Professional Documents
Culture Documents
Lab 5 Refrigeration-1
Lab 5 Refrigeration-1
Lab 5 Refrigeration-1
In the previous lab, we examined the compressor of the refrigeration cycle. That experiment
observed the performance and calculated the efficiency. This allows us to observe the
refrigeration cycle as a complete system. We will use the Hampden Model H-6710 Refrigeration
cycle demonstrator for this experiment. For this lab, we will be finding the coefficient of
performance and coefficient of refrigeration.
Equipment Setup
The Hampden Model H-6710 Refrigeration demonstrator is shown in Figure 1. There are
thermocouples located on each side of the condenser to measure the temperature for both the
water and refrigerant. When the refrigerant passes through the condenser it is cooled by tap
water. The water is supplied from a faucet, and drained into a sink. There are pressure gauges
and thermocouples to measure the pressure and temperature of the refrigerant before and
after both the condenser and evaporator.
Expansion Refrigerant
Valve Flowmeter
Evaporator
(Inside)
Condenser
Water Input
Compressor
Condenser
Water
Condenser
Water Input BV-3
Flowmeter Condenser
The unit is shut down by reversing the start up procedure after returning the compressor
control frequency to 60 Hz. You must press the stop button on the compressor motor controller
and wait until the motor ramps down to a stop before starting to turn off the power. For long
term shut down the instructor will pump the R134a refrigerant into the storage can.
Condenser Theory
The condenser of the refrigeration cycle is a counter-flow, shell-and-tube heat exchanger. If the
heat exchanger is completely insulated, we can assume that there is no heat loss in the pipes,
and we can assume that the water absorbs heat lost by the refrigerant so it can later expand in
the evaporator, gaining heat. The goal of the condenser in the refrigeration cycle is to cool the
hot refrigerant with water. In order to calculate the heat gained by the water we must use the
following equation
Q= ṁc ∆ T Eqn 1
Where Q is the heat gained from the refrigerant per unit time, ṁ is the mass flow rate (in
lbm/s), c is the specific heat (in Btu/lbm°F) and ΔT is the change in temperature (in °F). The
value of the specific heat can vary by temperature, but for water the change is minimal for the
range of temperatures you will observe. For this lab the specific heat value will be 1 Btu/lbm °F.
To calculate the heat loss of the refrigerant, one must understand what is occurring in the
condenser. The refrigerant is going through a phase change. When the refrigerant leaves the
compressor, it leaves at a high pressure, high temperature gas. When the refrigerant passes
though the condenser it changes from a gas to a liquid. The refrigerant will leave as a low
temperature, high pressure liquid. Since the refrigerant is going through the phase change and
a drop in temperature, the specific heat cannot be used. Therefore, equation 1 will be invalid
for finding the heat loss of the refrigerant. In order to find the heat loss of the refrigerant you
must find the change in enthalpy. The equation is as follows:
where H 2 is the enthalpy (measured in Btu) of the refrigerant entering the condenser and H 3 is
the enthalpy of the refrigerant exiting the condenser. The change of enthalpy can be also
obtained by using specific enthalpy or enthalpy per unit mass. The unit of specific enthalpy is
Btu/lbm. The equation will be:
q=h 2−h3 Eqn 3
Where h2 and h3 are the specific enthalpy of the refrigerant entering and exiting the condenser
and q is the heat gained per unit mass.
Since the refrigerant is entering the condenser as a gas, the enthalpy values are obtained in the
superheat tables. The refrigerant exits the condenser as a liquid, and the enthalpy are found in
the saturation chart. Keep in mind that the refrigerant exiting the condenser is liquid and not
vapor. Make sure that the proper value of enthalpy is selected.
The refrigerant mass flow rate must be also taken into account. The refrigerant flow meter is
located on the Hampden Model H-6710 Refrigeration demonstrator. The refrigerant flowmeter
has its own scale and the values must be looked up in Table A-1 excerpted from the Hampden
Model H-6710 Refrigeration demonstrator user manual. When reading the flowmeter, you
must read your value from the middle of the sphere located within the flowmeter.
The effectiveness can be calculated once the data has been obtained. Effectiveness is defined
as:
ε = Actual Heat Loss ¿ Hot Fluid ¿
Maximum Possible Heat Loss By Hot Fluid Eqn 4
The actual heat loss is relatively easy to find, but finding the maximum heat loss can be harder
to find. First, what is the maximum heat loss? The maximum heat loss is the maximum amount
of heat loss by the hot fluid and transferred into the cold fluid. The exit temperature of the hot
fluid can only be as cool as the cold fluid entering the condenser.
For equation 4 to be valid, the enthalpy of the refrigerant at the inlet temperature of the water
must be found which is the lowest enthalpy value that the refrigerant can reach. The maximum
heat loss for the refrigerant will be:
Q=H 2−H max Eqn 5
where Hmax is the enthalpy of the refrigerant at the water inlet temperature.
According to the second law of thermodynamics, heat cannot be transferred from a medium at
a lower temperature to one at a higher temperature without providing mechanical work. The
goal of the heat engine is to absorb thermal energy from a high temperature region and
convert it into work, while releasing heat to a lower temperature region. The heat engine must
obey the second law of thermodynamics. However, the refrigeration cycle is slightly more
complex. The goal of the refrigeration cycle is to remove thermal energy from a lower
temperature region and transfer it to a higher temperature region. The compressor does this
work to make the refrigeration cycle possible.
The refrigeration cycle has four main components: the evaporator, compressor, condenser, and
expansion valve. The schematic of a simple refrigeration cycle is shown in Figure 2.
The purpose of the evaporator is to transfer heat from a higher temperature environment to
the refrigerant. The evaporator will also cause the low-pressure refrigerant to vaporize as heat
is transferred from the evaporator to the refrigerant. From the evaporator the low-pressure
refrigerant gas then goes to the compressor. The compressor will compress the refrigerant
from a low-pressure gas to a high pressure, high temperature gas. Work is done on the
compressor by electrical means in order to achieve pressurization. After the compressor, the
refrigerant then goes through a condenser. The condenser will remove any heat from the
refrigerant, which will cause the gas to liquefy but remain at high pressure. Finally, the
refrigerant will pass through an expander, which will cause the refrigerant to go from being
high pressure to low pressure. This process causes the cooling effect and heat is transferred.
The cycle will then repeat itself.
The effectiveness equation for the evaporator in terms of Figure 2 will be:
h4 −h1
ε= Eqn 7
h4 −hmax
Where h4 is the enthalpy of the refrigerant entering the evaporator, h1 is the enthalpy of the
refrigerant leaving the evaporator, and hmax is the enthalpy of refrigerant at the temperature of
the water in the evaporator.
By finding work of the compressor, heat added, and heat rejected, you can easily calculate the
coefficient of performance, and the coefficient of refrigeration. The coefficient of performance
for a heat pump can be defined as:
Qrej
COPH ¿ Eqn 12
Wk cycle
1. Start the system and allow it to run for 20 minutes with the BV-3 valve closed and the
flow meter fully open so the thermostat controls the water flow rate through the
condenser.
2. Use this time to make sure you understand the system and determine what data you
need to collect to perform the calculations.
3. Collect the data for the thermostatically controlled system.
4. Open the BV-3 valve and adjust the flow meter to a flow rate of 2 gpm (gallons per
minute). Allow the system to stabilize for 5 minutes and collect the data under this
condition.
5. Adjust the flow meter to a flow rate of 1 gpm, allow the system to stabilize for 5 minutes
and collect the data under this condition.
6. Adjust the flow meter to a flow rate of 0.5 gpm, allow the system to stabilize for 5
minutes and collect the data under this condition.
7. Shut down the system as described earlier. Fully open the flow meter and shut off the
water making sure you do not shut off the water for other experiments.
Report
This will be a formal lab report by your entire laboratory group and should include the following
items in addition to the standard text describing what you did and what you learned.
A nicely drawn block diagram of the refrigerant path showing where all of the
measurements were taken.
A plot of the COPR and COPH vs. water flow rate.
A plot of the heat flows vs. flow rate
3. Can a vapor compression refrigeration system operate both as a refrigerator and a heater?