Professional Documents
Culture Documents
Performance Availability Guarantee
Performance Availability Guarantee
ANNEX 8.1
PERFORMANCE &
AVAILABILITY GUARANTEE
CONTENTS
1 INTRODUCTION .........................................................................................................................................3
1.1 PRINCIPLE 3
1.2 DEFINITIONS 3
1.3 REFERENCE DOCUMENTS 6
2 ENERGY AVAILABILITY ..............................................................................................................................7
2.1 DEFINITION 7
2.2 EXCLUSIONS 8
2.3 CALCULATION 8
2.3.1 LOSS CALCULATION – PARTIAL UNAVAILABILITY 9
2.3.2 LOSS CALCULATION – SITUATION OF GLOBAL UNAVAILABILITY 9
2.4 GUARANTEED AVAILABILITY 11
2.4.1 PENALTIES DURING VERIFICATION PERIOD 1 11
2.4.2 PENALTIES DURING VERIFICATION PERIOD 2 11
2.5 REFERENCE PERFORMANCE RATIO 12
2.5.1 DEFINITION 12
2.5.2 CALCULATION 12
2.5.3 SIMULATION PARAMETERS 13
2.6 WEATHER CORRECTED PERFORMANCE RATIO 16
2.6.1 CALCULATION 16
2.6.2 MEASURED WEATHER FILE FORMAT 17
2.7 MEASURED PERFORMANCE RATIO 18
2.8 SUMMARY OF THE METHODOLOGY 20
2.9 GUARANTEED PERFORMANCE 21
2.9.1 PENALTIES DURING VERIFICATION PERIOD 1 22
2.9.2 PENALTIES DURING VERIFICATION PERIOD 2 22
3 PENALTIES AS REMEDIES .........................................................................................................................23
ANNEX: PVSYST SIMULATION PARAMETERS ....................................................................................................24
PV MODULE FILE 24
INVERTER FILE 24
2/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
1 INTRODUCTION
1.1 PRINCIPLE
This annex describes all the calculations and tests that need to be made in order to validate the
performance of the PV Plant, which is determined by its ability to deliver the maximum active electrical
energy from solar energy.
This performance will be calculated through two indicators:
▪ The Energy Availability, 𝑨
▪ The Measured Performance Ratio, 𝑷𝑹𝑴𝒆𝒂𝒔𝒖𝒓𝒆𝒅
1.2 DEFINITIONS
Capitalized terms not defined in this Annex 8.1 shall have the meaning ascribed to them in the
Contract.
3/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
4/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
𝑷𝑹𝑹𝒆𝒇 𝒐𝒓 𝑹𝒆𝒇𝒆𝒓𝒆𝒏𝒄𝒆 𝑷𝒆𝒓𝒇𝒐𝒓𝒎𝒂𝒏𝒄𝒆 𝑹𝒂𝒕𝒊𝒐: is the ratio of the net energy produced by the PV Plant
ERef compared to the net energy that could have been
produced by a “perfect” system.
5/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
ID Document title
6/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
2 ENERGY AVAILABILITY
2.1 DEFINITION
The Energy Availability, named 𝑨, corresponds to the ratio of the PV Plant actual output energy to the
PV plant potential output energy if it were operating without any system downtime or any
unavailability of one of its components.
This Availability includes all types of unavailability under Contractor’s responsibility such as, but not
limited to:
▪ Inverter Failure, Disconnection or Communication Failure (including its potential
external control devices);
▪ Transformer Failure or Disconnection;
▪ DC junction box Failure, Disconnection or Communication Failure;
▪ Failure or Disconnection inside the MV switchgears located in the transformation station
or the MV switchgears located in the MV Substation;
▪ PV string Failure or Disconnection;
▪ Any cable default from the PV panels to the Point of Interconnection (cut,
degradation, isolation default, fusion, etc.) which prevents the normal current
circulation;
▪ Any preventive maintenance intervention that requires Disconnection of the PV Plant
or its devices.
▪ Overhead line from the PV plant and the interconnection equipment at AFINIA
substation.
The energy losses due to these circumstances and any other causes of unavailability other than
exclusions under Employer’s responsibility, are named 𝑬𝑳𝒐𝒔𝒔_𝑪𝒐𝒏𝒕𝒓𝒂𝒄𝒕𝒐𝒓 .
Exclusions listed in paragraph 2.2 describe the types of unavailability that do not fall under
Contractor’s responsibility but under Employer’s responsibility, and are accounted for under the name
𝑬𝑳𝒐𝒔𝒔_𝑬𝒎𝒑𝒍𝒐𝒚𝒆𝒓 .
7/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
2.2 EXCLUSIONS
2.3 CALCULATION
Where:
▪ 𝑨 is the Energy Availability of the PV Plant for the period considered for calculation, expressed
with 4 significant digits (namely 0.9975 which is written 99.75%)
▪ 𝑬𝑳𝒐𝒔𝒔_𝑪𝒐𝒏𝒕𝒓𝒂𝒄𝒕𝒐𝒓_𝒊 is the energy loss due to failure “i” under the Contractor’s responsibility, which
appeared during the period considered for calculation. 𝑬𝑳𝒐𝒔𝒔_𝑪𝒐𝒏𝒕𝒓𝒂𝒄𝒕𝒐𝒓_𝒊 is expressed with 4
significant digits, in kWh
▪ 𝑬𝑳𝒐𝒔𝒔_𝑬𝒎𝒑𝒍𝒐𝒚𝒆𝒓_𝒊 is the energy loss due to failure “i” under the Employer’s responsibility, which
appeared during the period considered for calculation. 𝑬𝑳𝒐𝒔𝒔_𝑬𝒎𝒑𝒍𝒐𝒚𝒆𝒓_𝒊 is expressed with 4
significant digits, in kWh
▪ 𝑬𝑮𝒓𝒊𝒅 is the active net energy produced by the PV Plant, in kWh, during the period considered
for calculation and measured at the Point of Connection with the Grid. It considers all energy
injected by the PV Plant and consumed by the grid
8/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
2.3 .1 L OS S C A LC UL A TI O N – P A R TI A L U N A V AI L ABI LI TY
For each failure leading to a partial unavailability, its corresponding loss is calculated according to
the ratio between total nominal power capacity of the devices connected Downstream from the
unavailable device 𝑷𝒖𝒏𝒂𝒗𝒂𝒊𝒍𝒂𝒃𝒍𝒆_𝒊 and total nominal power capacity of the PV Plant 𝑷𝑷𝒆𝒂𝒌 .
The corresponding energy losses 𝑬𝑳𝒐𝒔𝒔_𝒊 , either due to Contractor’s or Employer’s responsibility, are
counted only during the time of unavailability of the device and are calculated as follows:
𝑷𝒖𝒏𝒂𝒗𝒂𝒊𝒍𝒂𝒃𝒍𝒆_𝒊
𝑬𝑳𝒐𝒔𝒔_𝒊 = × 𝑬𝑷𝒓𝒐𝒅_𝒊
𝑷𝑷𝒆𝒂𝒌 − 𝑷𝒖𝒏𝒂𝒗𝒂𝒊𝒍𝒂𝒃𝒍𝒆_𝒊
Where:
▪ 𝑬𝑳𝒐𝒔𝒔_𝒊 corresponds to energy losses due to the failure “i”, in kWh
▪ 𝑷𝒖𝒏𝒂𝒗𝒂𝒊𝒍𝒂𝒃𝒍𝒆_𝒊 is the peak power of unavailable devices connected Downstream from the failure
“i”, in kWp
▪ 𝑷𝑷𝒆𝒂𝒌 is the total nominal power capacity of the PV Plant, in kWp
▪ 𝑬𝑷𝒓𝒐𝒅_𝒊 is the total energy generated during the failure “i”, in kWh
For example, in a plant containing 9 MWp of PV modules connected with 9 inverters (each inverter
connects 1MWp of PV panels), if two inverters are not available and during this unavailability 3,5 MWh
have been delivered to the Point of Connection with the available inverters, then the energy loss
corresponding to this unavailability is:
2
𝑬𝑳𝒐𝒔𝒔_𝒊 = × 3,5
9−2
2
𝑬𝑳𝒐𝒔𝒔_𝒊 = × 3,5
7
𝑬𝑳𝒐𝒔𝒔_𝒊 = 1,0 MWh
2.3 .2 L OS S C A LC UL A TI O N – SI T U A TI O N O F G L OB A L U N A V AI L ABI LI T Y
For each failure leading to a global unavailability, the corresponding energy losses 𝑬𝑳𝒐𝒔𝒔_𝒊 are
calculated on the basis of the monthly reference performance 𝑷𝑹𝑴𝒐𝒏𝒕𝒉_𝑹𝒆𝒇_𝒊 of the PV Plant, as defined
in the PVSyst simulation report in Annex 2.5 and indicated in Table 1 below
9/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
The corresponding energy losses 𝑬𝑳𝒐𝒔𝒔_𝒊 are counted only during the time of unavailability of the device
and are calculated as follows:
Where:
▪ 𝑬𝑳𝒐𝒔𝒔_𝒊 is the energy loss observed during failure “I”, in kWh
▪ 𝑷𝑷𝒆𝒂𝒌 is the sum of peak power from all PV modules nameplate, in kWp
▪ 𝑮𝑻𝑰 is the total measured solar energy during the period of unavailability in the plane of array, in
kWh/m2
▪ 𝑷𝑹𝑴𝒐𝒏𝒕𝒉_𝑹𝒆𝒇_𝒊 is the Reference Performance Ratio of the month during which the unavailability
occurs. The different values of 𝑷𝑹𝑴𝒐𝒏𝒕𝒉_𝑹𝒆𝒇_𝒊 are detailed in Annex 2.5, and given in the following
table:
Theoretical Specific
Month 𝐏𝐑 𝐌𝐨𝐧𝐭𝐡_𝐑𝐞𝐟 Energy based on TMY
(annex 8.4)
Table 1 – Monthly PR
Remark : In case of unavailability of Global Tilted Irradiation (GTI) data, because of a SCADA
unavailability or pyranometers failure, the Contractor shall suggest a replacement method for the
missing data, on the basis of realistic assumptions which will be detailed (extrapolation, using data
from a nearby weather station or from satellite weather systems).
* This value is adjusted by a factor of -0.31 % due to the influence of the topography in the simulation
(not considered due to PVsyst limitations).
10/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
For a defined test period, the Contractor commits to ensure an Availability 𝑨 equal or superior to a
Guaranteed Availability 𝑨𝒈 .
For this project:
𝑨𝒈 = 𝟗𝟖. 𝟓𝟎%
If 𝑨𝑽𝑷_𝟏 , during the Verification period 1, is below 𝑨𝒈 then penalties shall be paid by the Contractor in
order to compensate the production losses.
These penalties are calculated as follows:
(𝑨𝒈 − 𝑨𝑽𝑷_𝟏 )
𝑷 𝑨_𝑽𝑷𝟏 = × 𝒄𝟏
𝑨𝒈
Where:
▪ 𝒄𝟏 is the coefficient for Verification Period 1 and is equal to 9,205 MCOP
▪ 𝑨𝒈 is the Guaranteed Availability
▪ 𝑨𝑽𝑷_𝟏 is the Availability of the PV Plant during Verification Period 1
▪ 𝑷𝑨_𝑽𝑷𝟏 is the penalties payable by the Contractor to compensate the production losses during
Verification Period 1
11/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
Where:
▪ 𝑨𝒈 is the Guaranteed Availability
▪ 𝑨𝑽𝑷_𝟐 is the Availability of the PV Plant during Verification Period 2
▪ 𝑷𝑨𝑽𝑷𝟐 −𝟏 is the penalties payable by the Contractor to compensate the production losses due to
Special Events
▪ 𝑷𝑨𝑽𝑷𝟐 −𝟐 is the penalties payable by the Contractor to compensate the production losses due to
Intrinsic Defaults
▪ 𝒄𝟐−𝟏 is the coefficient for Verification Period 2 Special Events and is equal to 9,205 MCOP
▪ 𝒄𝟐−𝟐 is the coefficient for Verification Period 2 Intrinsic Defaults and is equal to 97,258
MCOP,
2.5 .1 DE FI NI TI O N
The Performance Ratio, named PR, as defined in IEC 61724 standard, indicates the overall effect of
losses on the array rated output, due to array temperature, incomplete utilization of the incident
irradiation, and system component inefficiencies or Failures.
The performance of the PV plant is initially assessed through simulation, in order to define a Reference
Performance Ratio. This simulation is based on historical meteorological data.
To limit the bias error correlated to actual weather conditions, the Reference Performance Ratio is
recalculated to adjust to the actual measured weather. A new simulation following the same model
is carried out with on-site weather conditions measurements, to define a Weather Corrected
Performance Ratio.
Based on on-site energy production and weather conditions, a Measured Performance Ratio is
calculated, and compared to the Weather Corrected Performance Ratio.
2.5 .2 C A LC U L A TIO N
The Reference Performance Ratio 𝑷𝑹𝑹𝒆𝒇 as defined in Annex 2.5 corresponds to the ratio of the net
energy produced compared to the net energy that could have been produced by a “perfect”
system. Such PR includes all PV Plant losses: far and near shadings, PV conversion, module quality,
dust, inverter and transformer efficiencies, cable losses, auxiliaries, etc.
Disclaimer: The PVSYST simulation described in Annex 2.5 “Reference PR PVsyst simulation report” does
not consider possible irradiance losses due to Near Shadings originated by trees, either inside AKUO
property or outside on third party properties. The Employer will guarantee that the areas that may
have a negative impact on the Yield of the PV Plant will be identified, removing the corresponding
trees. In the event of the Employer not being able to act due to external factors, both Parties agree
to revise the PVsyst simulation to take into consideration such impact in the Performance Guarantees
calculation.
𝑷𝑹𝑹𝒆𝒇 is based on a simulation from PVsyst software (version 7.1). The simulation is based on historical
weather data, the Typical Meteorological Year (TMY) Weather File provided in Annex 8.4. This file
12/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
contains hourly time series of horizontal and plane of array irradiances, ambient temperature and
wind speed. The simulation parameters are listed in section 2.5.3.
The unavailability of the PV Plant as well as grid unavailability are excluded from the 𝑷𝑹𝑹𝒆𝒇
calculations.
This 𝑷𝑹𝑹𝒆𝒇 is calculated as follows:
𝑬𝑹𝒆𝒇
𝑷𝑹𝑹𝒆𝒇 =
𝑮𝑻𝑰𝑹𝒆𝒇
𝑷𝑷𝒆𝒂𝒌 ×
𝜱𝑺𝑻𝑪
Where:
▪ 𝑬𝑹𝒆𝒇 is the total estimated AC energy from the PVSyst simulation performed internally, using
simulation parameters indicated in the Contract and TMY Weather File, in kWh (excluding
unavailability)
▪ 𝑮𝑻𝑰𝑹𝒆𝒇 is the Global Tilted Irradiation estimated from the PVSyst simulation performed internally,
using simulation parameters indicated in the Contract and TMY Weather File, in kWh/m 2. Far
shadings are excluded from the calculation of 𝑮𝑻𝑰𝑹𝒆𝒇 .
▪ 𝜱𝑺𝑻𝑪 is the irradiance at Standard Test Conditions (STC), 1 kW/m2
▪ 𝑷𝑷𝒆𝒂𝒌 is the sum of peak power from all PV modules nameplate, in kWp
2.5 .3 SI M U L AT IO N P A R A ME TE R S
This section describes the parameters of the PVsyst simulation which are used to calculate 𝑷𝑹𝑹𝒆𝒇 based
on TMY Weather File. The simulation is carried out with the version 7.1 of PVsyst software.
If the simulation needs to be performed again in the future, the exact same version of PVsyst software
shall be used, unless both Stakeholders agree on another solution according to each specific project.
The result report of the simulation is provided in Annex 2.5 “Energy Yield Assessment”.
The simulation parameters related to PV modules and inverters are detailed in Annex 1 at the end of
this Document.
2.5 .4 M ODE LI N G P A R A ME T E R S
All parameters for which no value is entered are considered to be in their default state or default
value.
# GENERAL PARAMETERS
# PROJECT SETTINGS
## ALBEDO
13/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
ALBEDO 0.20
## DESIGN CONDITIONS
# ORIENTATION
Azimuth 0°
Pitch 10,7 m
Electrical effect NO
# SYSTEM
## SUB ARRAY #1
Nb. of inverters 6
Mod. in series 30
# DETAILED LOSSES
## THERMAL PARAMETERS
14/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
## OHMIC LOSSES
## SOILING LOSS
## IAM LOSSES
IAM Custom
## AUXILIARIES
Night loss NA
15/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
# HORIZON
# NEAR SHADING
# MISCELLANEOUS
## INVERTER TEMPERATURE
Type Outdoor
## POWER FACTOR
PF 0.8
Limit applied at NA
Specified PF NA
2.6 .1 C A LC U L A TIO N
In order to properly account for the actual weather conditions observed during the period of interest
for performance tests during the Verification Periods, which might impact positively or negatively the
apparent performance of the Plant, the 𝑷𝑹𝑹𝒆𝒇 needs to be adjusted. This includes an adjustment to
the Soiling Factor, which will be measured throughout the year with the Weather Station.
A new simulation is thus performed at the end of each Verification Period to determine the Weather
Corrected Performance Ratio 𝑷𝑹𝑾𝒆𝒂𝒕𝒉𝒆𝒓 , using the exact same model as for 𝑷𝑹𝑹𝒆𝒇 calculation.
The parameters are listed in section 2.5.2, but the previous weather input consisting of TMY Weather
File is replaced with the Measured Weather file, which contains data from on-site measurements.
This 𝑷𝑹𝑾𝒆𝒂𝒕𝒉𝒆𝒓 is calculated as follows:
𝑬𝑾𝒆𝒂𝒕𝒉𝒆𝒓
𝑷𝑹𝑾𝒆𝒂𝒕𝒉𝒆𝒓 =
𝑮𝑻𝑰𝑴𝒆𝒂𝒔𝒖𝒓𝒆𝒅
𝑷𝑷𝒆𝒂𝒌 × × (𝟏 − 𝒌𝑳𝒐𝒔𝒔_𝑭𝒂𝒓_𝑺𝒉𝒂𝒅𝒊𝒏𝒈𝒔 )
𝜱𝑺𝑻𝑪
16/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
Where:
▪ 𝑬𝑾𝒆𝒂𝒕𝒉𝒆𝒓 is the total estimated AC energy from the PVsyst simulation performed internally, using
simulation parameters indicated in the Contract and Measured Weather File, in kWh (excluding
unavailability)
▪ 𝑮𝑻𝑰𝑴𝒆𝒂𝒔𝒖𝒓𝒆𝒅 is the total measured solar energy in the plane of array, in kWh/m2. 𝑮𝑻𝑰𝑴𝒆𝒂𝒔𝒖𝒓𝒆𝒅 includes
all periods of unavailability of the PV Plant.
▪ 𝒌𝑳𝒐𝒔𝒔_𝑭𝒂𝒓_𝑺𝒉𝒂𝒅𝒊𝒏𝒈𝒔 is energy losses coefficient due to far shadings, in %. For this project, 𝒌𝑳𝒐𝒔𝒔_𝑭𝒂𝒓_𝑺𝒉𝒂𝒅𝒊𝒏𝒈𝒔
is equal to 0,85%
▪ 𝜱𝑺𝑻𝑪 is the irradiance at Standard Test Conditions (STC), 1 kW/m2
▪ 𝑷𝑷𝒆𝒂𝒌 is the sum of peak power from all PV modules nameplate, in kWp
The 𝑷𝑹𝑾𝒆𝒂𝒕𝒉𝒆𝒓 calculation excludes all unavailability of the PV plant and the Grid.
2.6 .2 ME A S U RE D WE A THE R FI LE F O R MA T
The Measured Weather file, which is used in the simulation for 𝑷𝑹𝑾𝒆𝒂𝒕𝒉𝒆𝒓 calculation, will consist in hourly
averages.
Measured data will come from a subset of installed plant instrumentation identified in the Contracts
and shall include the following:
▪ Horizontal pyranometers to determine global horizontal irradiance, in W/m²
▪ Inclined pyranometers in the Plane of Array (POA) to determine POA irradiance in W/m²
▪ Thermometer to determine the ambient temperature, in °C
Collected data will be reviewed for accuracy and will be reduced to hourly averages for the
calculations. If there are redundant instruments, then the average of all redundant instruments will be
used in the calculations.
Some missing or invalid data may occur (in case of defaulting instruments). These data will be treated
as indicated in the following sections. However, since the PV Plant will be equipped with redundant
instruments, the risk for missing measurements is particularly low.
17/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
2.6 .2 .2 T RE A TME N T O F I N V AL I D OR MI S SI N G D AT A
Invalid or missing data will be treated as follows:
- They can be replaced by estimations from valid data recorded before or after the invalid or
missing data occurred
- They can be replaced by average values corresponding to the same period of interest
- The time interval corresponding to the invalid or missing data may be assessed as invalid and
removed from the analysis
The Measured Weather file data will be presented in the following format:
2018 01 01 8 1232 26
… … … … … …
The Measured Performance Ratio 𝑷𝑹𝑴𝒆𝒂𝒔𝒖𝒓𝒆𝒅 is based on measurement from on-site pyranometers and
Point of Connection (POC) energy meter.
The unavailability of the PV Plant as well as grid unavailability are included in the 𝑷𝑹𝑴𝒆𝒂𝒔𝒖𝒓𝒆𝒅
calculations.
This 𝑷𝑹𝑴𝒆𝒂𝒔𝒖𝒓𝒆𝒅 is calculated as follows:
18/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
▪ 𝑮𝑻𝑰𝑴𝒆𝒂𝒔𝒖𝒓𝒆𝒅 is the total measured solar energy in the plane of array, in kWh/m 2, including
periods where the grid and the PV Plant are unavailable
▪ 𝒌𝑳𝒐𝒔𝒔_𝑭𝒂𝒓_𝑺𝒉𝒂𝒅𝒊𝒏𝒈𝒔 is energy losses coefficient due to far shadings, in %. For this project, 𝒌𝑳𝒐𝒔𝒔_𝑭𝒂𝒓_𝑺𝒉𝒂𝒅𝒊𝒏𝒈𝒔
is equal to 0.85%
▪ 𝜱𝑺𝑻𝑪 is the irradiance at Standard Test Conditions (STC), 1 kW/m2
▪ 𝑷𝑷𝒆𝒂𝒌 is the sum of peak power from all PV modules nameplate, in kWp
19/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
Step 1:
Determination of Reference Performance Ratio 𝑃𝑅𝑅𝑒𝑓
HISTORICAL/TMY PV Plant
weather data parameters
Simulation model
Reference Performance
Ratio 𝑷𝑹𝑹𝒆𝒇
Step 2:
Determination of Weather Corrected Performance Ratio 𝑃𝑅𝑊𝑒𝑎𝑡ℎ𝑒𝑟
MEASURED PV Plant
weather data parameters
Weather Corrected
Performance Ratio
𝑷𝑹𝑾𝒆𝒂𝒕𝒉𝒆𝒓
20/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
Step 3:
Determination of Measured Performance Ratio 𝑃𝑅𝑀𝑒𝑎𝑠𝑢𝑟𝑒𝑑
Measured
Performance Ratio
𝑷𝑹𝑴𝒆𝒂𝒔𝒖𝒓𝒆𝒅
Figure 1 above: Diagram representing the modelling and calculation procedure of Reference,
Weather Corrected and Measured Performance Ratios using historical and measured weather
data
The Measured Performance Ratio is then compared to the Weather Corrected Performance Ratio.
Although the Reference Performance Ratio is not used for the comparison of simulated and measured
performances, this index remains a good reference point of the expected Performance Ratio of the
PV Plant.
The Contractor commits to ensure a 𝑷𝑹𝑴𝒆𝒂𝒔𝒖𝒓𝒆𝒅 , excluding unavailability of the Grid and PV Plant,
equal or superior to a Guaranteed Performance Ratio called 𝑷𝑹𝑮𝒖𝒂𝒓𝒂𝒏𝒕𝒆𝒆𝒅 , defined for each
Verification Period. Performance is deemed acceptable if the following formula is verified:
𝑷𝑹𝑴𝒆𝒂𝒔𝒖𝒓𝒆𝒅 ≥ 𝑷𝑹𝑮𝒖𝒂𝒓𝒂𝒏𝒕𝒆𝒆𝒅
with
Where:
▪ 𝑪𝒐𝒏𝒕𝒓𝒂𝒄𝒕_𝑻𝒐𝒍𝒆𝒓𝒂𝒏𝒄𝒆 is set at 98%, assuming:
- Accuracy of active power measurement
- Accuracy of combined pyranometers irradiance measurement
- Modelling inaccuracies
For verification period VP1 and VP2, 𝑷𝑹𝑮𝒖𝒂𝒓𝒂𝒏𝒕𝒆𝒆𝒅 is corrected by a coefficient 𝑷𝑽𝒎𝒐𝒅𝑫𝒆𝒈𝒓𝒂𝒅𝒂𝒕𝒊𝒐𝒏
representing the guaranteed maximum yearly degradation of the PV modules peak power.
𝑷𝑽𝒎𝒐𝒅𝑫𝒆𝒈𝒓𝒂𝒅𝒂𝒕𝒊𝒐𝒏 = 𝟎, 𝟓%/𝒚𝒆𝒂𝒓
21/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
𝑷𝑹𝑮𝒖𝒂𝒓𝒂𝒏𝒕𝒆𝒆𝒅_𝑽𝑷𝟏 is defined as the PR simulated using the simulation parameters indicated in section
2.5.3 and the weather measured during Verification Period 1, taking into account the PV module
guaranteed performance degradation.
𝑷𝑹𝑮𝒖𝒂𝒓𝒂𝒏𝒕𝒆𝒆𝒅_𝑽𝑷𝟏 = 𝑪𝒐𝒏𝒕𝒓𝒂𝒄𝒕_𝑻𝒐𝒍𝒆𝒓𝒂𝒏𝒄𝒆 × 𝑷𝑹𝑾𝒆𝒂𝒕𝒉𝒆𝒓 (𝑾𝒆𝒂𝒕𝒉𝒆𝒓𝑽𝑷𝟏 )
Where :
▪ 𝑷𝑹𝑾𝒆𝒂𝒕𝒉𝒆𝒓 (𝑾𝒆𝒂𝒕𝒉𝒆𝒓𝑽𝑷𝟏 ) is the Weather Corrected Performance Ratio calculated with the
simulation parameters defined in section 2.5.3 and the Measured Weather data from verification
period 1
If the 𝑷𝑹𝑴𝒆𝒂𝒔𝒖𝒓𝒆_𝑽𝑷𝟏 measured during the Verification Period 1 is below the 𝑷𝑹𝑮𝒖𝒂𝒓𝒂𝒏𝒕𝒆𝒆𝒅_𝑽𝑷𝟏 , then
penalties shall be paid by the Contractor to compensate the production contractor losses.
These penalties are calculated as follows:
𝑷𝑹𝑮𝒖𝒂𝒓𝒂𝒏𝒕𝒆𝒆𝒅_𝑽𝑷𝟏 − 𝑷𝑹𝑴𝒆𝒂𝒔𝒖𝒓𝒆𝒅_𝑽𝑷𝟏
𝑷𝑽𝑷𝟏 = × 𝒄𝟏
𝑷𝑹𝑮𝒖𝒂𝒓𝒂𝒏𝒕𝒆𝒆𝒅_𝑽𝑷𝟏
Where 𝒄𝟏 is the coefficient for Verification Period 1 and is equal to 9,205 MCOP.
𝑷𝑹𝑮𝒖𝒂𝒓𝒂𝒏𝒕𝒆𝒆𝒅_𝑽𝑷𝟐 is defined as the PR simulated using the simulation parameters indicated in section
2.5.3 and the weather measured during Verification Period 2, taking into account PV module
guaranteed performance degradation. 𝑷𝑹𝑮𝒖𝒂𝒓𝒂𝒏𝒕𝒆𝒆𝒅_𝑽𝑷𝟐 is calculated as follows:
𝑷𝑹𝑮𝒖𝒂𝒓𝒂𝒏𝒕𝒆𝒆𝒅_𝑽𝑷𝟐 = 𝑪𝒐𝒏𝒕𝒓𝒂𝒄𝒕_𝑻𝒐𝒍𝒆𝒓𝒂𝒏𝒄𝒆 × 𝑷𝑹𝑾𝒆𝒂𝒕𝒉𝒆𝒓 (𝑾𝒆𝒂𝒕𝒉𝒆𝒓𝑽𝑷𝟐 ) × (𝟏 − 𝑷𝑽𝒎𝒐𝒅𝑫𝒆𝒈𝒓𝒂𝒅𝒂𝒕𝒊𝒐𝒏)
Where :
▪ 𝑷𝑹𝑾𝒆𝒂𝒕𝒉𝒆𝒓 (𝑾𝒆𝒂𝒕𝒉𝒆𝒓𝑽𝑷𝟐 ) is the Weather Corrected Performance Ratio calculated with the
simulation parameters defined in section 2.5.3 and the Measured Weather data from verification
period 2
If the 𝑷𝑹𝑴𝒆𝒂𝒔𝒖𝒓𝒆_𝑽𝑷𝟐 measured during the Verification Period 2 is below the 𝑷𝑹𝑮𝒖𝒂𝒓𝒂𝒏𝒕𝒆𝒆𝒅_𝑽𝑷𝟐 , then
penalties will be applied to the Contractor to compensate the production losses.
These penalties are calculated as follows:
𝑷𝑹𝑮𝒖𝒂𝒓𝒂𝒏𝒕𝒆𝒆𝒅_𝑽𝑷𝟐 − 𝑷𝑹𝑴𝒆𝒂𝒔𝒖𝒓𝒆𝒅
𝑷𝑽𝑷𝟐 = × 𝒄𝟐
𝑷𝑹𝑮𝒖𝒂𝒓𝒂𝒏𝒕𝒆𝒆𝒅_𝑽𝑷𝟐
Where 𝒄𝟐 is the coefficient for Verification Period 2 and is equal to 97,258 MCOP.
22/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
3 PENALTIES AS REMEDIES
The Parties acknowledge and agree that it is difficult or impossible to determine with precision the
amount of damages that would or might be incurred by Employer as a result of the failure of the PV
Plant to achieve the guaranteed availability and/or performance levels for the PV Plant. It is
understood and agreed by the Parties that (i) the Employer suffers a damage by failure of the PV Plant
to achieve the guaranteed availability and/or performance levels, (ii) it would be impracticable or
extremely difficult to accurately determine the actual damages resulting therefrom, (iii) any penalties
which should become payable under paragraphs 2.4.1, 3.6.1 and 3.6.2 of this Annex 8.1 are fair and
reasonable, and (iv) each payment represents a reasonable estimate of fair compensation for the
losses that may reasonably be anticipated from each such failure.
23/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
This section describes PV modules and inverters settings for PVsyst simulations.
PV MODULE FILE
24/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
25/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
26/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
INVERTER FILE
27/28
DocuSign Envelope ID: 62BDC244-E6CB-4685-8E8E-982C04EEBA8A
28/28