Special application in places with poor ventilation and places public attendance high.
DESCRIPTION
Application:
In low voltage power distribution networks. Special application in places with poor
ventilation, direct application in places with high public attendance. It can be installed
in ducts, ladders or cable trays,in dry, humid or wet environments.
Construction:
Marking:
Packing:
Colour:
Insulation: Natural.
National standards
NTP-IEC 60502-1: Power cables with extruded insulation and their accessories for
rated voltages from 1 kV and 3 kV.
Halogen free Oil resistance Gases toxicity Gases corrosivity Smoke density Flame retardant Fire retardant U.V resistance
IEC 60754-1 ICEA S-95-658 Zero toxicity to Zero Corrosivity Zero Smoke IEC 60332-1-2; FT1 IEC 60332-3-24 UL 2556 - Sunlight
IEC 60684-2 IEC 60754-2 Emission IEC Cat.C Resistance
61034-2
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 4.3 Generated 8/8/23 www.nexans.pe Page 1 / 6
FREETOX N2XOH 0,6/1 kV Single-core; Contact
UV Resist; METRIUM Local Sales
ventas.peru@nexans.com
International standards
IEC 60502-1: Power cables with extruded insulation and their accessories for rated
voltages from 1 kV and 3 kV.
IEC 60332-1-2: Test for vertical flame propagation for a single insulated wire or cable -
Procedure for 1 kW pre-mixed flame.
UL 2556: Wire and Cable Test Methods. Section 9.3: FT1 (Vertical-Specimen) Flame
Test.
IEC 60332-3-24: Test for vertical flame spread of vertically-mounted bunched wires or
cables - Category C.
IEC 60754-1: Test on gases evolved during combustion of materials from cables - Part
1: Determination of the halogen acid gas content.
IEC 60754-2: Test on gases evolved during combustion of materials from cables - Part
2: Determination of acidity (by pH measurement) and conductivity.
ICEA S-95-658: Power cables rated 2000 volts or less for the distribution of electrical
energy. Section 6.4.2: Oil Immersion Test.
UL 2556: Wire and Cable Test Methods. Section 4.2.8.5: Carbon-Arc and Xenon-Arc
Tests- Sunlight resistance.
CHARACTERISTICS
Construction characteristics
Conductor material Soft copper
Insulating material XLPE
Outer sheath Halogen free thermoplastic compound - UV
Resist.
Halogen free IEC 60754-1
Electrical characteristics
Dielectric strength 3.5 kV
Time of application Dielectric strength core to screen AC 5 min.
Usage characteristics
Oil resistance ICEA S-95-658
Halogen free Oil resistance Gases toxicity Gases corrosivity Smoke density Flame retardant Fire retardant U.V resistance
IEC 60754-1 ICEA S-95-658 Zero toxicity to Zero Corrosivity Zero Smoke IEC 60332-1-2; FT1 IEC 60332-3-24 UL 2556 - Sunlight
IEC 60684-2 IEC 60754-2 Emission IEC Cat.C Resistance
61034-2
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 4.3 Generated 8/8/23 www.nexans.pe Page 2 / 6
FREETOX N2XOH 0,6/1 kV Single-core; Contact
UV Resist; METRIUM Local Sales
ventas.peru@nexans.com
Usage characteristics
Gases toxicity Zero toxicity to IEC 60684-2
Gases corrosivity Zero Corrosivity IEC 60754-2
Smoke density Zero Smoke Emission IEC 61034-2
Flame retardant IEC 60332-1-2; FT1
Fire retardant IEC 60332-3-24 Cat.C
U.V resistance UL 2556 - Sunlight Resistance
Metric marking Double marking of sequential footage
METRIUM
Maximum operating temperature 90 °C
Overload maximum core temperature 130 °C
Short-circuit max. conductor temperature 250 °C
DIMENSIONAL DATA
Cross Conductor Min. insulation Min. outer sheath Diam. over Approx.
Total nb
section diam. thick. thick. sheath weight
wires
[mm²] [mm] [mm] [mm] [mm] [kg/km]
1.5 7 1.5 0.7 0.9 4.9 38
2.5 7 1.9 0.7 0.9 5.3 50
4 7 2.4 0.7 0.9 5.8 66
6 7 3.0 0.7 0.9 6.3 87
10 7 3.7 0.7 0.9 7.1 126
16 7 4.6 0.7 0.9 8 185
25 7 5.8 0.9 0.9 9.6 283
35 7 6.8 0.9 0.9 10.6 373
50 19 7.9 1.0 0.9 11.9 492
70 19 9.5 1.1 0.9 13.7 695
95 19 11.2 1.1 1.0 15.6 943
120 37 12.8 1.2 1.0 17.4 1183
150 37 14.2 1.4 1.1 19.4 1439
185 37 15.8 1.6 1.2 21.7 1810
240 37 18.2 1.7 1.2 24.1 2339
300 37 20.1 1.8 1.2 26.4 2901
400 61 23.3 2.0 1.4 30.4 3803
500 61 26.2 2.2 1.5 33.9 4809
630 61 30.0 2.4 1.6 38.4 6257
Halogen free Oil resistance Gases toxicity Gases corrosivity Smoke density Flame retardant Fire retardant U.V resistance
IEC 60754-1 ICEA S-95-658 Zero toxicity to Zero Corrosivity Zero Smoke IEC 60332-1-2; FT1 IEC 60332-3-24 UL 2556 - Sunlight
IEC 60684-2 IEC 60754-2 Emission IEC Cat.C Resistance
61034-2
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 4.3 Generated 8/8/23 www.nexans.pe Page 3 / 6
FREETOX N2XOH 0,6/1 kV Single-core; Contact
UV Resist; METRIUM Local Sales
ventas.peru@nexans.com
ELECTRICAL DATA
Cross Max. DC Resist. Perm. Current Perm. current rating in air current rating in Nominal
section Cond. 20°C buried/duct 20°C 30°C - flat formation air 30°C - trefoil capacitance
[mm²] [Ohm/km] [A] [A] [A] [pF/m]
1.5 12.1 21 22 21 200.0
2.5 7.41 28 30 29 239.0
4 4.61 36 42 40 286.0
6 3.08 44 55 53 363.0
10 1.83 58 77 74 408.0
16 1.15 75 105 101 492.0
25 0.727 96 141 135 490.0
35 0.524 115 176 169 564.0
50 0.387 135 216 207 589.0
70 0.268 167 279 268 641.0
95 0.193 197 342 328 744.0
120 0.153 223 400 383 778.0
150 0.124 251 464 444 747.0
185 0.0991 281 533 510 713.0
240 0.0754 324 634 607 762.0
300 0.0601 365 736 703 802.0
400 0.047 426 868 823 838.0
500 0.0366 481 998 946 859.0
630 0.0283 545 1151 1088 901.0
PRODUCT LIST
Nexans Ref. Country Ref. Name Sheath colour Approximate weight
[kg/km]
P00038736-1 - FREETOX N2XOH 0,6/1 kV 50 mm2 VD Green - UV 492
P00038737-0 - FREETOX N2XOH 0,6/1 kV 70 mm2 VD Green - UV 695
P00038729-0 - FREETOX N2XOH 0,6/1 kV 10 mm2 AZ Blue - UV 126
P00038734-0 - FREETOX N2XOH 0,6/1 kV 16 mm2 VD Green - UV 185
P00038342-DB-1 - FREETOX N2XOH 0,6/1 kV 16 mm2 Black - UV 185
P00038345-DB-1 - FREETOX N2XOH 0,6/1 kV 95 mm2 Black - UV 943
P00038346-DB-0 - FREETOX N2XOH 0,6/1 kV 120 mm2 Black - UV 1184
P00038901-0 - FREETOX N2XOH 0,6/1 kV 6 mm2 - VD Green - UV 87
= Make to order, = In stock,
Halogen free Oil resistance Gases toxicity Gases corrosivity Smoke density Flame retardant Fire retardant U.V resistance
IEC 60754-1 ICEA S-95-658 Zero toxicity to Zero Corrosivity Zero Smoke IEC 60332-1-2; FT1 IEC 60332-3-24 UL 2556 - Sunlight
IEC 60684-2 IEC 60754-2 Emission IEC Cat.C Resistance
61034-2
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 4.3 Generated 8/8/23 www.nexans.pe Page 4 / 6
FREETOX N2XOH 0,6/1 kV Single-core; Contact
UV Resist; METRIUM Local Sales
ventas.peru@nexans.com
Halogen free Oil resistance Gases toxicity Gases corrosivity Smoke density Flame retardant Fire retardant U.V resistance
IEC 60754-1 ICEA S-95-658 Zero toxicity to Zero Corrosivity Zero Smoke IEC 60332-1-2; FT1 IEC 60332-3-24 UL 2556 - Sunlight
IEC 60684-2 IEC 60754-2 Emission IEC Cat.C Resistance
61034-2
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 4.3 Generated 8/8/23 www.nexans.pe Page 5 / 6
FREETOX N2XOH 0,6/1 kV Single-core; Contact
UV Resist; METRIUM Local Sales
ventas.peru@nexans.com
CURRENT CAPACITY VALUES AND CURRENT CALCULATION CONDITIONS BASED ON IEC 60364-5-52:2009 :
Halogen free Oil resistance Gases toxicity Gases corrosivity Smoke density Flame retardant Fire retardant U.V resistance
IEC 60754-1 ICEA S-95-658 Zero toxicity to Zero Corrosivity Zero Smoke IEC 60332-1-2; FT1 IEC 60332-3-24 UL 2556 - Sunlight
IEC 60684-2 IEC 60754-2 Emission IEC Cat.C Resistance
61034-2
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 4.3 Generated 8/8/23 www.nexans.pe Page 6 / 6