Z-D-15/35/55E-..

Active Harmonic Filter with SiC Technology


Operating Instructions

Index 002

Keep for reference!

_________________________________________________________________________________

L-BAL-E321-D 2021/11 Index 002


Operating Instructions Z-D-15/35/55E-..
__________________________________________________________

Content
1 General .............................................................................................................................................4
1.1 Manufacturer............................................................................................................................ 4
1.2 Meaning of the instructions ...................................................................................................... 4
1.3 Validity ..................................................................................................................................... 4
1.4 Terms and definitions .............................................................................................................. 4
1.5 Intended use ............................................................................................................................ 5
1.6 Improper use............................................................................................................................ 5
2 Safety precautions ..........................................................................................................................6
2.1 What this chapter contains ...................................................................................................... 6
2.2 Safety definitions and warning symbols .................................................................................. 6
2.3 General safety information ...................................................................................................... 8
2.4 Safety responsible persons ................................................................................................... 10
2.5 Specification of wires and cables .......................................................................................... 10
2.6 Rest danger ........................................................................................................................... 10
3 Fast start ....................................................................................................................................... 11
3.1 What this chapter contains .................................................................................................... 11
3.2 First check when unpacking .................................................................................................. 11
3.3 Suitability for the application .................................................................................................. 11
3.4 Environment conditions ......................................................................................................... 11
3.5 Check of the installation ........................................................................................................ 12
3.6 Simplified commissioning ...................................................................................................... 12
4 Product-Overview ......................................................................................................................... 13
4.1 What this chapter contains .................................................................................................... 13
4.2 Area of application / Notes on use: ....................................................................................... 13
4.3 Function principle: ................................................................................................................. 13
4.4 Label code ............................................................................................................................. 13
4.5 Rating plate............................................................................................................................ 14
4.6 Storage .................................................................................................................................. 15
4.7 Transport and handling .......................................................................................................... 15
5 Installation instructions ............................................................................................................... 16
5.1 What this chapter contains .................................................................................................... 16
5.2 Mechanical drawings ............................................................................................................. 16
5.2.1 Active harmonic filter Z-D-15E-.. ....................................................................................... 16
5.2.2 Active harmonic filter Z-D-35E-.. and Z-D-55E-.. .............................................................. 17
5.2.3 Mechanical installation ...................................................................................................... 18
_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 2/44


Operating Instructions Z-D-15/35/55E-..
__________________________________________________________
5.3 Electrical wiring ...................................................................................................................... 19
5.3.1 EMC directive .................................................................................................................... 20
5.3.2 Voltage supply ................................................................................................................... 20
5.3.3 LED status display ............................................................................................................. 21
5.3.4 Current transformer wiring ................................................................................................. 22
5.3.5 Active harmonic filter in parallel wiring .............................................................................. 23
5.3.6 Selection of CT (current transformers) .............................................................................. 24
5.3.7 Wiring when using current transformers with high ratio .................................................... 24
5.3.8 EPO and Z-D-15/35/55E-.. ID............................................................................................ 25
5.3.9 Input and output interface .................................................................................................. 26
6 Supervision- and control software ............................................................................................. 27
6.1 What this chapter contains .................................................................................................... 27
6.2 Introduction in the system ...................................................................................................... 27
6.2.1 Log In ................................................................................................................................. 27
6.2.2 Home ................................................................................................................................. 28
6.2.3 Initialize communication .................................................................................................... 29
6.2.4 System configuration ......................................................................................................... 30
6.2.5 Data ................................................................................................................................... 36
6.2.6 Procedure to power on ...................................................................................................... 36
7 Maintenance and check of hardware ......................................................................................... 37
7.1 What this chapter contains .................................................................................................... 37
7.2 Periodicity of maintenance .................................................................................................... 37
7.3 Disposal/Recycling ................................................................................................................ 38
8 Error description and repair ........................................................................................................ 39
8.1 What this chapter contains .................................................................................................... 39
8.2 Typical errors and repairs ...................................................................................................... 39
9 Enclosure ...................................................................................................................................... 40
9.1 Technical Data ....................................................................................................................... 40
9.1.1 Technical Data Active harmonic filter Z-D-15E-.. ............................................................. 41
9.1.2 Technical Data Active harmonic filter Z-D-35E-.. ............................................................. 42
9.1.3 Technical Data Active harmonic filter Z-D-55E-.. ............................................................. 43
9.2 Service information ................................................................................................................ 44

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 3/44


Operating Instructions Z-D-15/35/55E-.. General
__________________________________________________________
1 General
1.1 Manufacturer
The active harmonic filter is a product of ZIEHL-ABEGG SE. The manufacturer is referred to as ZIEHL-
ABEGG in the remainder of these operating instructions.
ZIEHL-ABEGG SE
Heinz-Ziehl-Straße 74653 Künzelsau
phone: +49 (0) 7940 16-0
info@ziehl-abegg.de
http://www.ziehl-abegg.com
Compliance with the following instructions is mandatory to ensure the functionality and safety of the
product. If the following instructions given especially but not limited for general safety, transport, storage,
mounting, operating conditions, start-up, maintenance, repair, cleaning and disposal / recycling are not
observed, the product may not operate safely and may cause a hazard to the life and limb of users and
third parties.
Deviations from the following requirements may therefore lead both to the loss of the statutory material
defect liability rights and to the liability of the buyer for the product that has become unsafe due to the
deviation from the specifications.

1.2 Meaning of the instructions


These instructions instruct you on how to use the specified product safely. They include safety
instructions and information that is necessary for fault-free operation.
• Store the instructions safely on the product for further use. They must be passed on to every
subsequent owner, user or end customer.
• Ensure that all persons performing activities on the product can easily view the instructions at
any time.

1.3 Validity
This instruction applies to:
Active harmonic filter: Z-D-15E-..; Z-D-35E-.., Z-D-55E-..
The used active Harmonic Filter is recognizable from the type designation (see rating plate).
These operating instructions apply only to a specific product and under no circumstances to the
complete system.
The instructions contain information for your guidance. No guarantee is provided with regard to the
accuracy of any information and no legal claims may be derived. Reproduction of this information, or
extracts thereof, is allowed only with written approval.

1.4 Terms and definitions


Filter module
For „Filter module Z-D-15/35/55E-..“ the term „Filter module“ or active harmonic filter will be used.
Drive controller
For the non-linear loads which are used together with the power feedback unit in the following the term
„Controller“ is used
Drive system
For a drive system with harmonic filter, power feedback units, controller and other components of the
drive system in the following the term „Drive system“ is used.

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 4/44


Operating Instructions Z-D-15/35/55E-.. General
__________________________________________________________
1.5 Intended use
Active harmonic filter are used for reduction of harmonics from for example 6-puls rectifier, frequency
converter or uninterruptible power sources (UPS). Filter are used with further equipment and are
implemented within an electrical system. Active harmonic filter are intended to be installed in an
electrical panel or similar electrical room. Active harmonic filter are not household appliances and may
be considered for commercial use only. Any other use in not allowed.
The manufacturer shall not be liable for any damage resulting from improper use. The user bears the
sole risk.

The intended use also includes:


• Compliance with technical data, application and performance limits according to the data sheet,
order confirmation and other specifications
• Compliance with the prescribed intervals for all inspection work
• Persons performing work completely reading and understanding this documentation and
especially the safety instructions chapter

1.6 Improper use


Any use that is not described in the intended use is improper and therefore impermissible.
The following foreseeable types of misuse are also improper:
• Unauthorized changes to the active harmonic filter
• Operating error
• Improper work on and with the harmonic filter
• Reversing the current direction of the current transformers
Use:
- as a safety component or for performance of safety
related functions as defined in EN ISO 13849- 1
- as an independent household appliance
- in low voltage systems with special fire risks in compliance with IEC 60364-4-42
- in explosive atmosphere
- proximity to flammable substances or objects
- in open operating rooms
Operation:
- use outside the operating data approved in the data sheet, the order confirmation and in
other provided specifications
- in a way that personal injury or material damage may occur in the event of malfunction or
failure
- with a load that leads to higher power consumption and current values than specified on the
rating plate
- with vibrations

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 5/44


Operating Instructions Z-D-15/35/55E-.. Safety precautions
__________________________________________________________
2 Safety precautions
2.1 What this chapter contains
Please read this manual carefully and follow all safety precautions before moving, installing, operating
and servicing the active harmonic filter, if ignored, physical injury or death may occur, or damage may
occur to the devices.
If any physical injury, death, or damage to the devices occurs for ignoring to the safety precautions in
the manual, our company will not be responsible for any damages and we are not legally bound in any
manner.

2.2 Safety definitions and warning symbols


All Safety definitions have a uniform layout:
- The pictogram shows the kind of danger
- The signal word characterizes the severeness of danger
- The note describes the danger and suggest how to avoid the danger.

Signal Word
Note

Used Pictogram Instruction


Warning of Imminent danger by Danger! Warns of an immediate imminent
personal electricity danger. In case of disrespect, death or
severe injury may happen.
injury
Warning of an Warning Warns of a possible, very dangerous
imminent danger situation.
In case of disrespect, death or severe
injury may happen.

Dangerous Caution! Warns of a possible, dangerous


situation situation.
In case of disrespect, minor injury may
happen.

Warning of hot Warning! Warns of touching of a hot surface.


surface In case of disrespect, burnings may
happen

Warning of Harmful Stop! Warns of possible property damage. In


property situation case of disrespect, the system and it’s
STOP
damages environment may be damaged

Usefull Information Note! Marks a general, useful hint. If it is


information and observed, usage of the system will be
and hints for easier
using

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 6/44


Operating Instructions Z-D-15/35/55E-.. Safety precautions
__________________________________________________________

Safety and application notes for drive systems


(following Low Voltage Directive 2006/95/EG)

1. General 4. Erection
During operation, filter modules may have, according to their type The modules must be erected and cooled according to the
of protection, live, bare, in some cases also movable or rotating regulations of the corresponding documentation. The filter
parts as well as hot surfaces. Non –authorized removal of modules must be protected from inappropriate loads.
required cover, inappropriate use, incorrect installation or Particularly during transport and handling, components must
operation, creates the risk of severe injury to persons or damage not be bent and / or isolating distances must not be changed.
to material assets. Touching of electronic components and contacts must be
avoided. Filter modules contain electro-statically sensitive
Further information can be obtained from the documentation. All
components which can easily be damaged by inappropriate
operations concerning transport, installation and commissioning
handling. Electrical components must not be damaged or
as well as maintenance must be carried out by qualified, skilled
destroyed mechanically (health risk are possible!).
personnel (IEC 364 and CENELEC HD 384 or DIN VDE 0100
and IEC-Report 664 or DIN VDE 0110 and national regulations
for the preventions of accidents must be observed). According to 5. Electrical Connection
this basic safety information qualified skilled personnel are When working on live filter modules, the valid national regulations
persons who are familiar with the erection, assembly, for the prevention of accidents (e.g. VBG 4) must be observed.
commissioning and operation of the product and who have the Before any installation or connection works, the plant has to be
qualifications necessary for their occupation. switched off and to be secured properly.
The electrical installation must be carried out according to the
2. Application as directed
Filter modules are components which are designed for appropriate regulations (e.g. cable cross-sections, fuses, PE-
installation in electrical systems or machinery. connection). More detailed information is included in the
documentation. When using the filter module with controllers
When installing in machines, commissioning of the filter module without safe separation from the supply line (to VDE 0100) all
(i.e. the starting of operation as directed) is prohibited until it is control wiring has to be include in further protective measures
proven, that the machine corresponds to the regulations of the (e.g. double insulated or shielded, grounded and insulated) .
EC Directive (2006/42/EG) (Machinery Directive); EN 60204 Notes concerning the installation in compliance with EMC – such
must be observed. Commissioning (i.e. starting operation as as screening, grounding, arrangement of filters and laying of
directed) is only allowed when there is compliance with the EMC- cables – are included in the chapter installation of this
Directive (2004/108/EG). documentation. These notes must be also observed in all cases
The filter modules meet the requirements of the Low-Voltage for filter modules with the CE-mark. The compliance with the
Directive (2006/95/EEC). The harmonized standards of the prEN required limit values demanded by the EMC legislation is the
50178/DIN VDE 0160 series together with EN 60439-1/DIN VDE responsibility of the manufacturer of the system or machine.
0660 part 500 and EN 60146/DIN VDE 0558 are applicable for
the power feedback unit. The technical data and information on 6. Operation
Systems where filter modules are installed, if applicable, have
the connection conditions must be obtained from the nameplate
to be equipped with additional monitoring and protective
and the documentation and must be observed in all cases.
devices according to the valid safety regulations e.g. law on
3. Transport, storage technical tools, regulations for the prevention of accidents, etc..
Notes on transport, storage and appropriate handling must be After disconnecting the filter module the supply voltage, live
observed. At non-observance any warranty expires. The filter parts of the filter module and power connections must not be
module unit has to be protected from inadmissible stress. The touched immediately, because of possibly charged capacitors.
transport is only valid in original packaging and in the thereon For this, observe the corresponding labels on the drive
by pictograms marked transport position. In particular during controllers.
transport and handling no components are allowed to be bent
and / or isolating distances may not be altered. The modules During operation, all covers and doors must be closed
are equipped with electrostatic sensitive devices, which may 7. Maintenance and service
be damaged by improper handling. Therefore, it has to be The manufacturer’s documentation must be observed.
avoided to get in contact with electronic components. If
The product-specific safety and application
electronic components are damaged mechanically the module
must not be put into operation, as it cannot be ensured, that all
notes in these Operating Instructions must
relevant standards. also be observed!!
This safety information must be kept!

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 7/44


Operating Instructions Z-D-15/35/55E-.. Safety precautions
__________________________________________________________
2.3 General safety information
• These safety regulations are not entitled to completeness. In case of questions please contact
our technicians.
• When commissioning the filter module is compliant with the state of the art. The filter module
generally allows safe operation.
• The statements of this manual describe the attributes of the products without guaranteeing
them.
• The filter module unit may expose persons, the power feedback units itself and other material
to danger, if
- non-qualified personal works at and with the filter module
- the filter module is used in opposite to its purpose.
• Filter modules have to be projected in a way, that they fulfil their function and don’t expose
persons to danger, if they are mounted correctly and are used in accordance with their purpose.
This applies also for the interplay with the whole plant.
• The units, operational data and circuit details described in this manual have to be understood
analogously and have to be checked for transferability to each application.
• Use the drive system only in flawless condition.
• Modifications of the filter modules without consultation of a ZIEHL-ABEGG-technician are not
allowed generally .
• The warranty given by us expires, if the unit is modified or (even partially) dismantled or if it is
used in contradiction to our instructions.
• The constructor of the plant, who has to know the technical guidelines, bears the responsibility
for the correct selection and arrangement of the electrical components.
• Putting into operation of the power feedback unit is only admissible at VDE-conform nets of
electrical power supply. Non observance may damage the device!
• In accordance with the corresponding standards and guidelines the operation on even for a
short time over-compensated networks (cos1) respectively on un-choked compensation-units
is not admissible. If this is done nevertheless, overvoltage will occur (caused by oscillating
currents), which may damage all connected components, especially electronic units like
controllers and filter modules.

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 8/44


Operating Instructions Z-D-15/35/55E-.. Safety precautions
__________________________________________________________

Stop!
STOP
Undisturbed and safe operation of the filter module is possible only if the hints of this instruction are
observed.

If they are not observed, in some cases malfunctions and damages may occur:

- Observe specified mains voltage.


- Power and control cables must be installed with distance (> 15cm)
- Use screened / twisted control wires. Connect screen to PE at both ends!
- Ensure good grounding of drive, motor and filter module. Connect the screen of power cables
to ground extensive at both ends.(remove lacquer)!
- Observe star layout for grounding of cabinets and systems (AVOID ground loops!)
- The filter module is designed for fixed mounting and electrical connection.
The ground wire must have a minimum cross section of 2,5mm² (depending of filter module
size).

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 9/44


Operating Instructions Z-D-15/35/55E-.. Safety precautions
__________________________________________________________
2.4 Safety responsible persons
Operator
- The operator is any natural or legal person who is using the system or let someone use the
system.
- The operator and / or the safety responsible person must take care for:
- all relevant rules , guidelines and laws must be observed
- only qualified personnel will work with and on the system
- the manual will be available for the personnel during working at the system.
- unqualified personnel will be forbidden to work on the system.

Qualified personal
Stop!
STOP Qualified technical personnel are persons, who - have appropriate training, knowledge and experience
- are informed about relevant specifications, standards and accident prevention regulations
- are trained in the installation and operation of relevant systems
- are able to recognize and avoid possible dangers
(Definition for qualified personnel in accordance to IEC 364)

2.5 Specification of wires and cables


The used wires and cables must comply the relevant standards at place of installation and operation.
Rules regarding minimum PE crass section must be observed in any case!

2.6 Rest danger


Danger!
After switching off the mains supply all terminals may stay life for up to ten minutes!

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 10/44


Operating Instructions Z-D-15/35/55E-.. Fast start
__________________________________________________________
3 Fast start
3.1 What this chapter contains
This chapter describes the basic guidelines for installation and commissioning of the active harmonic
filter, which should be observed for fast and easy usage.

3.2 First check when unpacking


Please check the goods during and immediately after receipt on the following characteristics:
Please check the packaging for intactness and dryness. If this is not the case, immediately
1
get in contact with the sender.
Please check if the type-code on the packaging matches the ordered product. If this is not the
2
case, immediately get in contact with the sender.
Please check for any kind of moisture inside the packaging and for any kind of damages at
3
the product. If this is not the case, immediately get in contact with the sender.
Please check if the type code on the packaging matches the data on the rating plate. If this
4
is not the case, immediately get in contact with the sender.
Please check if the packaging contains all accessories including manual. If this is not the
5
case, immediately get in contact with the sender.

3.3 Suitability for the application


Please check if all current transformers and the the adjusted parameters asre suitable for the
application before you start up the active harmonic filter for the first time.

3.4 Environment conditions


Please check and consider the following environment conditions before starting the installation:
Check for the ambient temperature to be below 40 °C. If it is higher, consider derating of
3%/K. This would mean that a Z-D-55E-.. with rated current 55 A at 45 °C must be loaded
1
with not more than 46,75 A. Operation above 50 °C is not acceptable.

Check for the ambient temperature to be above -10 °C. If it is lower, a heater must be
installed.
2
Hint: Ambient temperature means the temperature inside the cabinet with the Z-D-15/35/55E-
...
Check for the installation height to be below 1000m above sea level. If it is higher, consider
3. derating of 1%/100m. This would mean that a Z-D-35E-..with rated current 35 A at 2000mC
must be loaded with not more than 31,5 A. Operation above 4000 m is not acceptable.
Check for ambient moisture to be below 90%. If the moisture is higher, measures for
4 reduction of moisture must be taken.

Check for no direct sunlight exposition of the Z-D-15/35/55E-.. and for no dust impact. If that
5 could happen, countermeasures must be taken.

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 11/44


Operating Instructions Z-D-15/35/55E-.. Fast start
__________________________________________________________
3.5 Check of the installation
Perform this check AFTER installation but BEFORE first powering up:
Check the correct mounting and wiring of the current transformer (CT). The wired used must
1 comply with the requirements of components (CT, Z-D-15/35/55E-..) and of place of installation.

Check that power and controls wires are installed separately and that EMC guidelines are
3.
observed.
Check the grounding of the system and components for compliance with guidelines and
4
requirements of the drives.
Check if the clearance between the components comply with the requirements of these
5
instructions.
Check if the installation meets the requirements of these instructions. The active harmonic filter
6
must be mounted in an upright position.

3.6 Simplified commissioning


The active harmonic filter Z-D-15/35/55E-.. is a largely automated product for reduction of harmonics.
Complete the simplified commissioning as described below BEFORE first usage:

1 Check all parameters of the monitoring system on your computer

2 Check the correct wiring of the current transformers


3 If several products are used in parallel, check for compliant adjustment of the parameters.

Hint: If the result of harmonic compensation is not satisfying, please check the parameters once again
first, wiring (especially polarity) of the current transformers second. If everything is o.k., modify the phase
angel of the system to achieve even better results.

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 12/44


Operating Instructions Z-D-15/35/55E-.. Product-Overview
__________________________________________________________
4 Product-Overview
4.1 What this chapter contains
This chapter describes the function principle, the characteristics of the product and dimensions.

4.2 Area of application / Notes on use:


The active harmonic filter is intended to reduce harmonics of certain B6 rectifiers or frequency converters
in electrical power supply networks. Its intended to be used for installation in a machine or for assembly
with other components to build a machine. Active harmonic filters are electrical equipment for installation
in control cabinets or similar closed operating rooms. Active harmonic filters are not household
appliances, but are designed as components exclusively for commercial use.
Possible application examples:
- Reduction of harmonics in public and non-public networks
- Reduction of harmonics in industry and business networks

4.3 Function principle:


The following drawings show the principle, simplified setup for active harmonic filters.

Topology of Z-D-15/35/55E-..

4.4 Label code


The type code is part of the rating plate and contains important information about the active harmonic
filter.
Examples for a type code designation with explanation

Z - D - 15 E - 060
① ② ③ ④ ⑤
Nr. Detaillierte Bezeichnung
① Designation for product category accessoriesr
② Designation for 3 phase alternate current
③ Rated current of active harmonic filter = 15 A
④ Designation for assembly device (Protection rating IP20)

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 13/44


Operating Instructions Z-D-15/35/55E-.. Product-Overview
__________________________________________________________
⑤ Rated current of current transformer = 60 A

4.5 Rating plate


The rating plate carries the technical data valid for the delivered product.
Example for rating plate active harmonic filter

6 7 8 9

3 11

4
12

13
5

10

Nr. Designation Nr. Designation


ZIEHL-ABEGG related data UL related data
1 Part number ZIEHL-ABEGG SE 11 Motor identification UL
2 Series number 12 Rated voltage,
Rated frequency,
Rated current,
3 Rated voltage, 13 Max. ambient temperature authorisation
Rated frequency, at rated power
Rated current,
4 Max. ambient temperature at rated current
Protection rating
5 Components of part number
Type of active filter
Rated currrent of CT
Series number of coresponding CT
6 Date of manufacture
7 Type designation of active harmonic filter
including the coresponding CT
8 Weight
9 Barcode part number
10 European mark of conformity

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 14/44


Operating Instructions Z-D-15/35/55E-.. Product-Overview
__________________________________________________________
4.6 Storage
Store correctly:
• Store the product in the original packaging in a dry and weatherproof location and protect it from
dirt and weather until final installation.
• Make sure the environment is dry, vibration-free and condensation-free. Prevent formation of
condensation inside the product and packaging.
• Avoid extreme stresses due to heat, cold or moisture (see technical data for the temperature
range for storage and transport). Recommended values: Temperature 0 °C to 40 °C, max.
relative humidity 60 %.

4.7 Transport and handling


Improper transport can cause damage to the product and its accessories, which shortens the product
service life and/or impair its function.
Transport correctly:
• Transport active harmonic filter in the original packaging.
• Only transport if protected against weather; unprotected transport is not allowed. Moisture
penetration into the packaging is not allowed.
• Avoid impacts and bumps during transport and observe the limit values from ISTA 3E and ISTA
3B.
• When transporting a device with an installed active harmonic filter, do not exceed the limit values
stipulated in EN 60721-3-2, Category 2M1 for vibrations and impacts.

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 15/44


Operating Instructions Z-D-15/35/55E-.. Installation instructions
__________________________________________________________
5 Installation instructions
5.1 What this chapter contains
This chapter describes mechanical and electrical installation.

5.2 Mechanical drawings

5.2.1 Active harmonic filter Z-D-15E-..

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 16/44


Operating Instructions Z-D-15/35/55E-.. Installation instructions
__________________________________________________________
5.2.2 Active harmonic filter Z-D-35E-.. and Z-D-55E-..

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 17/44


Operating Instructions Z-D-15/35/55E-.. Installation instructions
__________________________________________________________
5.2.3 Mechanical installation
For safe and undisturbed operation, it is mandatory to follow those instructions for mechanical
installation:
1. Clearance between active harmonic filter and other components like chokes, cabinet walls,
drives:
- ≥100 mm in horizontal direction (left/right) and
- ≥100 mm in vertical direction (bottom)
2. Clearance between several active harmonic filter:
- ≥100 mm in horizontaldirection (left/right)
- ≥100 mm in vertical direction (bottom)
3. Min. clearance in vertical direction (top):
- Z-D-15E-..: 130 mm
- Z-D-35E-..: 180 mm
- Z-D-55E-..: 180 mm
4. Use screws with min. diameters
- Z-D-15E-..: 6 mm
- Z-D-35E-..: 6 mm
- Z-D-55E-..: 6 mm

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 18/44


Operating Instructions Z-D-15/35/55E-.. Installation instructions
__________________________________________________________
5.3 Electrical wiring
Active harmonic filters may only be installed, commissioned and serviced by certified electrician.
Connect the active harmonic filter according to the attached connection diagram. The labeling
is in the immediate vicinity of the connection terminals.

3 Wire 3 Phase

Note: For part numbers 349110, 349111, 349112, the conductor of the load current must be passed
through the converter two times (loop once) to achieve the correct current transformer rating. It is
essential (as with simple implementation) that the direction of energy flow in the conductor and the
direction of the arrow on the converter match.
Exemplary illustration:
One times passage of the conductor Two times passage of the conductor
Part number: 349114, 349115, 349116,
Part number: 349110, 349111, 349112
349117, 349118, 349119, 349120, 349121

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 19/44


Operating Instructions Z-D-15/35/55E-.. Installation instructions
__________________________________________________________
5.3.1 EMC directive
Compliance with the EMC directive is only given if the active harmonic filter is connected directly to the
main power supply.
If the active harmonic filter is built into a system or combined with other products, the manufacturer of
the system / operator of the device is responsible for compliance with the EMC directive according to
the locally applicable standards.

5.3.2 Voltage supply


The voltage supply must match the information on the rating plate (see technical data).
The voltage supply must comply with the EN 50160 quality characteristics and the defined standard
voltages of IEC 60038!

Remarks for connection of CT (current transformer):


Routing of wires: The wires between the active harmonic filter and current transformers must be
twisted pair cables. A correct function is only possible if the wiring matches exact the diagram below. If
wires are interchanged, the harmonics will not be reduced but amplified. To avoid interchanging of wires
it is strongly recommended not to use any wire colour twice.
Wire cross section: The cross section of the wires has a significant influence on the quality of the
control. Is the cross section to small in relation to the length of the wire, the resulting measurement
within the active harmonic filter will be too small to achieve a good control quality and good reduction of
harmonics.
2×𝑑×𝑣×𝐼²×𝜌
𝐴=
𝑆

The following values needed to be known:


- S = Power of the current transformer (30 A - 80 A typical 1.5 VA, ≥ 100 A typical 2.5 VA )
- d = Distance (length of cableway) between active harmonic filter and current transformer
- v = Twisting factor (typical 1,5)
- I = secondary current of the current transformer ( typical 5 A)
𝑂ℎ𝑚∗𝑚𝑚²
- ρ = Rho = specific resistance of copper ( 0,01786 )
𝑚
2×2 𝑚×1,5×52 ×0,01786 𝑂ℎ𝑚×𝑚
- Example: 𝐴 = = 1,07 𝑚𝑚²
2,5 𝑉𝐴 ×𝑚𝑚²

Wiring type: At 3W3P (installation of two current transformers) the neutral must not be connected to
the active harmonic filter. It is mandatory that the physical installation must match the adjusted method
in the software of the active harmonic filter. If this is not observed, the reduction of harmonics is not
optimal.

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 20/44


Operating Instructions Z-D-15/35/55E-.. Installation instructions
__________________________________________________________
5.3.3 LED status display

LED
Green: Operation
Red: Error
Flashing: Standby

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 21/44


Operating Instructions Z-D-15/35/55E-.. Installation instructions
__________________________________________________________
5.3.4 Current transformer wiring

PE GND CT_C GND CT_B GND CT_A

Terminal label Function / Terminal


CT_A CT S1 in Phase A(L1)
GND CT S2 in Phase A (L1.1)
CT_C CT S1 in Phase C(L3)
GND CT S2 in Phase C (L3.1)
PE Protective wire / screening
Remark: To achieve best performance of Z-D-15/35/55E-.. the pairs CT_A+GND and CT_C+GND
should be twisted.
Exemplary illustraiton of current transformer: Connection of S1 and S2:
One times passage:

Two times passage

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 22/44


Operating Instructions Z-D-15/35/55E-.. Installation instructions
__________________________________________________________
5.3.5 Active harmonic filter in parallel wiring
Z-D-15/35/55E-.. may be connected in parallel without limitation to achieve higher power ratings. It is
necessary to adjust the related parameters in the software and do adopt the wiring of the current
transformers.
Phase A (L1) is used for reference for the other phases.
Example Case 1:
Parallel wiring of two Z-D-15/35/55E-..:

Hint: Like the polarity of S1 and S2, the polarity of P1 and P2 is very important for the correct function.
P1 must face to mains supply and P2 (on opposite side of current transformer) must face to the load.

Example Case 2:
Parallel wiring of more than two Z-D-15/35/55E-..:

Hint: Like the polarity of S1 and S2, the polarity of P1 and P2 is very important for the correct function.
P1 must face to mains supply and P2 (on opposite side of current transformer) must face to the load.

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 23/44


Operating Instructions Z-D-15/35/55E-.. Installation instructions
__________________________________________________________
5.3.6 Selection of CT (current transformers)
Selection of current transformers depends on the load current of the application. Applicable are current
transformers in the range of 30:5 to 250:5. The transfer ratio must be adjusted in the correlated
parameter of the software. For optimal performance, the nominal current of the current transformer must
not be much higher than the load current of the application (e.g. load current 95A => current transformer
100A)
Following CT´s are provided for corresponding nominal current

Nominal current of CT (current


Nominal current of filter2 Order code3
transformer)1 Filter
in A Filter + CT
in A

30 Z-D-15E-030 15 349110
40 Z-D-15E-040 15 349111
50 Z-D-15E-050 15 349112
60 Z-D-15E-060 15 349114
60 Z-D-35E-060 35 349115
80 Z-D-35E-080 35 349116
100 Z-D-35E-100 35 349117
150 Z-D-35E-150 35 349118
150 Z-D-55E-150 55 349119
200 Z-D-55E-200 55 349120
250 Z-D-55E-250 55 349121
1Current transformers should be selected based on the maximum load current to be filtered and the
THDi target to be achieved
2Relates to the maximum possible compensation current

3Each part number consists of a filter and 2 current transformers

5.3.7 Wiring when using current transformers with high ratio


For part numbers 349110, 349111 and 349112 the conductor of the load current must be passed through
the converter two times (loop once) to achieve the correct current transformer rating. It is essential (as
with simple implementation) that the direction of energy flow in the conductor and the direction of the
arrow on the converter match. A 100A bushing current transformer is used as an example for part
number 349112, here the conductor must be passed through twice instead of once. See capture 5.3.
Such an adaptation is not possible with converters without a feed through.
If you have any questions, please contact our technical support for control systems - ventilation
technology.

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 24/44


Operating Instructions Z-D-15/35/55E-.. Installation instructions
__________________________________________________________
5.3.8 EPO and Z-D-15/35/55E-.. ID

EPO GND ID_DS

Terminal label Function


EPO EPO connection for usage as part of EMERGENCY OFF line. If the
contact to be wired here is closed, the EMERGENCY OFF function
GND is active.
Adjustment of the ID of the active harmonic filter. This is required for
ID_DS correct software function if several modules are connected to the
same interface of one computer

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 25/44


Operating Instructions Z-D-15/35/55E-.. Installation instructions
__________________________________________________________
5.3.9 Input and output interface

Terminal label Function


IN1+ for DC +,
1N1
recommended input voltage range: 10 ~ 24V DC
1N2 IN2+ for DC +,
recommended input voltage range: 10 ~ 24V DC
GND_O Common ground for DC input
NO1 Relay 1, Normal Open, DC, capacity: 8A/250VAC
COM Common ground for relay output
NO2 Relay 2, Normal Open, DC, capacity: 8A/250VAC
485+ 485 Interface for remote control by a computer. A standard-485-
485- communikation interface requires screened or twisted wires. If the
wire length exceeds 1m, GND must be connected.
+7,5V -
GND_O Common ground for communication 485 and CAN
CANH
CAN communication
CANL

Wiring example RS 485:

Z-D-15/35/55E-
..
USB=>RS485

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 26/44


Operating Instructions Z-D-15/35/55E-.. Supervision- and control software
__________________________________________________________
6 Supervision- and control software
6.1 What this chapter contains
This chapter contains guidelines for using the supervision and control software. There are hints how to
check the parameters before commissioning and how to optimize them during operation.

6.2 Introduction in the system


Naming of the software:
Software-Version Suitable for
High frequency RHF-Active SiC V3.2.3 RHF-Active 15, 35,55 A

6.2.1 Log In
After start, the following dialog screen is shown:

To log in use following data:


ID: 001
Password: 010101

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 27/44


Operating Instructions Z-D-15/35/55E-.. Supervision- and control software
__________________________________________________________
6.2.2 Home
The home screen will be shown:

Home: Information concerning grid and load are shown. The three buttons at the bottom are used to
start, stop and reset the active harmonic filter.
User Set: All parameters can be read and modified.
DATA: Displays grid voltage and current (each RMS, frequency and THD of all active wires), load
current (each RMS, frequency and THD of all active wires), power (each apparent, active, reactive and
power factor), load current of the inverter (RMS, load rate, choke current) and the temperatures of the
transistors
Record: Historical values of recorded data and warnings

Help: Shows easy hints.

Note!
The colour of the line beside the blue ribbon at the left shows connect status between PC and active
harmonic filter:
Red => no connect
Green => connect,

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 28/44


Operating Instructions Z-D-15/35/55E-.. Supervision- and control software
__________________________________________________________
6.2.3 Initialize communication
When computer and Z-D-15/35/55E-.. are connected the first time, it is necessary to set the
communication parameters. Thereto click on „User Set“, then „Comm“ and start „PortCheck“:

The drop down list offers the available ports. Choose one of them.
Adjust the transmission speed in accordance to the list below:
Software-Version Suitable for Baud Rate
SiCAHF-3.2.1 Z-D-15/35/55E-.. 19200

Initialize the connection by clicking on „Connect“. If succesful, the software will show this:

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 29/44


Operating Instructions Z-D-15/35/55E-.. Supervision- and control software
__________________________________________________________
6.2.4 System configuration
Overall there are seven pages for adjustment of parameters.
Page Content (Adjustment of…)
1 Module
2 Phase angle
3 Odd harmonics
4 Even harmonics
5 Sensor-calibration
6 Trouble shooting
7 communication

The description of page 7 „Communication“ is part of in chapter 6.2.3. All others can be found in the
following:

6.2.4.1 Device

This page shows the following adjustments:


Nr. Name Description
1 Compensate Mode of compensation:
priority H: only Harmonic compensation
HR: compensation of harmonics and reactive power, whereas harmonic
compensation has priority.
HRU: compensation of harmonics, reactive power and phase unbalance,
whereas harmonic compensation has priority.
2 Grid Adjustment to grid frequency: 50hz or 60hz
Frequency
3 CT Location Placing of current transformers. Load side (preferred) or grid side.

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 30/44


Operating Instructions Z-D-15/35/55E-.. Supervision- and control software
__________________________________________________________
4 CT Variable Ratio of current transformers, (typical XX: 5). XX must be written in here.
Ratio
5 Power Factor Set value for power factor if HR or HRU have been selected
6 Harmonic Harmonic compensation algorithm:
Detect Mode 1. Manual: The compensation rate must be adjusted manually.
2. Auto: The compensation rate is adjusted automatically.
3. Completely: the compensation rate is set to 1. Compensation includes
reactive power.
The default setting is „Manual
7 Compensate Compensation rate: It is possible to adjust between 0.1-1.0 to reduce the
Ratio compensation current. 1.0 means full compensation current
8 Parallel If several active harmonic filter operate in parallel (at one set of current
current transformers), this cell expects the total current of all active harmonic filter
9 Topology If three phases and three wires (L1, L2, L3) with two current transformers are
used, select 3P3W
If three phases and four wires (L1, L2, L3;N) with three current transformers are
used, select 3P4W.
10 Power On Power on status at voltage recovery.
mode Auto: At voltage recovery module will start automatically
Manuel: At voltage recovery the start of the module must be initiated manually
The default setting is „Manual
11 Grid Voltage Grid voltage. The default setting is 380 V (fits also for 400 V). Alternatively 480
V can be chosen.
12 CT Line Mode Connection type of current transformers. Possible are series and parallel
connection
13 Damp Damping of the control. Admissible values are between 10 and 30. At
symmetrical three phase load (3W3P) : 30. At single phase or unsymmetrical
load (4W3P) : 10.

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 31/44


Operating Instructions Z-D-15/35/55E-.. Supervision- and control software
__________________________________________________________
6.2.4.2 Angle_Coeff

The angle coefficient of can compensate deviation of current transformers.


No. Name Description
1 Fundamental Angle Set value range -99.99 to 99.99
2 Phase A Angle Set value range -99.99 to 99.99
3 Phase B Angle Set value range -99.99 to 99.99
4 Phase C Angle Set value range -99.99 to 99.99
5 3rd Angle Set value range -99.99 to 99.99
6 5th Angle Set value range -99.99 to 99.99
7 7th Angle Set value range -99.99 to 99.99
8 9th Angle Set value range -99.99 to 99.99
9 11th Angle Set value range -99.99 to 99.99
10 13rd Angle Set value range -99.99 to 99.99
11 15th Angle Set value range -99.99 to 99.99
12 17th Angle Set value range -99.99 to 99.99
13 19th Angle Set value range -99.99 to 99.99
14 21th Angle Set value range -99.99 to 99.99
15 23th Angle Set value range -99.99 to 99.99
16 25th Angle Set value range -99.99 to 99.99

Optimized parameters for ECblue are already stored at the factory. Normally, the best possible results
are achieved with these.

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 32/44


Operating Instructions Z-D-15/35/55E-.. Supervision- and control software
__________________________________________________________
6.2.4.3 Odd_Coeff

The odd coefficient can compensate characteristics of the grid on site:


No. Name Description
1-31 Compensation rate1st – 59th Set value range 0.01 to 1.0
Optimized parameters for ECblue are already stored at the factory. Normally, the best possible results
are achieved with these.

6.2.4.4 Even_Coeff

The even coefficient can compensate characteristics of the grid on site::


No. Name Description
1-30 Compensation rate 2nd – 60th Set value range 0.01 to 1.0
Optimized parameters for ECblue are already stored at the factory. Normally, the best possible results
are achieved with these.
_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 33/44


Operating Instructions Z-D-15/35/55E-.. Supervision- and control software
__________________________________________________________
6.2.4.5 Calibration

This page defines the calibration of external and internal sensors (current and voltage transformers).
This adjustment is done in factory and must not be changed without manufacturer’s acknowledgment.

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 34/44


Operating Instructions Z-D-15/35/55E-.. Supervision- and control software
__________________________________________________________
6.2.4.6 Debug

This page defines the internal variables of the active harmonic filter (among other purposes for trouble
shooting). This adjustment is done in factory and must not be changed without manufacturer’s
acknowledgment.

Refer to chapter 6.2.3.

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 35/44


Operating Instructions Z-D-15/35/55E-.. Supervision- and control software
__________________________________________________________
6.2.5 Data
The “Data” pages show electrical values of the system. Based on the data from the “Home” page, also
Voltage vs time and current vs. time are displayed.

6.2.6 Procedure to power on


1. Connect the Z-D-15/35/55E-.. with the PC
2. Adjust current transformer ratio, compensation rate, grid voltage, grid frequency etc. on pages „User
Set”
3. Check that on page „Record” no errors or alarms are displayed. If there are, first clear the messages
on page „Home“ by using „Clear Fault“ button.
4. Click at „Power on” on page „Home“.

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 36/44


Operating Instructions Z-D-15/35/55E-.. Maintenance and check of hardware
__________________________________________________________
7 Maintenance and check of hardware
7.1 What this chapter contains
This chapter contains instructions for predictive maintenance of the active harmonic filter.

7.2 Periodicity of maintenance


When installed in an appropriate environment the active harmonic filter from ZIEHL-ABEGG
required minimal maintenance. The recommended maintenance is listed below.

Check Task Method

Check of ambient temperature, humidity,


Optical check and measurment
vibrations and for absence of dust, gas, oil
of the parameters
Environment

mist and water drops


conditions

Ensure that no tools or other potentially


dangerous components have been placed Optical check
nearby
Voltage

Measurement with multimeter


Measure voltage in power and control circuits

Check for loosen screws


Supply lines

Check of system and cabinet Check of absence of sparks,


damages, dark colour due to
overheating or aging of
isolation
Ensure that no dust or dirt is
present

Optical check or estimation of


Check for abnormal sound emission or
operation time based on
vibrations
maintenance files
Fan
Cooling system

Check for loosen screws Fix screws


Optical check or estimation of
Check of absence of dark colour due to
operation time based on
overheating or aging
maintenance files
Air duct

Check for debris in the cooling system Optical check

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 37/44


Operating Instructions Z-D-15/35/55E-.. Maintenance and check of hardware
__________________________________________________________
7.3 Disposal/Recycling
Disposal must be carried out professionally and in an environmentally friendly way in accordance with
the respective national legal stipulations.
- Demountontaminate the product before starting work if it was previously used in a
contaminated environment.
- Separate the materials by type and in an environmentally friendly way.
- If necessary,commission a specialist company with the waste disposal.

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 38/44


Operating Instructions Z-D-15/35/55E-.. Error description and repair
__________________________________________________________
8 Error description and repair
8.1 What this chapter contains
This chapter describes known issues and their solving.

8.2 Typical errors and repairs


Error cause repair
Z-D-15/35/55E-.. Current transformer Check wiring and polarity
wrong compensation
(THDi rises) System settings Check transformer ratio
Setting the phase angle compensation
Phase angle with patience and carefully step by
step, Trial and error iteration
Z-D-15/35/55E-..
insufficient Low impedance of the connection
compensation (THDI result in very harmonic levels before
decreases but is compensation. It is highly
higher than expected) Low impedance recommended to install impedance as
first counter measurement against
harmonics (for Drives basically DC or
AC chokes).
Error signal
System settings Check for first error than for second
(red LED)
No communication Software settings Improve baud rate and/or interface
selection

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 39/44


Operating Instructions Z-D-15/35/55E-.. Enclosure
__________________________________________________________
9 Enclosure
9.1 Technical Data

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 40/44


Operating Instructions Z-D-15/35/55E-.. Enclosure
__________________________________________________________

9.1.1 Technical Data Active harmonic filter Z-D-15E-..


Electrical data
Network type 3 phase with/ without neutral 3P4W/3P3W
Rated voltage 380-480 V (+10 % / -15 %)
Rated current 15 A
Mains frequency 50 Hz / 60 Hz (5 Hz)
Harmonic compensation 1.-60. Harmonic
Response time 20 µs
Full response time 5 ms
Filter performance >96 %
Switching frequency 40 kHz-60 kHz, typical 50 kHz
Technology Advanced SIC
System topology Two Level Topology
Harmonic compensation, power factor correction, three phase
Function
balancing
Efficiency η >99,4% at nominal load
Power losses 207 W at 30 kW nominal power
User-Interface & Remote monitoring
HMI Not present / extern
Communication protocol RS485
PC-Software V3.2.3
Installation / Configuration
Noise <60db
Current transformer ratio 30/5~60/5
Cooling Forced air cooling
Air flow requirement >105m³/h
Mounting Wall mount
Parallel configuration Unlimited
Extensions Modules in parallel
Protection level IP20
Cable entering bottom
EMC regarding IEC60038 class A (EN61000-6-4*, EN 61000-6-1)
Environmental
Ambient temperature -10℃~40℃
Temperature-Derating Derating above 40℃ (3%/K)
Maximum temperature 50℃
Permissible temperature range for transport -25 °C~+70 °C (regarding EN 50178)
Permissible temperature range for storage -25 °C~+55 °C (regarding EN 50178)
Relative Humidity 5%~95% Class F without condensation
Altitude below 1000m
Altitude Derating above 1000m (5%/1000m to 4000m)
Weight, Dimensions, Certifications
Weight 10 kg
Dimensions W*D*H[mm] 89*417*260
Certifications CE
*Warning note: This device is not intended to be used in residential areas and cannot ensure adequate
protection of radio reception in such environments.
_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 41/44


Operating Instructions Z-D-15/35/55E-.. Enclosure
__________________________________________________________
9.1.2 Technical Data Active harmonic filter Z-D-35E-..
Electrical data
Network type 3 phase with/ without neutral 3P4W/3P3W
Rated voltage 380-480 V (+10 % / -15 %)
Rated current 35 A
Mains frequency 50 Hz / 60 Hz (5 Hz)
Harmonic compensation 1.-60. Harmonic
Response time 20 µs
Full response time 5 ms
Filter performance >96 %
Switching frequency 40 kHz-60 kHz, typical 50 kHz
Technology Advanced SIC
System topology Two Level Topology
Harmonic compensation, power factor correction, three phase
Function
balancing
Efficiency η >99,3% at nominal load
Power losses 415 W at 55 kW nominal power
User-Interface & Remote monitoring
HMI Not present / extern
Communication protocol RS485
PC-Software V3.2.3
Installation / Configuration
Noise <60db
Current transformer ratio 60/5~150/5
Cooling Forced air cooling
Air flow requirement >105m³/h
Mounting Wall mount
Parallel configuration Unlimited
Extensions Modules in parallel
Protection level IP20
Cable entering bottom
EMC regarding IEC60038 class A (EN61000-6-4*, EN 61000-6-1)
Environmental
Ambient temperature -10℃~40℃
Temperature-Derating Derating above 40℃ (3%/K)
Maximum temperature 50℃
Permissible temperature range for transport -25 °C~+70 °C (regarding EN 50178)
Permissible temperature range for storage -25 °C~+55 °C (regarding EN 50178)
Relative Humidity 5%~95% Class F without condensation
Altitude below 1000m
Altitude Derating above 1000m (5%/1000m to 4000m)
Weight, Dimensions, Certifications
Weight 17 kg
Dimensions W*D*H[mm] 105*548*360
Certifications CE
*Warning note: This device is not intended to be used in residential areas and cannot ensure adequate
protection of radio reception in such environments.

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 42/44


Operating Instructions Z-D-15/35/55E-.. Enclosure
__________________________________________________________
9.1.3 Technical Data Active harmonic filter Z-D-55E-..
Electrical data
Network type 3 phase with/ without neutral 3P4W/3P3W
Rated voltage 380-480 V (+10 % / -15 %)
Rated current 55 A
Mains frequency 50 Hz / 60 Hz (5 Hz)
Harmonic compensation 1.-60. Harmonic
Response time 20 µs
Full response time 5 ms
Filter performance >96 %
Switching frequency 40 kHz-60 kHz, typical 50 kHz
Technology Advanced SIC
System topology Two Level Topology
Harmonic compensation, power factor correction, three phase
Function
balancing
Efficiency η >99,3% at nominal load
Power losses 721 W at 90 kW nominal power
User-Interface & Remote monitoring
HMI Not present / extern
Communication protocol RS485
PC-Software V3.2.3
Installation / Configuration
Noise <60db
Current transformer ratio 150/5~250/5
Cooling Forced air cooling
Air flow requirement >105m³/h
Mounting Wall mount
Parallel configuration Unlimited
Extensions Modules in parallel
Protection level IP20
Cable entering bottom
EMC regarding IEC60038 class A (EN61000-6-4*, EN 61000-6-1)
Environmental
Ambient temperature -10℃~40℃
Temperature-Derating Derating above 40℃ (3%/K)
Maximum temperature 50℃
Permissible temperature range for transport -25 °C~+70 °C (regarding EN 50178)
Permissible temperature range for storage -25 °C~+55 °C (regarding EN 50178)
Relative Humidity 5%~95% Class F without condensation
Altitude below 1000m
Altitude Derating above 1000m (5%/1000m to 4000m)
Weight, Dimensions, Certifications
Weight 19 kg
Dimensions W*D*H[mm] 105*548*360
Certifications CE
*Warning note: This device is not intended to be used in residential areas and cannot ensure adequate
protection of radio reception in such environments.

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 43/44


Operating Instructions Z-D-15/35/55E-.. Enclosure
__________________________________________________________
9.2 Service information
Service information
Our products are manufactured in accordance with the relevant international regulations. If you have
any questions concerning the use of our products or plan special uses, please contact:
If you have any technical questions while commissioning or regarding malfunctions, please contact
phone: +49 (0) 7940 16-800
Email: fan-controls-service@ziehl-abegg.de

Our worldwide contacts are available in our subsidiaries for deliveries outside of Germany, see
www.ziehl-abegg.com.
Our products are manufactured in compliance with the applicable international regulations. If you have
any questions about the use of our products or if you are planning special applications, please contact
us. We would be pleased to help

_________________________________________________________________________________

L-BAL-E321-GB 2021/11 Index 002 44/44