Installation Instructions

Split Inverter Type


Room Air Conditioner
Environmental
Before installing the Cooling Type Series Protection
air conditioner, read
this instruction Indoor Units Outdoor Units
manual thoroughly RAS-08HT RAC-08HTP
and keep it well for RAS-10HT RAC-10HTP
reference in the RAS-15HT RAC-15HTP 【Contents】
future. RAS-19HT RAC-19HTP
RAS-24HT RAC-24HTP Installation Notices ....... 1
Indoor Units Installation
Instructions .................. 6
Outdoor Units Installation
Instructions ................ 11

Installation Notices

(Failure to observe the following items may cause serious consequences or


Caution damage to the objects)
 Dealers must explain in details the operations to their customers according to this manual.
damages to the objects)
 Wireless remote controller and parts are packed in the packing box supplied with the indoor unit.
 Before installing, check if the power supply and circuitry are normal and make sure the voltage is within ±10% of the
voltage rating.
 The distance of in the installation diagram is to ensure space for the air conditioner’s performance. For
convenience of service and maintenance in the future, install the air conditioner in the place with sufficient space in
the vicinity.
 Care should be taken in cutting, extension and bending of the refrigerant piping and not to break the pipes.
As this air conditioner uses new recyclable refrigerant, ”R410A” be sure to follow three principles - keeping
the refrigeration system dry, clean, and air tight, when installing the refrigerant piping.

Warning (Failure to observe the following items may cause injury or death)
(Failure to observe the following items may cause injury or death)
 Installation of air conditioner and electrical wiring must be handled by authorized installer only, do not attempt to handle
them by yourselves (Handling charges are additional.)
 Before installing, read the installation instructions thoroughly and correctly.
 Use only those specified accessories when installing, otherwise, it may cause the unit body to fall, water leakage, current
leakage and fire, etc.
 When discharging, refrigerant is required during installation, be sure to use an air vent and air breather, as refrigerant will
produce toxic gas once it mixes with hot air.
 When performing wiring work, be sure to follow the electrical codes and installation instructions, and also be sure to use the
power loops exclusively for the air conditioner.
 When installing or moving the units, the refrigeration system (piping) must not mix with refrigerant R22 or air, except
refrigerant R410A. If air is mixed in, the system capacity will reduce, causing abnormal high pressure in the refrigeration
system that may lead to copper tube breaking and failure to occur.

1
Earth wire and earth leakage circuit breaker.
To prevent current leakage:
 To avoid carelessness from power companies or other accidents that cause over current to get into the unit via the earth
wire resulting in damage to the unit, be sure to install a circuit breaker. Refer to the dealers (the qualified technicians) for
details.
 To prevent electric shock in case of current leakage, the outdoor unit must be connected with an earth wire with wire
specification of 2.5mm2 to 6mm2.
(When hooking up the earth wire, the installer must first handle the end tip of the wire. After crimping the wire with a ring
terminal, make sure to screw down the earth wire tightly to complete grounding at the place marked with a grounding
sign near the access panel combination or the valve base combination.)
 When installing near places with high humidity such as bathing facilities, damp, humid places, basements, and places
with frequent water accumulation, be sure to install a circuit breakers preventing leakage. Refer to the dealers (the
qualified technicians) for details.

NOTICE
1. To ensure your safety, this product must not be used in the highly humid areas such as laundry room and bathroom,
etc.
2. The earth wire must not be connected to the following positions:
 Water pipes: If there is a plastic pipe in the pipelines, do not connect the earth wire to the pipeline.
 Gas pipes: There is risk of explosion after ignited.
 Ungrounded neutral lines in the electrical circuit panel, earth wires of the telephone line and lightning rods, etc, which
may have large amount of current flowing through tending to cause danger when lightning strikes or by other factors.

Selection of installation locations (Confirm the location before installation)


Indoor
units
 The units must be installed at the places where sufficient Installation dimensions of outdoor units(mm)
supports are available, vibration-free, firm and stable places.
Models A B C D E
 There are no heat sources, fumes in the vicinity and no barriers RAC-08HTP
around the air outlet. RAC-10HTP 554 335 148 45 279
 There should have some clearance in the distance as indicated RAC-15HTP
by in the diagram ( page 4) on the top, left and right RAC-19HTP 509 335 214 100 237
sides of the unit. RAC-24HTP 530 335 287 175 245
 Places where it is convenient for the unit to drain water and to
connect piping of the outdoor units
 To avoid noise effect, keep the unit and the remote controller
1m or above away from TV and radio, etc.
 To avoid errors in the remote controller; keep the controller
away from high frequency machines and wireless machines
with high power output.
 Make sure the pullout direction of the pipes:
There are four pullout d ra in hos e
directions for the pipes -
straight backward,
downward, leftward and Pulling
Pulling
rightward
B

rightward. Pulling straight


leftward
E

Pulling
Outdoor downward

Units D
 Pulling
Do not install the unit at the places easy to expose rain or
rightward A C
Pulling downward
direct sunlight, but at the places where there are frequent
airflows.
 The airflow must not face directly to animals and plants.
 On the top, left, right, front and rear sides of the unit, there
must leave clearance in the distance as indicated in the
diagram ( page4). At least two sides should be open,
where one side is for the outflow.
【 TheContent
outflow air and noises must not annoy neighbors.
 The units must not be installed at the places where flammable
】 vapor, dust and fumes are available.
sgas,
 The drain hose must be kept unclogged.
 Installation
The outdoor units must be installed at the places capable of
.......................
sustaining heavy
Notices 1 the noise and vibration will
weight, otherwise,
be amplified, tending to cause the unit to fall or personal injury.
Indoor
Units
Installation 2
Instructions.................. 5
Wiring diagram
Powe r s up p ly NOTICE
Sing le Pha s e
 Do not use the connection wires together with the
Ind oor Unit 220V Outd oor unit
Ea rth Wire same cable for the power supply wire to prevent
signal interference that may cause errors.
C D L N C D
Bla c k
White

Bla c k
White
Conne c tion Wire
Be s ure to us e 1.25mm2 The c olor of c onne c tion wire s
s tra nd e d wire + fla t b e twe e n the ind oor a nd outd oor
ins ula tion te rmina l units mus t ma tc h a nd mus t not
b e mixe d d uring ins ta lla tion

3
Wiring diagram

Required tools for installation


 Screw driver
 Tape measure
 Knife
 Saw
 Ø65, Ø5mm Drill bit
 Allen wrench (diameter, 5mm)
 Adjustable wrench and torque wrench
 R134a (R410A) Gas leakage tester or soapsuds
 Tubing cutter
 Flaring tools (for R410A only)
 Adhesive-free tape
 Pliers
 Vacuum pump (for R410A only)
 Electronic scale

Electric specification

Gas Liquid Connection Wires Power supply wire


Models Fuse Capacity
pipe pipe Specification Specification

RAS-08HT / RAC-08HTP
Ø 9.53 Ø 2.0mm Single-core 10A
RAS-10HT / RAC-10HTP
1.25mm2 Stranded Wire Hard Wire
RAS-15HT / RAC-15HTP Ø 6.35
Ø 12.7 + Blade terminal or 15A
RAS-19HT / RAC-19HTP 3.5mm2 Stranded Wire
RAS-24HT / RAC-24HTP Ø 15.88 20A

4
Installation diagrams for the indoor and outdoor units
This ins ta lla tion d ia g ra m is inte nd e d for re fe re nc e only. the ind oor a nd outd oor units mus t b e b a s e d on
a c tua l mod e l of the unit.(This d ia g ra m is for mod e l of RAS-08HT/RAC-08HTP)

 Be sure to use new refrigerant pipe for piping(replace the


Ac c e s s orie s for ind oor unit R22 used pipe with new pipe, recycling the old R22 pipe
Ite m Pa rt na me Qua ntity Ite m Pa rt na me Qua ntity after cleaning is prohibited)
 Pipe size to be adopted for installation shall be as per
1 Ins ta lla tion p la te 1 6 Re mote c ontrolle r 1 specified specification, pipes with different size with the
2 Sp e c ia l s c re w 6 7 Ba tte ry(AAA 1.5V) 2 indoor unit is prohibited for piping.
 It is required for unit installation that two open installation
3 Loc king tie wra p 3 8 Sc re w (Φ4X16) 2 faces are reserved with one of them for unit air outlet.
4
Re mote c ontrolle r 1 Sc re w hole p lug 2  Installation distance between the indoor unit and other
hold e r 9
Wood s c re w appliances, such as the fluorescent lamp, television, radio
5 (Φ4X16) 2 10 Bla d e te rmina l 4 and so on, shall be above 1 meter to prevent the signal
Ac c e s s orie s for outd oor unit interference.

Ite m Pa rt na me Qua ntity


a Dra in e lb ow 1

b LN te rmina l s c re w 2 Ab ove 50mm

Ma ximum e le va tion b e twe e n


ind oor a nd outd oor units
Ab ove 100mm
Ma ximum Be s ure
Mod e ls e le va tion(m)
to s e a l
RAS-08HT / RAC-08HTP Ab ove 100mm
15 a ny g a p
RAS-10HT / RAC-10HTP with p utty
RAS-10HT / RAC-15HTP
RAS-19HT / RAC-19HTP 20
450mm

RAS-24HT / RAC-24HTP
Tie wra p s for p ip e s (for
p ulling the p ip e horizonta lly)
Ap p rox 300mm
No b e nd ing
De s ig ne d p ip e le ng th:5m

Ad he s ive fre e ta p e Pip ing s hould b e wra p p e d with


ins ula tion ma te ria ls re g a rd le s s
of s ma ll tub e s or la rg e tub e s .
Wra p p ip ing s urfa c e with
a d he s ive fre e ra p e from ind oor
Ab ove 500mm s id e to outd oor s id e (top to
b ottom). If the y a re not wound ,
Ab ove 200mm ins ula tion ma te ria ls will b e
d e g ra d e d p re ma ture ly.

J oints of d ra in hos e with


ins ula tion ma te ria ls .
Inne r d ia me te r is Φ16mm

Us e d ra in hos e wra p p e d with


ns ula tion ma te ria ls for the
p ortion of horizonta lly p ulle d
p ip ing tha t p a s s throug h ind oor.
(Op tiona l ite ms )
Ab ove 200mm
Ab ove 300mm
Note : Whe n e le va tion b e twe e n the
Ab ove 500mm ind oor a nd outd oor units is more
Mount an “S” tha n 10 me te rs a nd the ind oor
shape at every10 unit is loc a te d lowe r tha n the
Dra in e lb ow meters outd oor unit, the re frg e ra ting oil
(fitte d on the unit b ottom ) will ha ve d iffic ulty flowing b a c k. It
is ne c e s s a ry to mount a n "S"
s ha p e in e xte nd e d p ip ing a t e ve ry
10M maximum 10 me te rs of e le va tion, a s s hown
in the b e low d ia g ra m.

5
Handling condensate from the outdoor unit Maximum allowable hight of tilt for the indoor and outdoor u n i t

Not hig he r tha n a


Mod e ls a (mm)
Above 70mm RAS-08HT
RAS-10HT 7
RAS-15HT
RAS-19HT 10
RAS-24HT

Not hig he r tha n a


Hanging Press in
first

 The outdoor unit base is provided NOTICE


with a drain hole for condensed
water. The condensed water drain tray for the indoor unit can be fitted
 To drain condensed water by using from the left or right side. Hence, the installation plate must be
the drain hole, lift the unit about kept in a Series when fixing it, or the side fitted with the drain line
70mm or more above the ground, must be slightly tilted downward. Otherwise, the condensed
and then fit the drain elbow as water may spill out.
shown in the above diagram.
Screw it tight in clockwise direction
at an angle about 40∘.
 Install the outdoor unit on Series.
Check that the condensed water
can drain normally.
 The drainpipe (VP16) should be
.

supplied locally.

Indoor Units Installation Instructions

Removal of access panel of the indoor unit

Step 1:
Remove the fixing screws of the
screw cover beneath the unit
and the access panel.
螺絲遮蓋
Screw cover
Fixing screw dig輕摳此處可拆下
here slightly to remove Step 2:
固定螺絲
Support the access panel under
the base with two hands and
apply pressure inward on the
“ ” of two sides, until the
hook inside the access panel is
released from the base.
(A clear sound of “da” can be
heard when the hook is
released.)
Step 3:
After the hooks on both sides are
released, the access panel
beneath the unit can be removed
downward with both hands. After
the access panel is removed,
there has more space for wiring
and piping work.
服務蓋
Access panel

6
Assembly of access panel of the indoor unit

Step 1:
Align the round fixing axis with the rectangular hole below the
base, and insert it all the way upward.
Step 2:
Align the hooks on both sides with the guiding slots on the
base and push slightly upward from the bottom of the access
panel until the base engages in the access panel and the
surfaces are flush. (A clear “da” sound can be heard when the
hook is engaged.)
Step 3:
服務蓋
Access panel Tighten the fixing screw that fixes the access panel to the
bottom of the unit.
Step 4:
Press the screw cover into the access panel.

底座
Base

螺絲遮蓋
Screw cover 螺絲
Screw

Additional fixing to the installation ①Installation


安裝架 plate
plate and the base

Note: To let the indoor unit attach closely to the wall, the base and
the installation plate can be tightened and secured by using
the item screw after piping work is completed, and then
assembly the access panel.

1 Fitting the installation plate


 Secure the installation plate by using the intermediate post  Installation procedure for fitting the installation plate on
between walls. the wall.
1. Drilling on the wall. 2. Aligning with the
Ins ta lla tion p la te hole on the
Sp e c ia l s c re w Le ve l installation plate.
Ins ta lla tion p la te

Wa ll
Φ5mm

Knoc k in or
Sp e c ia l
Ins c rip tion s c re w in s c re w
Pip ing hole
Thre a d Plumme t
Secure it with 4 or
more special Wa ll
screws
 When fitting the installation plate, the figures printed on the 3. Secure the installation plate on the wall by
bottom of the packaging carton of the unit can be used to using Item  special screws.
position.

Contour of the s ha p e of the ind oor unit Ce iling


unit : mm
Md ole s a b Ab ove 70mm
Series RAS-08HT
08~15 RAS-10HT
82 88
RAS-15HT 93 88
RAS-19HT 88 88
RAS-24HT
a b

Sp e c ia l s c re w
Series (The d ia g ra m is a n ins ta nc e of RAS-20NF)
RAS-08HT)
19、24

a b

7
2 Drilling the wall and fitting the tube guard
 When drilling a hole of Outdoor
Indoor side
side NOTICE
Ø65mm in diameter,
keep the outdoor side When connecting the
slightly downward and wires, do not let the wires
drill it with a small slope. come in touch with the
 Cut the tube guard metal grids inside the wall;
based on the thickness In addition, if the wires run
of the wall to be installed. through a hollow wall,
Putty
there is risk of being bitten
 The clearance of pipe Tube guard Wall Pipe plug
by rats and causes
plugs must be sealed danger. Be sure to use the
completely to prevent tube guard.
rain from penetrating
indoor.

3 Preparation for installing the indoor unit

 To pull down the pipes directly:


1. Remove the access panel, then pull
out the connection wires and joint Connection wire,
them. pipes and drain
2. Pull out the pipes, connection wires hose must be
secured using a
and the drain hose. tape.

 To pull the pipes horizontally, replace and


fit the drain hose and drain cap as shown
below. In addition, the drain hose must be
inserted all the way in.

 Turn and remove the drain cap by using a


plier (this method is easier to remove the
cap) as shown in the right diagram.

Drain cap

Drain hose

Pull it out from access panel

 To pull the pipes leftward or


rightward and downward, use tools
NOTICE
such as a saw to cut and remove
the plugs or access panel as  The drain cap and drain hose must be inserted
shown below and then trim the completely, or the condensed water may spill over.
burr.

Drain hose
Drain cap

Insert it to Insert it to
Plug here here
Plug

AcAccess
c e s s p a ne l
Plug
Plug panel

8
4 Installation of the indoor unit
A. To install the indoor unit after jointing the
refrigerant lines:
NOTICE
 The junction of pipes must be wrapped with When wrapping too
insulation materials for fittings. forcibly the insulation
 Connect the power lines. material for fitting by a
 After arranging the connection wires and pipes, tape, the insulation
place them in the space at the bottom of indoor effect will reduce and
unit and secure them with tie wraps. causes condensation. Pipe Wrapping too
 The insulation pipes must be wound by tape at forcibly with a tape
every 120mm.

Insulation material for fittings Insulation pipe Tie wrap

B. To install the indoor unit before jointing


the refrigerant pipes:
 Refrigerant lines and connection wires must be
tied together.
The front end of the refrigerant pipe must be
 For the length of the refrigerant lines to be positioned at the location inscribed with marks.
reserved, refer to the right diagram.
 For the length of connection wires to be
reserved, refer to the table below.

Modleless
Mod LL
RAS-08HT
RAS-08HT
RAS-10HT
70
70
RAS-10HT
RAS-15HT
RAS-14HT 95
95 ( L cm )
(The diagram is an instance of RAS-08HT)
RAS-19HT
RAS-19HT (圖像以RAS/RAC-20級機種為例)
RAS-24HT
RAS-24HT
110
110

C. Installation
 Hang the indoor unit onto the installation plate.
 Keep the bottom of the inside unit moving forward about 15 Installation
安裝板
plate Tie wrap
配管固定束帶
cm by using the tie wrap on the back of indoor unit to support
against the wall.
 Remove the access panel at the bottom of the indoor unit.
 Insert the drain hose in the hole on the wall. 固定勾
Hook
 After pipes are jointed, the junctions should be wrapped with
insulation materials for fittings.
 Jointing connection wires.
 After arranging the connection wires and pipes, place them in
the space at the bottom of indoor unit and secure them with Pawl
固定爪 服務蓋 panel
Access
tie wraps. About約15c
15cmm
 The pawl at the bottom of indoor unit must securely engage
the hook of the installation plate.
 Finally replace the access panel on the unit.
Insulation
管接頭隔熱材 material When jointing a pipe, it
配管接續時,需向前
for fittings must be pulled forward
拉出,配管才容易。
to make piping easier.

排水管
Drain hose

Tube保護管
guard
Connection
wire連接電線 Pipe
配管
接續部
Junction
連接電線
Connection wire
配管固定板
Tip wrap
D. Draining precautions
 The drain hose  The drain  The front end of  The front end  When pulling
must not point hose must not the drain hose of the drain horizontally, the front
up. be bent in must not be hose must not end of drain hose must
waves. dipped in water. point up. not be higher.

排水溝
Ditch 積水
Water sump
積水 sump
Water 積水sump
Water 前端
Front end

9
5 Jointing pipes
Remove the cap nut. After tightening with wrench, slightly rotating
(Helium in the indoor unit will be backward and tighten with torque wrench. For small
discharged) diameter pipes, to avoid screwing too tightly, use a
torque wrench.

Don’t screw all the


hsiu way in a sudden,
but screw slowly
until they are tight.

Piping of indoor unit Flare nut


When jointing pipes, align the pipes
with hands and screw them to the [Tightening torque]
N
end. 外徑(Φ)
Outer
diameter(Φ) 扭力(kgf-cm)
Torque (kgf-cm)
O
 Care should
(Before jointing, apply some 細徑側
Liquid diameter
pipes 6.35(1/4") 140~190
refrigerating oil at the flare opening.) T when
be taken
粗徑側
Gas diameter
pipes 9.53(3/8") 350~450
I the
bending
粗徑側
Gas diameter
pipes 12.7(1/2") 450~550
pipes.
C
粗徑側
Gas diameter
pipes 15.88(5/8") 500~600
[Tighten to the end with hands] E

6 Jointing of connection wires and securing method


Run the connection wire from the back of unit to
Stripped length of the connection wire.
the front.
stranded wire
Lift up the panel.(See page 4 in the user manual Inner covering

for instructions)
After removing the screws fixing the electric
access panel, lift up the electric access panel 6mm 30mm
and joint the connection wires.
Use Φ1.25mm stranded wire + flat insulation Outer covering

terminal to connect the connection wires. The screw must be


The flat insulation terminal after inserted in the tightened to secure
terminal board, it must be secured by tightening the connection
fixed the flat insulation
wire.
terminal
the screw. Make sure that each wire is secured
and will not be pulled out; otherwise, the
terminal board may be burned out resulting in
the unit incapable of working, as shown in the CD terminal
right diagram. board Connection
(Insert securely)
wire
10 Fla t ins ula tion te rma ina l

6mm (s trip p e d le ng th) NOTICE


Stra nd e d wire
 Be sure to use the power loop exclusively for
the air conditioner only.
Se c ure with c rimp ing tools
 For installation method of the connection
wires, refer to technical reference related to
To remove the
electric facilities.
connection  Before energizing the connection wires
wires, between the indoor and outdoor units, the
unscrew the
screws. earth wire of the outdoor unit must first be
earthed. Conversely, the connection wire
between the indoor and outdoor units should
18mm

first be removed before the outdoor earth


Flat insulation wire is removed.
terminal  Do not use the same cable for the connection
Covering wires and the power supply wire to prevent
signal interference that can cause errors.

10
● Outdoor unit
● installation instructions
● ●

L NC D L NC D

C D L N
Jointing the connection wires and
1 D power supply wires
the For the fitting method of the connection wires, refer to the
C
N technical reference related to the electric facilities,
L
 For handling of the junction of the connection wires, refer to the instructions of indoor units. (Refer to the
diagrams below for the scheme after jointed)
 For specifications of the power supply wire and the connection wires, refer to the specification specified in the
table of “Electric specification” on Page 3.
 Description of the jointing method:
Remove the upper cover (for RAC-08HTP~10HTP) or electric access panel (for RAC-15~24HTP) or service
cap. Us e s tra nd e d wire of
Joint each wire as specified in the diagram. 5.5mm a s p owe r
Replace the upper cover or the electric access panel or service cap and valve cap. s up p ly wire

●˙RAC-22~ 36級
RAC-08~10HTP ● ˙RAC-40~ 50級 ●
RAC-15~19HTP ˙RAC-63級
RAC-24HTP
● ●

LN CD LN C D
The
螺絲確實 screws must
L N C DC D C D LN be tightened
C D C D L N 鎖緊固定 L N C DC D LNCD C D CD
securely

The screws must


Connection 螺絲確實
The screws must
螺絲確實 連接電線
wire be tightened
鎖緊固定
(N0.1) (N0.2)

be tightened securely
鎖緊固定
securely 電源線supply
Power
wire

Power supply 接地線


Earth wire
接地線
Earth wire
電源線
wire Power supply
連接電線 wire
Connection 電源線
wire
接地線 連接電線
Connection
Earth wire
wire

● C D CD C D C D

The screw must be


螺絲須確實鎖緊
tightened securely
b

 Instructions of power line(LN terminal board)tip handling and slicing.

12mm
LN terminalLN端子台
board 電源線
Power supply wire
When using single-core hard wires.
使用單芯硬線時,不需使用圓形端子
no ring terminals are required.

The screw must be


tightened to secure
the connection 10 Fla t ins ula tion te rma ina l
fixed the flat insulation
wire.
terminal 6mm (s trip p e d le ng th)
Stra nd e d wire
15mm
 Instructions CD
of splicing
terminal the connection wires(CD terminal board)
Se c ure with c rimp ing tools
board Connection
(Insert securely)
wire

NOTICE
● Wire attachment must be firmly secure, poor tightening or misconnection is contributable to burn-down of the circuit board.
● Use stranded wire of 2.5~6.0mm2 as the earth wire and the wire must be crimped with a ring terminal before attached to
the earth wire screw. The screw must be tightened securely without loosening.

11
2 Preparing the pipes
Thickness of copper pipes for general refrigerant pipes.
● The pressure of refrigerant R410A is higher than
Nominal outer Standard outer Thickness of copper
that of R22, and thus the thickness of copper
diameter (inch) diameter (mm) tube (mm)
pipes must comply with that shown in the right
table. The copper pipe of 0.7 mm thickness Ø1/4 Ø6.35 0.8
available on the market must not be used. Ø3/8 Ø9.52 0.8
 Cutting and flaring operation of copper tubes 。 Ø1/2 Ø12.7 0.8
Use pipe cutter to cut the copper pipe Ø5/8 Ø15.88 1.0
perpendicularly.
Rotate to right
Before flaming the pipe with a flaming tool, do not forget
Pipe cutter to feed the to fit a flare nut.
knife.
Tighten the pipe
Copper pipe cutter to cut the
Tighten the pipe Handle copper pipe
Flaring tool
cutter to cut the
copper pipe
Screw gripper

When deburring the copper pipe, point Flare nut


down to the pipe to avoid copper chips Copper pipe
coming in the pipe. 【Size of overhang (Strictly observe the size of overhang to
Deburring tool of copper pipe】 avoid leakage.)

A (mm)
Ensure that the
inside of copper Outer diameter(Ø) Tool for R410A Tool for R22
tube has no
scratches. 6.35(1/4") 0~0.5 1.0
9.53(3/8") 0~0.5 1.0
Perform the pipe flaring. 12.7(1/2") 0~0.5 1.0
Check the pipe flares. Poor flaring Press
15.88(5/8") 0~0.5 1.0
will cause leakage when they are die
Copper pipe
jointed.
 Example of poor flaring:
Scratches

Incomplete deburring Copper chips scratch the inside Under flaring Over flaring Cracking

3 Precautions for refrigerant piping Cap and plastic bag Rain enters
Pipe the pipe
Burr
Tying with a rubber
Deburring tool band

Copper chips and copper


powder come in the pipe

Foreign matters and


water enters
Indoor Sealed
Outdoor
Outdoor

Outdoor
Indoor
Sealed Indoor

Rubber band Cap and Wall


plastic
Sand enters the
Cap and plastic pipe
Foreign Tying with a
Without Ground matters and
touching water enters rubber band
Ground
the ground

4 Jointing the pipes


Notice: Before jointing the pipes, apply some refrigerating oil at the flare opening
to ensure no leakage from the joint.

Remove the After tightening with a wrench, slightly screw [Tightening torque]
flare nut. backward and then tighten it using the torque Outer diameter
(Ø) Torque (kgf-cm)
wrench.
Align and Liquid diameter 6.35(1/4") 140~190
Do not tighten all
tighten the the way in a Gas diameter 9.53(3/8") 350~450
pipe end with [ Screw all the way sudden, but screw
down with hand] ]
slowly and tight it
Gas diameter 12.7(1/2") 450~550
hand.
Gas diameter 15.88(5/8") 500~600

12
5 Vacuum Operation
 As the outdoor unit contains
refrigerant without leakage, to NOTICE
maximize the unit’s performance, be sure to Be sure to use the vacuum pump
use the following vacuum pump method to exclusively for R410A or install an oil
vacuum the system after piping work of the check valve (solenoid valve) to prevent
indoor and outdoor units is finished. unidentified refrigerating oil from entering in
 When vacuuming, it is not necessary to run the unit, resulting in damage to parts and
the units. failure to the unit. Strictly observe this!
 Before trial run, do not turn on the power to ● Using the refrigerant left in the unit is
the air conditioner. prohibited be sure to use the composite
pressure gauge and refigerant charging
hose exclusively for R410A. Composite
pressure gauge
-0.1Mpa
 Using the vacuum pump method
Connect the vacuum pump with a Knob Switch Lo
composite pressure gauge as shown in the Knob Switch Hi
right diagram. Discharge vent
It closes when the knob at Hi position, it fully Charging hose
opens when the knob at Lo position. Ball valve switch
Startup the vacuum pump. Charging
Pump check
hose
Now loosen the flare nut of the service valve valve
on the small tube side and make sure air is
sucked in, if yes, tighten the flare nut Flare nut
immediately. Service valve
Keep the pump working for 10 to 15 (Liquid pipe)
minutes. When the composite pressure Vacuum pump
gauge indicates -0.1MPa (-76cmHg), fully
Flare nut
close the knob Lo.
Stop the vacuum pump.
Remove the valve cap and fully open the
spindles of the service valves of the small
and large tube sides by turning the Allen
wrench in the counterclockwise direction.
Then, remove the charging tube and tighten Service valve
the valve cap and service valve nut by the (Gas pipe)
Ball valve
tool such as a wrench. switch

NOTICE
 When fitting the check valve, ensure that
the arrow on the check valve points to the
vacuum pump.
 When power outage happens during
vacuuming, open the discharge vent of the
composite pressure gauge to let it reach
normal pressure. Then, tighten the vent to
re-do vacuuming.
Service service
Allen
六角 服務閥
valve 閥心帽
valve nut
wrench
扳手
 Service valve operating precautions Valve閥頭帽
cap
Screw the spindle until it clutches, excess
force will cause failure.
Valve
閥頭帽 cap
Tightening torques for the valve head nut and
the valve core nut are shown in the right table.
[Tightening torque]
Valve cap 200~250kgf-cm
Valve cap 125~160kgf-cm
 Check gas leakage
Use soap suds or “gas leakage tester
R134a(R410A)” to check if refrigerant leaks from
the joint of the flare nut, if yes, tighten the nut to
avoid leakage. Wipe off the soap suds after
check.

13
6 Test run and other precautions
1 Test run check 4 Refrigerant recharging
 After installation, check the piping, wiring, length Length of Recharge
of connection wires and power supply wire pipes refrigerant Maximum
inserted in the terminal board and their polarities

Types
without when the piping
(or signs) are correct. Models necessity pipeline is length
 This product will absorb the noises produced by of refilling extended (m)
static electric charge, be sure to connect the refrigerant (g/m)
earth wire.
 To avoid current leakage, be sure to install a RAC-08HTP 10 20

Single split
“high sensitivity, high speed earth leakage circuit RAC-10HTP
(for inverter).” No longer
RAC-15HTP than 10m 10
2 Test run RAC-19HTP 20 30
 After installation, check the piping, wiring, length RAC-24HTP 15
of connection wires and power supply wire
inserted in the terminal board and their polarities  As R410A is mixed refrigerant, if charged in gas
(or signs) are correct. phase the components of refrigerant will alter,
 This product will absorb the noises produced by which will affect normal working of the system. So,
static electric charge, be sure to connect the be sure to charge refrigerant in liquid phase.
earth wire.  Verify indications on the refrigerant cylinder. If the
 To avoid current leakage, be sure to install a refrigerant cylinder does not contain a siphon, the
“high sensitivity, high speed earth leakage circuit cylinder must be positioned up side down; if it con-
(for inverter).” tains a siphon, the cylinder must be positioned
upright.
 To ensure a correct refrigerant recharging quan-
3 Installation of a remote controller holder tity, use an electronic scale.
 The remote controller can be attached to the 5 Maintenance operation
wall, column or table by using the remote
controller holder.
 If the remote controller is to be operated on the  When refrigerant recycle or outdoor-unit-only
operation is carried out, please turn off the breaker
holder, make sure that the unit can receive the
firstly, then open the switch and wait 1 minute at
signals sent from the position of remote
least, and then press the service switch for 1
controller before determining the position to be
second at least on the main PCB of the outdoor
installed. The unit will react with a “beep” sound
unit to start the unit operation.
when receiving a signal. The signals can be
attenuated due to the fluorescent tube, so when  Press the service switch again for 1 second at least
determining the position of installation, even if it to stop unit operation.
is daytime, the light must be turned on.  After unit stoppage, please turn off the breaker, and
 Attach the remote controller with wood screws then turn on it again to return to the normal state
at the suitable position. (Do not attach it to the mode.
places where it can expose to direct sunlight  To protect the compressor, please do not operate
and places where strong heat can generate) the unit for more than 5 minutes when the service
 Insert the remote controller in it's holder. (As valve is closed.
indicated by the arrow in the diagram)
NOTICE
Re mote c onntrolle r
 Maintenance operation is for professional repair-
men use only, users are prohibited to operate it.

 Please do not operate the unit with the service


Re move
valve closed for more than 5 minutes to prevent
the unit malfunction.
Ins e rt

Re mote c ontrolle r Plug


hold e r
Φ6.5mm

Wood s c re w

30mm
Wa ll
Drilling on the wa ll

14
~ ~ MEMO ~ ~

15
~ ~ MEMO ~ ~

16
14
66MP1385 RA-AE-K
17