Professional Documents
Culture Documents
EX-proof Posters A4 Final
EX-proof Posters A4 Final
at glance
IG
substances (e.g. gas or dust) can form
NI
explosive atmospheres, which can be ignited by
T
N
IO
GE
N
ignition source (e.g. sparks or heat).
SO
OX
UR
CE
Oxygen and flammable substances are difficult or
impossible to remove from the environment, but
FLAMMABLE SUBSTANCE
typically ignition sources can be avoided.
Regional:
• ATEX, mandatory in European Union, but a lso widely accepted globally
• CSA, applicable to United States and Canada
• EAC Ex, for Eurasian Economic Union
Local:
• INMETRO for Brazil
• CCC for China
• UKCA Ex for Great Britain
• etc.
Konecranes Ex-proof info posters 3/2021 rev1.
Ex-proof equipment
Compatibility charts
Temperature
Customer area Suitable Gas or Dust group Suitable Suitable
classification in
classification equipment classification equipment equipment
Gas environment
Zone 0 Zone 0 IIC IIC T6 (85°C) T6
Zone 1 Zone 0 or Zone 1 IIB IIC or IIB T5 (100°C) T6 or T5
Zone 2 Zone 0, Zone 1 or Zone 2 IIA IIC, IIB or IIA T4 (135°C) T6, T5 or T4
Zone 20 Zone 20 IIIC IIIC T3 (200°C) T6, T5, T4 or T3
Zone 21 Zone 20 or Zone 21 IIIB IIIC or IIIB T2 (300°C) T6, T5, T4, T3 or T2
Zone 22 Zone 20, Zone 21 or Zone 22 IIIA IIIC, IIIB or IIIA T1 (450°C) T6, T5, T4, T3, T2 or T1
Examples of Konecranes
Examples of customer request
offering
Zone 2 IIA T1 Zone 2 IIB T3 Konecranes group does not provide
Zone 2 IIB T4 Zone 1 IIB T4 equipment to Zones 0 or 20
Zone 1 IIC T6 N/A
Zone 22 IIIA T225°C Zone 22 IIIC T120°C
Zone 21 IIIB T320°C Zone 21 IIIC T120°C
Equipment Equipment
Substance Presence of substance Zone
category protection level
Continuously or for long periods or frequently 0 1G Ga
Likely to occur in normal operation occasionally 1 2G Gb
Gas
Not likely to occur in normal operation but, if it
2 3G Gc
does occur, will persist for a short period only
Continuously or for long periods or frequently 20 1D Da
Likely to occur in normal operation occasionally 21 2D Db
Dust
Not likely to occur in normal operation but, if it
22 3D Dc
does occur, will persist for a short period only
II 2G Ex h IIC T4 Gb
Explosion
protection symbol
Maximum
surface temperature
Equipment group Prefix for Dust: Gas:
I: Underground equipment (mines) protection Actual T1: 450°C
II: Above ground equipment concept(s) temperature T2: 300°C
value T3: 200°C
e.g. T120°C T4: 135°C
T5: 100°C
T6: 85°C
Protection concept*
Description
[protection levels]
Common marking for all non-electrical
h GAS group Typical Gas
equipment protection concepts
c Constructional safety IIA Propane
d [da, db, dc] Flameproof enclosure IIB Ethylene
e [eb, ec] Increased safety IIC Hydrogen
i [ia, ib, ic] Intrinsic safety Or
nA Non-sparking DUST group Hazardous substances
m [ma, mb, mc] Encapsulation
Combustible volatile
IIIA
o [ob, oc] Liquid immersion substances
t [ta, tb, tc] Protection by enclosure IIIB Non-conductive dusts
*Not all possible protection concepts are listed IIIC Conductive dusts
Konecranes Ex-proof info posters 3/2021 rev1.