MODELS
Ceiling-mounted Cassette type (Multi flow model)
FCQ18PVJU
FCQ24PVJU English
FCQ30PVJU
Français
1 English
English 2
(12) Small
• Operation manual 3. SELECTING INSTALLATION SITE
Please attach additional thermal insulation material to the unit
body when it is believed that the relative humidity in the ceiling
(11) Medium
exceeds 80%. Use glass wool, polyethylene foam, or similar
with a thickness of 3/8 in.. or more as thermal insulation mate-
2-2 OPTIONAL ACCESSORIES rial.
• The optional decoration panel and remote controller are (1) Select an installation site where the following conditions
required for this indoor unit. are fulfilled and that meets with your customer’s approval.
• In the upper space (including the back of the ceiling) of the
Table 1
indoor unit where there is no possible dripping of water
Optional decoration panel from the refrigerant pipe, drain pipe, water pipe, etc.
Model
Color White • Where optimum air distribution can be ensured.
FCQ18 · 24 · 30PVJU BYC125K-W1 • Where nothing blocks the air passage.
3 English
NOTE
26 3/4 (Suspension bolt pitch)
• Install the indoor and outdoor units, power supply wire and
connecting wires at least 3.5ft. away from televisions or 33 1/16 (Indoor unit)
radios in order to prevent image interference or noise. 34 5/8 (Ceiling opening)
(Depending on the radio waves, a distance of 3.5ft. may not 37 3/8 (Decoration panel)
be sufficient enough to eliminate the noise.)
A
(5 15/16)
before installing the unit. False [View as seen from A]
ceiling
(Installation pitch is marked on the paper pattern for (length: in.)
installation. Refer to it to check for points requiring rein-
forcing.) Installation is possible when ceiling opening dimensions is
[Space required for installation] as follows.
• When installing the unit within the frame for fixing false
ceiling.
H
35 13/16
35 13/16
(Dimension inside frame) (length: in.)
English 4
1 15/16 -
3 15/16
Frame Long nut or turn-buckle
Suspension bolt
False
ceiling False ceiling
NOTE) All the above parts are field supplied.
13/16 or more 33 13/16-*35 13/16 13/16 or more
(length: in.)
(Ceiling opening dimension) (Ceiling-panel
overlapping
dimension)
5 English
Insulation
Center of ceiling opening
Approx. 3/8
(length: in.)
Make sure the inner surface of insulation tightly contacts
with the inner insulation edge and the side plate.
Paper pattern for
Fig. 2 installation (5)
(accessory)
Screw (6)
Screw (6)
6. INDOOR UNIT INSTALLATION (accessory)
(accessory)
Installing optional accessories (except for the decoration
panel) before installing the indoor unit is easier. However, 〈Ceiling work〉
for existing ceilings, install fresh air inlet component kit (3) Adjust the unit to the right position for installation.
and branch duct before installing the unit. (Refer to “PREPARATIONS BEFORE INSTALLA-
TION-(1)”.) (Page 4)
(1) Install the indoor unit temporarily.
(4) Check the unit is horizontally level.
• Attach the hanger bracket to the suspension bolt. Be
• The indoor unit is equipped with a built-in drain
sure to fix it securely by using a nut and washer from
pump and float switch. At each of the unit’s 4 cor-
the upper and lower sides of the hanger bracket.
ners, verify that it is level by using a water-level or a
The washer fixing plate (7) will prevent the washer from
water-filled vinyl tube.
falling.
(If the unit is inclined against condensate flow, the
Part to be procured in the field float switch may malfunction and cause water to
Washer (3) (accessory) drip.)
(5) Remove the washer fixing plate (7) used for preventing the
washer from falling and tighten the upper nut.
Hanger bracket
(6) Remove the paper pattern for installation (5).
Tighten
(double nut)
Water level
English 6
Table 3
Pipe Flare Clamp (4) ×4
Tightening torque
size dimensions Flare shape (in.) (accessory) Insulation for
(ft.lbf)
(in.) A (in.) fitting (9) (accessory)
R0.016- (for liquid line)
φ 3/8
0
24.1-29.4 0.504-0.520
45 ±2
0
90 ±2
A
0
(accessory)
φ 5/8 45.6-55.6 0.760-0.776 (for gas line)
Liquid pipe Gas pipe
7 English
3/16 or less
ing.
• If the drain pipe cannot be sufficiently set on a slope, ex- Drain raising pipe
Clamp metal (2) (accessory)
ecute the drain raising pipe. Rise
• To keep the drain pipe from sagging, space hanging wires Drain hose (1) (accessory)
every 3.28 ~ 4.92ft. (length: in.)
English 8
29 1/2 or less
2 15/16
or less 208V–230V
Indoor unit
PC board Single phase
(length: in.) power supply
Control box lid (1) Power supply
Select converging drain pipe whose gauge is suitable for terminal block
the operating capacity of the unit. Control box lid (2)
• Drain pipe connections
Do not connect the drain pipe directly to sewage pipes that
smell of ammonia. The ammonia in the sewage might enter
9. ELECTRIC WIRING WORK
the indoor unit through the drain pipe and corrode the heat
exchanger.
• Keep in mind that it will become the cause of getting drain
9-1 GENERAL INSTRUCTIONS
pipe blocked if water collects on drain pipe. • All field supplied parts and materials, electric works must
conform to local codes.
(2) After piping work is finished, check if drainage flows • Use copper wire only.
smoothly. • Follow the “WIRING DIAGRAM” attached to the unit body to
• Open the water inlet lid, add approximately 37 in³ of wire the outdoor unit, indoor unit and the remote controller.
water slowly and check drainage flow. For details on hooking up the remote controller, refer to the
“INSTALLATION MANUAL OF REMOTE CONTROLLER”.
WHEN ELECTRIC WIRING WORK IS FINISHED • All wires must be performed by an authorized electrician.
• Check drainage flow during COOL running, explained under • A circuit breaker capable of shutting down the power supply
“TEST OPERATION”. to the entire system must be installed.
• Be sure to ground the air conditioner.
WHEN ELECTRIC WIRING WORK IS NOT FINISHED
• Remove the control box lids, connect a power supply wire and DANGER
remote controller wire to the terminals.
(Refer to the “HOW TO CONNECT WIRES” (Page 10)) • Do not ground units to water pipes, telephone wires or
Next, press the INSPECTION/TEST OPERATION button lightning rods because incomplete grounding could cause a
“ ” on the remote controller. The unit will engage the test severe shock hazard resulting in severe injury or death, and
operation mode. Press the OPERATION MODE SELECTOR to gas pipes because a gas leak could result in an explo-
button “ ” until selecting FAN SPEED CONTROL button sion which could lead to severe injury or death.
“ ”. Then, press the ON/OFF button “ ”. The indoor unit
fan and drain pump will start up. Check that the water has 9-2 ELECTRICAL CHARACTERISTICS
drained from the unit. Press “ ” to go back to the first mode.
Power
The water inlet lid Units Fan motor
supply
Drain pipe
Voltage
Portable pump Model Hz Volts MCA MFA W FLA
range
FCQ18PVJU 1.3 15 90 1.0
Inspection 208- Max. 253
opening FCQ24PVJU 60 1.3 15 90 1.0
230V Min. 187
FCQ30PVJU 1.3 15 90 1.0
MCA: Min. Circuit Amps (A) MFA: Max. Fuse Amps (A)
Bucket KW: Fan Motor Rated Output (kW) FLA: Full Load Amps (A)
(Adding water from
inspection opening)
Service condensate outlet
3 15/16 or more (with rubber plug)
(Use this outlet to condensate
Plastic watering can from the drain pan)
(Tube should be about
3 15/16 long.) (length: in.)
Adding water through air discharge outlet ®
[Method of adding water]
9 English
Transmission
terminal block (6P) Wiring diagram Control box lid (2)
Control box lid (1)
English 10
protection.
Indoor unit
4. Outside of the unit, keep transmission wire at least 5 in.
away from power supply wire. The equipment may malfunc- P1 P2 P1 P2
MAIN/SUB CHANGEOVER
(1) Insert a screw driver into the recess between the upper
and lower part of remote controller and, working from the
2 positions, pry off the upper part.
The remote controller PC board is attached to the upper
part of remote controller.
Indoor unit Upper part of
Remote controller remote controller
Lower part of
Insert the screwdriver here and remote controller
gently work off the upper part of
remote controller
11 English
(3) How to select FORCED OFF and ON/OFF OPERATION 〈When using wireless remote controllers〉
• Turn the power on and then use the remote controller to • When using wireless remote controllers, wireless remote
select operation. controller address setting is necessary. Refer to the installa-
tion manual attached to the wireless remote controller for
10-5 CENTRALIZED CONTROL setting instructions.
• For centralized control, it is necessary to designate the
group No. For details, refer to the manual of each optional
controllers for centralized control. 12. INSTALLATION OF THE DECORATION
PANEL
Refer to the installation manual attached to the decoration
panel.
After installing the decoration panel, ensure that there is no
space between the unit body and decoration panel.
English 12
13 English
English 14