Project Name:
UMM WU'AL PHOSPHATE PROJECT
ITP No. DATE DISCIPLINE:
INSPECTION AND TEST PLAN
ITP FOR MV, LV, CONTROL CABLE EL-ITP-006 2-Feb-17 ELECTRICAL
INSPECTION RESPONSIBILITY
PROJECT PHASE
ITEM ACCEPTANCE Verifying Document & ASSIGNMENTS
& Quality Related Activity Reference REMARKS
NO. CRITERIA Form #
ACTIVITY CODE SBM JACOBS PMC
DOCUMENT
1.0
REVIEW
MD-101-SMEM-EG-EL-SPC-
Ensure All Drawings are issued
1.1
for Construction
0001 Visual Check Approved Drawing R R R
Section 4.5
MD-101-SMEM-EG-EL-SPC-
Ensure Materials Approved Prior Material Approved
1.2
to Installation
0001 Visual Check
Document
R R R
Section 5.2
Cable Termination and MD-101-SMEM-EG-EL-SPC-
1.3 Splicing Special Work 0001 Visual Check Approved MS R R R
Procedure Section 5.9.12
MV Cable Termination and MD-101-SMEM-EG-EL-SPC-
1.4 splice personal Qualification 0001 Review Qualification Certification R R R
Certification Section 5.9.12
MATERIAL
2.0
RECEIVING
Cable Storage, Handling & MD-101-SMEM-EG-EL-SPC-
2.1 Preservation Visual 0001 Visual Check QC-CL-E-017 H W R
Inspection Section 5.3
Cable Reel Material & MD-101-SMEM-EG-EL-SPC-
2.2 Accessories Receiving 0001 Visual Check QC-CL-E-017 H W R
Visual Inspection Section 5.3
Cable Material Receiving MD-101-SMEM-EG-EL-SPC-
QC-CL-E-017 /
2.3 Cable Reel Continuity and 0002 Visual Check / Measure
QC-CL-E-022
H W R
Insulation Testing (MV cable) Section 5.2
Page 1 of 8
ITP No. DATE DISCIPLINE:
INSPECTION AND TEST PLAN
ITP FOR MV, LV, CONTROL CABLE EL-ITP-006 2-Feb-17 ELECTRICAL
INSPECTION RESPONSIBILITY
PROJECT PHASE
ITEM ACCEPTANCE Verifying Document & ASSIGNMENTS
& Quality Related Activity Reference REMARKS
NO. CRITERIA Form #
ACTIVITY CODE SBM JACOBS PMC
Page 2 of 8
ITP No. DATE DISCIPLINE:
INSPECTION AND TEST PLAN
ITP FOR MV, LV, CONTROL CABLE EL-ITP-006 2-Feb-17 ELECTRICAL
INSPECTION RESPONSIBILITY
PROJECT PHASE
ITEM ACCEPTANCE Verifying Document & ASSIGNMENTS
& Quality Related Activity Reference REMARKS
NO. CRITERIA Form #
ACTIVITY CODE SBM JACOBS PMC
MD-101-SMEM-EG-EL-SPC-
Ensure that cable tray /
0001
6.1 conduit installed as per
Section 5.9.5
Visual Check QC-CL-E-018 H W R
drawing or specification
Section 5.9.6
MD-101-SMEM-EG-EL-SPC-
Cable ties are installed as
0001
6.3 per drawing and
Section 5.9.5
Visual Check QC-CL-E-018 H W R
specification
Section 5.9.6
Page 3 of 8
ITP No. DATE DISCIPLINE:
INSPECTION AND TEST PLAN
ITP FOR MV, LV, CONTROL CABLE EL-ITP-006 2-Feb-17 ELECTRICAL
INSPECTION RESPONSIBILITY
PROJECT PHASE
ITEM ACCEPTANCE Verifying Document & ASSIGNMENTS
& Quality Related Activity Reference REMARKS
NO. CRITERIA Form #
ACTIVITY CODE SBM JACOBS PMC
MD-101-SMEM-EG-EL-SPC-
Inspection of cable layout in
7.1
trench
0001 Visual Check QC-CL-E-019 H W R
Section 5.9.8
MD-101-SMEM-EG-EL-SPC-
5KV IR test will be
0002 Measure and Visual
7.2 performed on underground
Section 4.3 Check
QC-CL-E-025 H W R
cables prior to any backfill
Section 4.4.1
MD-101-SMEM-EG-EL-SPC-
Installation of cable marking
7.4
tape / protective tiles
0001 Visual Check QC-CL-E-019 H W R
Section 5.9.8
MD-101-SMEM-EG-EL-SPC-
5KV IR test will be performed to
0002 Measure and Visual
7.5 confirm no damage of cable after
Section 4.3 Check
QC-CL-E-022 H W R
laying/backfilling works
Section 4.4.1
Page 4 of 8
ITP No. DATE DISCIPLINE:
INSPECTION AND TEST PLAN
ITP FOR MV, LV, CONTROL CABLE EL-ITP-006 2-Feb-17 ELECTRICAL
INSPECTION RESPONSIBILITY
PROJECT PHASE
ITEM ACCEPTANCE Verifying Document & ASSIGNMENTS
& Quality Related Activity Reference REMARKS
NO. CRITERIA Form #
ACTIVITY CODE SBM JACOBS PMC
MD-101-SMEM-EG-EL-SPC-
Verify correct cable origin &
8.1
destination point
0001 Visual Check QC-CL-E-020 H H R
Section 5.9.12
MD-101-SMEM-EG-EL-SPC-
Cable glands are of correct
8.2
type & size
0001 Visual Check QC-CL-E-020 H H R
Section 5.9.12
MD-101-SMEM-EG-EL-SPC-
Cables / wires properly
8.3
dressed
0001 Visual Check QC-CL-E-020 H H R
Section 5.9.12
MD-101-SMEM-EG-EL-SPC-
Cable lugs are correct type
8.5
& size
0001 Visual Check QC-CL-E-020 H H R
Section 5.9.12
Page 5 of 8
ITP No. DATE DISCIPLINE:
INSPECTION AND TEST PLAN
ITP FOR MV, LV, CONTROL CABLE EL-ITP-006 2-Feb-17 ELECTRICAL
INSPECTION RESPONSIBILITY
PROJECT PHASE
ITEM ACCEPTANCE Verifying Document & ASSIGNMENTS
& Quality Related Activity Reference REMARKS
NO. CRITERIA Form #
ACTIVITY CODE SBM JACOBS PMC
MD-101-SMEM-EG-EL-SPC-
Check if splicers are trained
9.1
and approved by client
0001 Visual Check QC-CL-E-021 H W R
Section 5.9.12
MD-101-SMEM-EG-EL-SPC-
Check cable set-up prior to
9.2
splice
0001 Visual Check QC-CL-E-021 H W R
Section 5.9.12
MD-101-SMEM-EG-EL-SPC-
Traceability record for every
9.4
splice is provided
0001 Visual Check QC-CL-E-021 H W R
Section 5.9.12
10.0 PRE-COMMISSIONING
MD-101-SMEM-EG-EL-
Visual and mechanical
10.1
check of low voltage cables
SPC-0002 Visual Check QC-CL-E-018 H W R
Section 5.2
MD-101-SMEM-EG-EL-
Phase identification test as Measure and Visual
10.2
required
SPC-0002
Check
QC-CL-E-022 H W R
Section 5.2
Page 6 of 8
ITP No. DATE DISCIPLINE:
INSPECTION AND TEST PLAN
ITP FOR MV, LV, CONTROL CABLE EL-ITP-006 2-Feb-17 ELECTRICAL
INSPECTION RESPONSIBILITY
PROJECT PHASE
ITEM ACCEPTANCE Verifying Document & ASSIGNMENTS
& Quality Related Activity Reference REMARKS
NO. CRITERIA Form #
ACTIVITY CODE SBM JACOBS PMC
MD-101-SMEM-EG-EL-
Measure and Visual
10.3 Insulation resistance test SPC-0002
Check
QC-CL-E-022 H W R
Section 5.2
MD-101-SMEM-EG-EL-
Measure and Visual
10.4 Torque test as required SPC-0002
Check
QC-CL-E-024 H W R
Section 5.2
MD-101-SMEM-EG-EL-
Measure and Visual
10.6 Phase identification test SPC-0002
Check
QC-CL-E-022 H W R
Section 5.2.3
MD-101-SMEM-EG-EL-
Measure and Visual
10.7 Shield continuity test SPC-0002
Check
QC-CL-E-022 H W R
Section 5.2.3
MD-101-SMEM-EG-EL-
Measure and Visual
10.8 Insulation resistance test SPC-0002
Check
QC-CL-E-022 H W R
Section 5.2.3
MD-101-SMEM-EG-EL-
Measure and Visual
10.9 VLF AC Hi-pot test SPC-0002
Check
QC-CL-E-023 H W R
Section 5.2.3
Page 7 of 8
ITP No. DATE DISCIPLINE:
INSPECTION AND TEST PLAN
ITP FOR MV, LV, CONTROL CABLE EL-ITP-006 2-Feb-17 ELECTRICAL
INSPECTION RESPONSIBILITY
PROJECT PHASE
ITEM ACCEPTANCE Verifying Document & ASSIGNMENTS
& Quality Related Activity Reference REMARKS
NO. CRITERIA Form #
ACTIVITY CODE SBM JACOBS PMC
MD-101-SMEM-EG-EL-
Measure and Visual
10.10 Torque test as required SPC-0002
Check
QC-CL-E-024 H W R
Section 5.2.3
LEGEND
W Witness Inspection/Test H Hold Point for QC Inspection or Test RH Review and Approval of Documents
R Review of Documents
GENERAL NOTES
1 Surveillance: QA/QC organization to monitor work in progress without notice from Construction Organization
Witness: QA/QC organization shall be notified of the timing of Inspection or test in advance. However, the inspection or test shall be performed as scheduled if the QA/QC organization representative is not
2 present.
3 Hold: QA/QC organization shall be notified of the timing of inspection or test in advance. Inspection or test shall not be carried out without the QA/QC organization representative in attendance.
4 REVIEW POINT: Is processed through the Reviewing and result of Inspection or test report as a method of Ensuring the Inspection or test is in comfirmity with the Data
Page 8 of 8
ITP No. DATE DISCIPLINE:
INSPECTION AND TEST PLAN
ITP FOR CONDUITS & FITTINGS EL-ITP-007 ELECTRICAL
INSPECTION
PROJECT PHASE RESPONSIBILITY
ITEM ACCEPTANCE Verifying Document &
& Quality Related Activity Reference ASSIGNMENTS REMARKS
NO. CRITERIA Form #
ACTIVITY CODE
SBM JACOBS PMC
DOCUMENT
1.0
REVIEW
MATERIAL
2.0
RECEIVING
Page 1 of 4
ITP No. DATE DISCIPLINE:
INSPECTION AND TEST PLAN
ITP FOR CONDUITS & FITTINGS EL-ITP-007 ELECTRICAL
INSPECTION
PROJECT PHASE RESPONSIBILITY
ITEM ACCEPTANCE Verifying Document &
& Quality Related Activity Reference ASSIGNMENTS REMARKS
NO. CRITERIA Form #
ACTIVITY CODE
SBM JACOBS PMC
MD-101-SMEM-EG-EL-
Conduit & Fittings to
SPC-0001
3.1 conform project
Section 5.8.1
Visual Check QCL-004 or 005 H W W
specification.
Section 5.8.2
MD-101-SMEM-EG-EL-
Check conduit spacing from
SPC-0001
3.2 other utilities
Section 5.8.1
Visual Check QCL-004 or 005 H W W
section 5.8.2
MD-101-SMEM-EG-EL-
Conduit support snd spacing SPC-0001
3.3
as per specification Section 5.8.1
Visual Check QCL-004 or 005 H W W
Section 5.8.2
MD-101-SMEM-EG-EL-
Field bend and radius are SPC-0001
3.4
correct as per specification Section 5.8.1
Visual Check QCL-006 OR 007 H W W
Section 5.8.2
MD-101-SMEM-EG-EL-
Proper fittings installed as
SPC-0001
3.5 per drawings &
Section 5.8.1
Visual Check QCL-006 OR 007 H W W
specifications.
Section 5.8.2
Page 2 of 4
ITP No. DATE DISCIPLINE:
INSPECTION AND TEST PLAN
ITP FOR CONDUITS & FITTINGS EL-ITP-007 ELECTRICAL
INSPECTION
PROJECT PHASE RESPONSIBILITY
ITEM ACCEPTANCE Verifying Document &
& Quality Related Activity Reference ASSIGNMENTS REMARKS
NO. CRITERIA Form #
ACTIVITY CODE
SBM JACOBS PMC
MD-101-SMEM-EG-EL-
SPC-0001
Conduit permanently &
3.6
effectively grounded.
Section 5.8.1 Visual Check QCL-004 or 005 H W W
Section 5.8.2
MD-101-SMEM-EG-EL-
Finall inspection of conduit prior SPC-0001
3.8
to cable pulling / installation Section 5.8.1
Visual Check QCL-004 or 005 H W W
Section 5.8.2
Page 3 of 4
ITP No. DATE DISCIPLINE:
INSPECTION AND TEST PLAN
ITP FOR CONDUITS & FITTINGS EL-ITP-007 ELECTRICAL
INSPECTION
PROJECT PHASE RESPONSIBILITY
ITEM ACCEPTANCE Verifying Document &
& Quality Related Activity Reference ASSIGNMENTS REMARKS
NO. CRITERIA Form #
ACTIVITY CODE
SBM JACOBS PMC
4.0 Pre-Commissioning
LEGEND
W Witness Inspection/Test H Hold Point for QC Inspection or Test RH Review and Approval of Documents
R Review of Documents
GENERAL NOTES
1 Surveillance: QA/QC organization to monitor work in progress without notice from Construction Organization
Witness: QA/QC organization shall be notified of the timing of Inspection or test in advance. However, the inspection or test shall be performed as scheduled if the QA/QC organization representative
2 is not present.
3 Hold: QA/QC organization shall be notified of the timing of inspection or test in advance. Inspection or test shall not be carried out without the QA/QC organization representative in attendance.
4 REVIEW POINT: Is processed through the Reviewing and result of Inspection or test report as a method of Ensuring the Inspection or test is in comfirmity with the Data
Page 4 of 4
ITP No. DATE DISCIPLINE
INSPECTION AND TEST PLAN
ITP- PVC Pipes Sleeves EL-ITP-008 2-Feb-17 ELECTRICAL
INSPECTION
RESPONSIBILITY
ITEM PROJECT PHASE & ACCEPTANCE Verifying Document &
Quality Related Activity Reference ASSIGNMENTS REMARKS
NO. ACTIVITY CODE CRITERIA Form #
SBM JACOBS PMC
DOCUMENT
1.0
REVIEW
MD-101-SMEM-EG-EL-SPC-
Ensure All Drawings are issued
1.1
for Construction
0001 Visual Check Approved Drawing H R R
Section 4.5
MD-101-SMEM-EG-EL-SPC-
Ensure Materials Approved Material Approved
1.2
Prior to Installation
0001 Visual Check
Document
H R R
Section 5.2
MATERIAL
2.0
RECEIVING
MD-101-SMEM-EG-EL-SPC-
Storage, Handling and
2.1
Preservation Visual Inspection
0001 Visual Check QCL-001 H W R
Section 5.3
Manufactured Rigid Heavy Duty
MD-101-SMEM-EG-EL-SPC-
PVC Conduit
2.2
Material Receiving Visual
0001 Visual Check QCL-001 H W R
Section 5.3
Inspection
3.0 INSTALLATION
LEGEND
W Witness Inspection/Test H Hold Point for QC Inspection and Test RH Review and Approval of Documents
R Review of Documents
GENERAL NOTES
1 Surveillance: QA/QC organization to monitor work in progress without notice from Construction Organization
Witness: QA/QC organization shall be notified of the timing of Inspection or test in advance. However, the inspection or test shall be performed as scheduled if the QA/QC organization
2 representative is not present.
Hold: QA/QC organization shall be notified of the timing of inspection or test in advance. Inspection or test shall not be carried out without the QA/QC organization representative in
3 attendance.
4 REVIEW POINT : Is Processed through the Reviewing and Result of Inspection or test report as a method of Ensuring the Inspection or test is in comfirmity with the Data
Page 1 of 1
ITP No. DATE DISCIPLINE:
INSPECTION AND TEST PLAN
ITP FOR OIL AND DRY TYPE DISTRIBUTION TRANSFORMER EL-ITP-009 2-Feb-2017 ELECTRICAL
INSPECTION RESPONSIBILITY
ITEM PROJECT PHASE & ACCEPTANCE Verifying Document & ASSIGNMENTS
Quality Related Activity Reference REMARKS
NO. ACTIVITY CODE CRITERIA Form #
SBM JACOBS PMC
DOCUMENT
1.0
REVIEW
MD-101-SMEM-EG-EL-SPC-
Ensure All Drawings are issued for
1.1
Construction.
0001 Visual Check Approved Drawing R R R
Section 4.5
MD-101-SMEM-EG-EL-SPC-
Ensure Materials Approved Prior to Material Approved
1.2
Installation.
0001 Visual Check
Document
R R R
Section 5.2
MATERIAL
2.0
RECEIVING
MD-101-SMEM-EG-EL-SPC-
Transformer Storage, Handling, and
2.1
Preservation Visual Inspection
0001 Visual Check QC-CL-E-064 H W R
Section 5.3
MD-101-SMEM-EG-EL-SPC-
Transformer Material Receiving Visual
2.2
Inspection
0001 Visual Check QC-CL-E-064 H W R
Section 5.3
MD-101-SMEM-EG-EL-SPC-
Transformer Accessories Material
2.3
Receiving Visual Inspection
0001 Visual Check QC-CL-E-064 H W R
Section 5.3
MD-101-SMEM-EG-EL-SPC-
Check the area are clean and free of
3.1
debris. Ready for installation.
0001 Visual Check QC-CL-E-065 H W R
Section 5.4.1
Check complete assembly for MD-101-SMEM-EG-EL-SPC-
3.2 mechanical damage and missing parts 0001 Visual Check QC-CL-E-066 H W R
as equipment inventory Section 5.5.1
Concrete foundation for MD-101-SMEM-EG-EL-SPC-
3.3 proper level and orientation 0001 Visual Check QC-CL-E-066 H W R
of cables Section 5.5.1
Page 1 of 5
ITP No. DATE DISCIPLINE:
INSPECTION AND TEST PLAN
ITP FOR OIL AND DRY TYPE DISTRIBUTION TRANSFORMER EL-ITP-009 2-Feb-2017 ELECTRICAL
INSPECTION RESPONSIBILITY
ITEM PROJECT PHASE & ACCEPTANCE Verifying Document & ASSIGNMENTS
Quality Related Activity Reference REMARKS
NO. ACTIVITY CODE CRITERIA Form #
SBM JACOBS PMC
Page 2 of 5
ITP No. DATE DISCIPLINE:
INSPECTION AND TEST PLAN
ITP FOR OIL AND DRY TYPE DISTRIBUTION TRANSFORMER EL-ITP-009 2-Feb-2017 ELECTRICAL
INSPECTION RESPONSIBILITY
ITEM PROJECT PHASE & ACCEPTANCE Verifying Document & ASSIGNMENTS
Quality Related Activity Reference REMARKS
NO. ACTIVITY CODE CRITERIA Form #
SBM JACOBS PMC
MD-101-SMEM-EG-EL-SPC-
Check the area are clean and free of
4.1
debris. Ready for installation.
0001 Visual Check QC-CL-E-065 H W R
Section 5.4.1
Dry-type transformers shall be suitable
MD-101-SMEM-EG-EL-SPC-
for indoor or outdoor installation as
4.2
specified on the
0005 Visual Check QC-CL-E-067 H W R
Section 5.5.1
data sheets.
Each transformer shall be fitted with a
nameplate. The name plate shall not be MD-101-SMEM-EG-EL-SPC-
4.3 fixed to any portion of the transformer 0005 Visual Check QC-CL-E-067 H W R
that is required to be removed for Section 5.1.6
maintenance.
All metal parts of each transformer shall
MD-101-SMEM-EG-EL-SPC-
be electrically bonded. Transformer
4.4
shall be connected to the main earth
0005 Visual Check QC-CL-E-067 H W R
Section 5.1.5
grid
All terminals shall be clearly marked to
MD-101-SMEM-EG-EL-SPC-
identify the phase connections in
4.5
accordance with the connection
0005 Visual Check QC-CL-E-067 H W R
Section 5.5.8
diagram on the rating plate.
MD-101-SMEM-EG-EL-SPC-
Identification and warning
4.6
labels installed.
0005 Visual Check QC-CL-E-067 H W R
Section 5.1.6
Page 3 of 5
ITP No. DATE DISCIPLINE:
INSPECTION AND TEST PLAN
ITP FOR OIL AND DRY TYPE DISTRIBUTION TRANSFORMER EL-ITP-009 2-Feb-2017 ELECTRICAL
INSPECTION RESPONSIBILITY
ITEM PROJECT PHASE & ACCEPTANCE Verifying Document & ASSIGNMENTS
Quality Related Activity Reference REMARKS
NO. ACTIVITY CODE CRITERIA Form #
SBM JACOBS PMC
MD-101-SMEM-EG-EL-SPC-
Visual and mechanical 0002
5.1
check of Transformer. Section 5.1
Visual Check QC-CL-E-066 H W R
Section 5.5
MD-101-SMEM-EG-EL-SPC-
Contact resistance
0002 Measure and
5.2 measurement for all bolted
Section 5.1 Visual Check
QC-CL-E-069 H H R
connection.
Section 5.5
MD-101-SMEM-EG-EL-SPC-
Insulation resistance and 0002 Measure and
5.3
polarization index test. Section 5.1 Visual Check
QC-CL-E-068 H H R
Section 5.5
MD-101-SMEM-EG-EL-SPC-
Power factor test on 0002 Measure and Test forms will be submitted at the
5.4
bushing and windings Section 5.1 Visual Check
Vendor Test Form H H R time of testing
Section 5.5
MD-101-SMEM-EG-EL-SPC-
0002 Measure and Test forms will be submitted at the
5.5 Winding resistance test
Section 5.1 Visual Check
Vendor Test Form H H R time of testing
Section 5.5
MD-101-SMEM-EG-EL-SPC-
0002 Measure and Test forms will be submitted at the
5.6 Turn ratio test
Section 5.1 Visual Check
Vendor Test Form H H R time of testing
Section 5.5
Page 4 of 5
ITP No. DATE DISCIPLINE:
INSPECTION AND TEST PLAN
ITP FOR OIL AND DRY TYPE DISTRIBUTION TRANSFORMER EL-ITP-009 2-Feb-2017 ELECTRICAL
INSPECTION RESPONSIBILITY
ITEM PROJECT PHASE & ACCEPTANCE Verifying Document & ASSIGNMENTS
Quality Related Activity Reference REMARKS
NO. ACTIVITY CODE CRITERIA Form #
SBM JACOBS PMC
MD-101-SMEM-EG-EL-SPC-
Over potential test(AC high 0002 Measure and Test forms will be submitted at the
5.7
pot test) Section 5.1 Visual Check
Vendor Test Form H H R time of testing
Section 5.5
MD-101-SMEM-EG-EL-SPC-
0002 Measure and Test forms will be submitted at the
5.8 Oil filtrations
Section 5.1 Visual Check
Vendor Test Form H H R time of testing
Section 5.5
MD-101-SMEM-EG-EL-SPC-
0002 Measure and Test forms will be submitted at the
5.9 Oil sample test
Section 5.1 Visual Check
Vendor Test Form H H R time of testing
Section 5.5
MD-101-SMEM-EG-EL-SPC-
Functional testing of
0002 Measure and Test forms will be submitted at the
5.10 auxiliary wiring and
Section 5.1 Visual Check
Vendor Test Form H H R time of testing
components.
Section 5.5
LEGEND
W Witness Inspection/Test H Hold Point for QC Inspection or Test RH Review and Approval of Documents
R Review of Documents
GENERAL NOTES
1 Surveillance: QA/QC organization to monitor work in progress without notice from Construction Organization
2 Witness: QA/QC organization shall be notified of the timing of Inspection or test in advance. However, the inspection or test shall be performed as scheduled if the QA/QC organization representative is not present.
3 Hold: QA/QC organization shall be notified of the timing of inspection or test in advance. Inspection or test shall not be carried out without the QA/QC organization representative in attendance.
4 REVIEW POINT: Is processed through the Reviewing and result of Inspection or test report as a method of Ensuring the Inspection or test is in comfirmity with the Data
Page 5 of 5
CHECKLIST NUMBER DATE RFI NUMBER
INSPECTION CHECKLIST
LV Power & Control Cables Termination Checklist QC-EL-A-004 2-Feb-17 15KB-64-RFI-000
PROJECT TITLE CONTRACTOR / SUBCONTRACTOR
ITEM RE-INSP
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No. DATE
MD-101-SMEM-EG-EL-
1 The construction drawings and documents is the final edition.
SPC-0001
The cable rating, size, number of core is complying with cable MD-101-SMEM-EG-EL-
2
schedule / connection drawings SPC-0001
The cable tag installed, and the tag description is complying MD-101-SMEM-EG-EL-
3
with termination schedule SPC-0001
The type and size of cable lug is correct. The crimping of lug is MD-101-SMEM-EG-EL-
4
good without loose or crack. SPC-0001
The cable/wires dressing inside terminal chamber is MD-101-SMEM-EG-EL-
5
acceptable. SPC-0001
The terminal block, wire marker and cable number is according MD-101-SMEM-EG-EL-
6
to the connection list and meet specification requirement. SPC-0001
The terminal block, terminal and lug is fastened without loose MD-101-SMEM-EG-EL-
7
and no stress on terminals. SPC-0001
MD-101-SMEM-EG-EL-
8 The entrance of cable is sealed
SPC-0001
Cable gland size & installation is correct and the gland is MD-101-SMEM-EG-EL-
9
bonded with grounding grid. SPC-0001
After termination of cable, Insulation resistance test has been MD-101-SMEM-EG-EL-
10
carried out SPC-0001
All wires are restored after insulation /continuity test and MD-101-SMEM-EG-EL-
11
terminations are tight well SPC-0001
All the cable is fastened and aligned properly where the cable MD-101-SMEM-EG-EL-
12
enters in to the panel or terminal box. SPC-0001
The torque test has been checked and recorded in QC Form # QC-CL-E- MD-101-SMEM-EG-EL-
13
024 as per specification and vendor recommendation. SPC-0001
The surround of work area is kept clean and the inner of panel MD-101-SMEM-EG-EL-
14
is clean. SPC-0001
REMARKS:
Contractor Jacobs
Construction Department
Work is Complete and Ready for Inspection:
QC Supervisor
Quality Record Approved:
Page 1 of 1
CHECKLIST NUMBER DATE RFI NUMBER
INSPECTION CHECKLIST
Dry-type Transformer Installation Checklist QC-EL-A-005
PROJECT TITLE CONTRACTOR / SUBCONTRACTOR
ITEM RE-INSP
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No. DATE
MD-101-SMEM-EG-EL-
1 Check the area clean and ready for installation.
SPC-0001
MD-101-SMEM-EG-EL-
4 Check transformer nameplate against data sheet.
SPC-0002
MD-101-SMEM-EG-EL-
6 Check all cable connection for tightness.
SPC-0002
MD-101-SMEM-EG-EL-
7 Check cable glands for waterproofing.
SPC-0002
MD-101-SMEM-EG-EL-
8 Check terminal box sealed correctly and terminal .
SPC-0002
Check terminal box sealed correctly and clearly marked to identify the
MD-101-SMEM-EG-EL-
9 phase connections in accordance with the connection diagram on the rating
SPC-0002
plate.
MD-101-SMEM-EG-EL-
10 Identification and warning labels installed.
SPC-0002
MD-101-SMEM-EG-EL-
11 Earthing as per detailed drawings.
SPC-0002
MD-101-SMEM-EG-EL-
12 Check earthing connections to main grid.
SPC-0002
MD-101-SMEM-EG-EL-
13 Check transformer are clean, dry and dust-free.
SPC-0002
REMARKS:
Contractor Jacobs
Construction Department
Work is Complete and Ready for Inspection:
Name, Initials and Date:
QC Supervisor
Quality Record Approved:
Name, Sign and Date:
Page 1 of 1
CHECKLIST NUMBER DATE RFI NUMBER
INSPECTION CHECKLIST
Electrical Aboveground Cable Pulling Checklist QC-EL-A-006 2-Feb-17
PROJECT TITLE CONTRACTOR / SUBCONTRACTOR
WITNESS HOLD
ITEM RE-INSP
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No. DATE
MD-101-SMEM-EG-EL-
3 Bend radius correct as per specification and free of deformity
SPC-0001
MD-101-SMEM-EG-EL-
4 Cable support spacing as per drawing and specification
SPC-0001
MD-101-SMEM-EG-EL-
5 Installation neat and evenly spaced
SPC-0001
MD-101-SMEM-EG-EL-
7 Cable ties as per drawing and specification
SPC-0001
Junction boxes size and type are levelled and positioned MD-101-SMEM-EG-EL-
8
correctly as per drawing. SPC-0001
MD-101-SMEM-EG-EL-
9 Verify cable is free of surface damage
SPC-0001
Insulation Test record for all power, control and instrumentation wire MD-101-SMEM-EG-EL-
10
and cables ( QC form # QC-CL-E-022) SPC-0001
MD-101-SMEM-EG-EL-
11 All revisions recorded on "As built" drawing
SPC-0001
REMARKS:
Contractor Jacobs
Construction Department
Work is Complete and Ready for Inspection:
QC Supervisor
Quality Record Approved:
Page 1 of 1
CHECKLIST NUMBER DATE RFI NUMBER
INSPECTION CHECKLIST
Electrical Underground Cable Pulling Checklist QC-EL-A-007
PROJECT TITLE CONTRACTOR / SUBCONTRACTOR
WITNESS HOLD
ITEM RE-INSP
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No. DATE
Inspect, IR test and record all cables on reels before they are MD-101-SMEM-EG-
3
laid in trench EL-SPC-0001
The cable drum has been set up to ensure the cable pulling is in accordance
MD-101-SMEM-EG-
4 with the direction of pull indicated on the drum
EL-SPC-0001
(The lead end of the cable coming from the top of the drum)
Cable Rollers installed as required and additional cable rollers installed at any MD-101-SMEM-EG-
11
change of direction EL-SPC-0001
After cable installation ensure the cable ends are sealed to prevent ingress of MD-101-SMEM-EG-
13
moisture or foreign matter EL-SPC-0001
MD-101-SMEM-EG-
14 All revisions recorded on "As built" drawing
EL-SPC-0001
REMARKS:
Contractor Jacobs
Construction Department
Work is Complete and Ready for Inspection:
Name, Initials and Date:
QC Supervisor
Quality Record Approved:
Page 1 of 1
CHECKLIST NUMBER DATE RFI NUMBER
INSPECTION CHECKLIST
Conduit Checklist - RGS (Above Ground) QC-EL-A-008
PROJECT TITLE CONTRACTOR / SUBCONTRACTOR
WITNESS HOLD
ITEM RE-INSP
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No. DATE
MD-101-SMEM-EG-
10 Seals and drains installed per drawings
EL-SPC-0001
MD-101-SMEM-EG-
11 Conduit permanently and effectively earthed
EL-SPC-0001
Screwed, ABS and PVC-coated conduits installed as per MD-101-SMEM-EG-
12
drawing EL-SPC-0001
PVC insulated steel flexible conduit installed with proper bending MD-101-SMEM-EG-
13
radius and with standard fittings EL-SPC-0001
Junction boxes levelled and supported as per drawing with MD-101-SMEM-EG-
14
proper hubs, locknuts and bushings installed EL-SPC-0001
Installation in accordance with specification, referenced code MD-101-SMEM-EG-
15
and standards EL-SPC-0001
MD-101-SMEM-EG-
16 Relative deficiencies list closed out
EL-SPC-0001
REMARKS:
Contractor Jacobs
Construction Department
Work is Complete and Ready for Inspection:
Name, Initials and Date:
QC Supervisor
Quality Record Approved:
Name, Sign and Date:
Page 1 of 1
CHECKLIST NUMBER DATE RFI NUMBER
INSPECTION CHECKLIST
Conduit Checklist (Under Ground) QC-EL-A-009
PROJECT TITLE CONTRACTOR / SUBCONTRACTOR
ITEM RE-INSP
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No. DATE
Trenching checked for location, elevation and level, and it is free MD-101-SMEM-EG-
1
of debris EL-SPC-0001
Trench location, elevation, depth, form and conduit size conform MD-101-SMEM-EG-
2
to drawing EL-SPC-0001
MD-101-SMEM-EG-
3 Dimensions checked for cable protection conduit
EL-SPC-0001
Conduit field bend radius is correct as per drawing. Check that MD-101-SMEM-EG-
4
bends are free of any defect, as per specification. EL-SPC-0001
MD-101-SMEM-EG-
5 Trenching checked for interference with underground piping
EL-SPC-0001
MD-101-SMEM-EG-
6 Conduit seals are installed on all exposed concrete pouring pipe ends
EL-SPC-0001
Road crossings for installation of spare sleeves as called for on MD-101-SMEM-EG-
7
drawing. These spare pipes shall have caps on the ends EL-SPC-0001
After concrete is in place, conduits checked for free of damage or MD-101-SMEM-EG-
8
deformation. EL-SPC-0001
MD-101-SMEM-EG-
9 Backfill work and compaction test performer as per specification
EL-SPC-0001
MD-101-SMEM-EG-
10 Pipe ends filled with specified sealant (after cable installation)
EL-SPC-0001
MD-101-SMEM-EG-
11 Installation of cable sleeve, Cable marker under roadways
EL-SPC-0001
MD-101-SMEM-EG-
12 All revisions recorded on "As built" drawing
EL-SPC-0001
MD-101-SMEM-EG-
13 Relative deficiencies list closed-out
EL-SPC-0001
REMARKS:
Contractor Jacobs
Construction Department
Work is Complete and Ready for Inspection:
Name, Initials and Date:
QC Supervisor
Quality Record Approved:
Name, Sign and Date:
Page 1 of 1