pro-
tect transient suction pressure decay economically.

Analysis of Qti-Off Type Deaerator Bypass System


Some conservative assumptions that simplify analysis while
V
v
h
d /
'
BYPASS
VALVE
' still taking the mixing zone into consideration are as follows:
1 The temperature of bypass flow at the pump suction (not
at the point of injection) is equal to the temperature of con-
Fig. T Deaerator-pump suction system under transient densate at the deaerator inlet.

250 / JULY 1974 Transactions of the ASME

Downloaded From: http://gasturbinespower.asmedigitalcollection.asme.org/ on 01/29/2016 Terms of Use: http://www.asme.org/about-asme/terms-of-use


M, From equations (3), (12), and (13),
2 Adjusted pump suction resident capacity is
-1 Amax
, 'M. - Mm h, = hi + [abM(eM»'hM - 1) + (fci - hi)]e-^bM (17)
stead of — + Mm.
A *tmax
3 The bypass ratio is constant and equal to i? m a x throughout Differential Enthalpy Between hs and hd, or Ah,

the transient period; therefore, the bypass factor defined in the 1 x < Mm
following is also constant.
From h, = hi, and equation (8),
1
6 = (7)
Ru Ah = h, — hd

Deaerator Pressure Decay. If M' is substituted by bM in equa- = (hi - hi) - a(bM - x) + (abM - h + ht)e -x'hM
tions (2) and (4), deaerator pressure decay equations are obtained
as follows: = (h - ht)(l - e-*'hM) + abM ( - j - - 1 + e-x'bM\
\oM )
1 x < M„
Then,
hd = a(bM - x) + hi - (abM - hi + ln)e-^bM (8)

2 x > Mu dAh hi — hi -x/bM


dx -• 0 ( 1 - . - ^ ) + \ M -
hi =h+ [abM (fiMJbM _ i ) + (/n _ hi-)]e-x/bM (9)

dAh
Feedwater Enthalpy at Pump Suction Without Injection. Except for Both Ah and its first derivative ——- are positive; therefore, Ah
dx
the first replacement of the suction pipe volume, the enthalpy of
increases with an increase in x, and reaches its maximum at
feedwater at the pump suction without injection can be obtained
from equations (8) and (9) with a substitution of x — bMs for x, x = Mm.
and hd' replacing hd.
2 Mm < x < bM,
1 x < bM,
From equations (8) and (14),
hd' = hi (10)

2 bMs < x < bM, + M„ Aft = ( ( A , - hi)(e-*?bM - -\

hd' = a[b(M + M.) - x] + ht x bM


+ a bM(l - e- ? ) - -
- (abM - h + hi)be-^hM (11) b

3 x > bM, + Ma dAh 1


[aM - (abM - h + hi)e~x>bM]
dx ~ bM
hd' = h + [abM(eM»>bM - 1) + (h - hi)]be"x/bM (12)
Vapor Pressure at Pump Suction. The enthalpies of feedwater at
If x = 0,
the boiler feed pump suction after mixing with the bypass flow Ah = -(hi - hi)(l - e-M»'M) < 0
can be determined by mass and energy balance and are expressed
by
If x = bM„
h, = h0 + 7 (hd' — h0)
b
(13) Ah -aMy eM,/M _ x
M]
<0

With a substitution of suitable and adequate equations into dAh hi — hi


equation (13), the vapor pressure at the pump suction can be > 0
dx b2M
expressed as follows:
The foregoing analysis indicates that, after injection water has
1 x < bM,
reached the pump suction, deaerator pressure pd is greater than
From equations (1), (10), and (13), pump suction vapor pressure p,; therefore, a negative suction
pressure decay exists throughout this period. However, this
negative suction pressure decay is decreasing as x increases when
h. = T [hi + (hi - ax)(b - 1)] (14)
o x = bM,.

2 bM, < x < Mw 3 bM, < x < Ma

From equations (1), (11), and (13), From equations (8) and (15),
x hM
K = a(M + M, - x) + hi - (abM - h + ht)e' ' (15) M\
Ah = -aM{eM-'M - 1 - <0
3 Ma < x < bM, + Ma
M)

From equations (3), (11), and (13), A negative Ah exists in this period and its magnitude remains
constant. However, owing to nonlinearity between saturated
M^ _ x\ liquid enthalpy and corresponding pressure, negative suction
M + M,+ b b/ pressure decay is not necessarily constant.
<
+ h - (abM - h + hi)e-x'bM (16) 4 Mu < x < bM, + M„

4 x > bM, + Ma From equations (9) and (16),

Journal of Engineering for Power JULY 1974 / 251

Downloaded From: http://gasturbinespower.asmedigitalcollection.asme.org/ on 01/29/2016 Terms of Use: http://www.asme.org/about-asme/terms-of-use


bM, + Ma - x 6 Baron, S., "Detect Recirculating BF Pump Load-Drop Cavi-
Ah = -aM
Ik bM- )'
tation Mathematically," Power Engineering, July 1954, pp. 75-77.
7 Karassik, I. J., "Steam Power Plant Clinic—Part III," Com-
bustion, Oct. 1958, pp. 55-56.
8 karassik, I. J., Bosworth, G. H., and Elston, W. D., "Sudden
+ :5!\ bM J+ " '' J Load Drop in Open Feed Cycles of Steam Turbine Power Plants,"
The International Operating Engineer, July, Aug., Sept., and Dee
Afc, = 0, when a; = 6M", + Af„ 1957, and Jan. 1958.
9 Karassik, I. J., "Steam Power Plant Clinic—No. 4," Power
The negative suction pressure decay continues to decrease as x Engineering, Nov. 1957.
10 Karassik, I. J., "Steam Power Plant Clinic—Part VIII,"
increases in this period, and finally diminishes a t the end of this Combustion, May 1959, pp. 53-55. ' '
period. 11 Karassik, I. J., Zabel, L. E., and Hess, E. K., "Steam Power
Plant Clinic—Part XIII," Combustion, Nov. 1959, pp. 49-51.
5 x > bM„ + Ma 12 Hardie, P. H., Karassik, I, J., and Zabel, L. E., "Protecting
Boiler Feed Pumps Against Flashing," Combustion, Feb. 1960, pp.
Since deaerator pressure decay and pump suction pressure decay 37-40.
are identical, Ah is equal to zero; consequently, no suction pres- 13 Karassik, I. J., "Steam Power Plant Clinic—Part XVIII,"
Combustion, July 1960, pp. 51-53.
sure decay exists during this period. 14 Strub, R. A., "Reduction of the Suction Pressure of Boiler
Maximum Suction Pressure Decay. From t h e analytical results Feed Pumps as a Result of Sudden Load Drops," Sulzer Technical
obtained in the section entitled "Vapor Pressure at Pump Suc- Review No. 3, 1960,
tion," the maximum suction pressure decay will occur at the end 15 Karassik, I. J., "Steam Power Plant Clinic—Part XXXII,"
Combustion, June 1962, pp. 48-50.
of the first replacement of the mixing zone; i.e., x = Mm. T h e
deaerator pressure p,i can be obtained from equation (8) by sub-
stituting M„t for x, whereas pump suction vapor pressure p , re- APPENDIX A
mains pi_. This positive suction pressure decay must be provided
in the form of static head over and above t h e normal operating Determination of Maximum Required Bypass Ratio
requirement.
The whole transient operation is divided into four periods in
determining Umax-
Conclusion Ms . , , . .
In order to restrain t h e ever-increasing cost of providing an 1 % < Ms' — —; from the instant of load rejection to the
adequate suction head for boiler feed pump to handle transient 1 — R
suction pressure decay, t h e on-off type deaerator bypass system first replacement of the pump suction line.
substantiated by the analytical solution presented in this paper Since h/ — hi, and h<s and h,i are expressed by equations (1)
is recommended. The analyses reveal t h e following major and (2), required bypass ratio can be obtained from equation (5).
points: _ (fe - hi) - a(M' - x) + (aM' - h, + hje-*/*1'
h — hi + ax
1 Cold water injection into the pump suction line in the form
of deaerator bypass is a reliable and very effective method for
If M' is assumed constant, the first derivative of R with respect
avoiding transient suction pressure decay.
to x is

a>M'i e~*<M' lex'M' - 1- ~ \ + {^ - h,)(ax + hi - hi)e-^M'


dR
dx M'(hi - ht + axf

r/7?
2 The maximum required bypass ratio to prevent transient Since — is always positive for any x within this range, the
dx
suction pressure decay throughout the transient period can be
largest R is required when x ~ M/.
accurately determined and is expressed by 1 — e-Ms/M^ ^ i g j j j g
approximately t h e ratio of suction pipe capacity to deaerator
storage capacity. 2 M,' < x < Ma; from the first replacement of t h e suction
line to the first replacement of the low pressure heaters and inter-
3 Other parameters, such as deaerator operating pressure,
connecting pipings.
enthalpy and mass of warm condensate, deaerator pegging pres-
Both ha and h& are expressed by equation (2), except the latter
sure, etc., have no effect on the required bypass ratio.
lags b y Ms'.
4 The required bypass ratio throughout the transient period
is fairly constant. I t is slightly smaller in the beginning but in-
aM,' + (aM' ~ h + In) (1 - eMs'/M')e-x/M'
creases to its maximum when the hotwell condensate has been R =
admitted to t h e deaerator. I t remains a t t h e maximum there- a(M' + M,') - (aM' - hi + hi)eM-''M'e~'x'u'
after.
„MS'/M>
M{ ,-x/M'
a(aM' - hi + hi) 1 -
dR M'
References
dx [a(M' + M,') - (aM' - hi + ht)eM>'/M'e-x'M'\'
1 Liao, G. S., and Leung, P., "Analysis of Feedwater Pump
Suction Pressure Decay Under Instant Turbine Load Rejection,"
JOURNAL OF ENGINEERING FOR POWER, TRANS. ASME, Series A, dR ,
Vol. 34, Apr. 1972, pp, 83-90. Since — is always positive for any x within this range, the
2 Liao, G. S., and Leung, P., Authors' Closure to the foregoing dx
paper. largest R is required when x = Mu.
3 Karassik, I. J., "Certain Aspects of High-Pressure Centrifugal
Pumping Cycles," TRANS. ASME, Vol. 68, Jan. 1946, pp. 65-74. 3 Ma < x < M,' + Ma; the hot-well condensate entered the
4 Karassik, I. J., "Boiler Feed Pump Control," 17. S. Patent No. deaerator but has not yet reached the pump suction.
2,372,087, Mar. 20, 1945.
5 Baron, S., "Detect BF Pump Load-Drop Cavitation Mathe- Since ho and hd are expressed by equations (3) and (4), whereas
matically," Power Engineering, May 1954, pp. 69-72. h^ is expressed by equation (2) with a lag of M/,

252 / JULY 1974 Transactions of the ASME

Downloaded From: http://gasturbinespower.asmedigitalcollection.asme.org/ on 01/29/2016 Terms of Use: http://www.asme.org/about-asme/terms-of-use


V y OEAERATOR PRESSURE
, . VAPOR PHES5URL ^ ^
1 1 WITH BYPASS ' ^

! '/»„
S\
tr"
1/
/
* VAPOR PRESSURE
WITHOUT BYPASS

!
»4J

M
M * M e

Fig. 3 Deaerator pressure and pump suction vapor pressure under transient

B = 1 Without Protective System. If the analytical method introduced


previously [1] is applied,
[aM' (eM"/M' - 1) + (hi - ht)] e - * / M '
a(M' + M,' + Ma - x) - (aM' - h + hi)eM''/M' e~x'M' Affmax = 27.9 ft

dR _ a[aM' (eM»'M' - 1) + (h - ht)}(Ms' + Ma - x)e~x/M'


Hx ~ M'[a(M' + M.' + Ma - x) - (aM' - h + hs)eM''/M'e-x/M'V

dR
Let- 0. and solve for x.
dx

M.' + M„
This signifies t h a t maximum bypass ratio Rmax is required
when x = M.' + Ma.
Substituting x by M,' + Mw one obtains

Rn = 1 _ e-M,'/M' = i - e-M,/M

4 x > Ms' + Mu; after the hot-well condensate reaches the


pump suction.
Both hd and hi' are expressed by equation (4), except the
latter lags by M,'. If the foregoing equations together with ha =
h are substituted into equation (5), R is obtained as a constant.

R = 1 - MJM

which is equal to Rw

APPENDIX B
Example Calculations
Data
pi = 150 psia, hi = 330.6 B t u / l b
=P2 20 psia, h = 196.27 B t u / l b
hi = 272 B t u / l b
hi = 82 B t u / l b
M = 470,000 lb (5 min storage)
Ma = 134,000 lb
M, = 20,000 lb (two 14-in. lines)
Mm = 10,000 lb
(NPSH) r = 52 ft at 100 percent load
Wf = 94,000 lb/min
CUMULATIVE FEEDWATER, 1000 LBS
Hsl = 95 ft
Hf = 14.0 ft at 14.3 fps Fig. 4 Transient suction pressure decay

Journal of Engineering for Power JULY 1974 / 253

Downloaded From: http://gasturbinespower.asmedigitalcollection.asme.org/ on 01/29/2016 Terms of Use: http://www.asme.org/about-asme/terms-of-use


The minimum required static head is: Wb = Wf (1 - e~M"M) = 33401b/min
Hal = (NPSH) r + Hf + AHmaK = 93.9 ft < 95 ft provided
The elevation of the deaerator is, therefore, adequate. which amounts to only 3.55 percent of the maximum feedwater
Recommended Bypass System. With this protective system, Hst flow.
can be reduced. If H3t is assumed to be 74 ft, M, will be 17,000 A computer was used to calculate deaerator pressure and pump
lb proportionally. suction vapor pressure for the whole transient operation. The
The maximum suction pressure decay due to the mixing zone results were plotted in Pig. 3 to compare the subject protective
capacity Mm can be determined by substituting Mm for x into system with the ordinary system. I t indicates that there are
equation (8). negative suction pressure decays when cumulative feedwater *
is within the range between Mm and Ma + M%eM*>u; therefore
hi = 329.1 B t u / l b this protective system provides the pump with some excess
available N P S H during this period.
Since h, = hi, the corresponding pressures and liquid specific
Recommended Bypass System with 3-Minute Deaerator Storage Ca-
volumes are: pacity. Based on:

Pd = 147.60 psia, vd = 0.01807 M = 282,000 lb and M, = 17,600 lb,


p, = 150 psia, v, = 0.01809
we obtain
Then,
Affmax = 10.0 ft
/0.01807 + 0.01809 \
Affmax = (150 - 147.6)( 1 = 6.3 ft
which is only 3.7 ft more than the deaerator with 5 min storage.
The required bypass flow increases to 5690 Ib/min, or 6.05
Hence, the minimum required static head is, percent of maximum feedwater flow. Although it results in a
slight increase in both deaerator height and bypass flow, a re-
H„ = 52 + 14 + 6.3 duction in deaerator storage capacity from 5 min to 3 min can be
= 72.3 ft, which is smaller than 74 ft assumed. a significant capital saving both from deaerator and its support-
ing structure.
Therefore, the bypass system reduces the elevation of the de- The transient suction pressure decays in feet of liquid for the
aerator by 21 ft. The required bypass flow is then, foregoing three cases are shown in Fig. 4.

DISCUSSION These controls, in their initial conception, were to be actuated


by signals originated from a measurement of the NPSH at the
I. J. Karrasik 2 pump suction, whereas Mr. Liao prefers and recommends signals
indicating turbine load reduction and cutoff of outside steam sup-
ply. It may well be that Mr. Liao is right and that his type of
control is both less expensive and more reliable. Basically, the
Nothing gives an engineer as much pleasure as the opportunity choice of the signal is not important. What is extremely impor-
to discuss a technical paper on a familiar subject, written by a tant is that the initiation of protective action be as near to 100
congenial author from a point of view that is compatible to one's percent reliable as possible. If Mr. Laio finds that his choice of
own. Such is certainly the case today as I review Mr. Liao's paper. signal has greater reliability, then by all means it should be pre-
That the subject is familiar to me can be readily demonstrated by ferred.
examining Mr. Liao's list of references; that his point of view is I am, however, just a bit unhappy that, my good friend Liao has
compatible with mine is apparent from his recommendation to pro- ascribed to me the intention of diverting "most of the condensate
tect boiler feed pumps against transient conditions by means of a flow to the boiler' feed suction." If I had, I would have to agree
control which I patented in 1945, even though Mr. Liao recom- with him that all the disadvantages he ascribes to such an ap-
mends modifying it somewhat; finally you will have to take my proach would indeed exist. But I insist on my complete innocence
word for the fact that I find the author of this paper congenial. in this connection. A careful reading of the reference he cites 3 will
All the preceding should not be interpreted to mean that there reveal that, on the contrary, I suggested a very modest bypassing of
are absolutely no differences of opinion between Mr. Liao and condensate flow directly to the boiler feed pump suction. I quote:
myself. But the differences which do exist are not very important, "A nominal admixture of colder water is sufficient to add a sub-
nor do they lead us to widely diverging conclusions or recommen- stantial amount of surplus NPSH to the p u m p . " In the example I
dations. As a matter of fact, Mr. Liao implies some differences used it was only necessary to provide 12.5 percent of the total
which are really nonexistent, as I shall point out later on. flow from the colder condensate source to achieve 50 ft of addi-
Let me first state my complete agreement with Mr. Liao's ap- tional NPSH. I should add that there can be no difference what-
proach to the problem, which is to see that "the wolf must be fed soever in the calculated amount of colder water admixture to
while the sheep remain safe." In other words, he has concentrated achieve a given NPSH increase, given the "immutability" of
on recommending means that would fully protect the boiler feed steam tables and of the formulas for mixing flows of different
pump against the unfavorable effects of sudden load reduction temperatures.
without imposing unnecessary increases in the cost of the deaera- We now come to the differences between the various approach-
tor or of its supporting structure. As he says, this approach es for calculating the effects of sudden load reduction that I have
should produce "enormous savings" in the light of the rapid in- used in the past, and Liao's approach. It is entirely true that, for
creases taking place in the average unit size. But I submit that the sake of simplicity, I had neglected changes in the temperature
the development of the automatic protection controls to which I of the condensate entering the deaerator after a load drop. The
addressed myself as early as 1945 was intended for the same pur- results thus calculated were on the conservative side, but not
pose.
3
Karassik, I. J., "Steam Power Plant Clinic—Part XXXII," Combustion
2
Vice-President and Chief Consulting Engineer, Worthington Corp. June 1962, pp. 48-50, (Worthington Reprint 45-RP-1014-37).

254 / JULY 1974 Transactions of the ASME

Downloaded From: http://gasturbinespower.asmedigitalcollection.asme.org/ on 01/29/2016 Terms of Use: http://www.asme.org/about-asme/terms-of-use

You might also like