300

25 MM FLOORING OVER 75 MM ANCHOR BOLTS


BASE CONC.
300 1200 300 1200
10 50
150 GL GL 80
80
16 MM Ø BARS 6 NOS. 16 MM Ø BARS 9 NOS. EACH 4800 1200 1800 50
X' X1
EACH INNER FACE OUTER FACE
8 MM TIES @ 300 MM C/C
1140 A1 SAND FILLING A1
's' 300
12 MM Ø BAR 32 NOS. EACH WAYS 40 110 80 80 50
12 MM Ø BAR 19 NOS.
EACH WAYS
1800
310
150
300 300 300 300
4800 DETAILS AT ''S''
50 MM CONC. COVER
(SHOWING POSITION OF ANCHOR BOLTS)
75
C:C 1:4:8 WITH 40 MM STONE
BALLAST
PLAN
4800 (ATMS TYPE GANTRY FDN.)
SECTION AT X' - X1
12 MM Ø BARS 32 NOS. EACH WAYS
12 MM Ø BARS 19 NOS. EACH WAYS 8 MM TIES @ 300 MM C/C
16 MM Ø BARS 9 NOS. (EACH OUTER FACE)
16 MM Ø BARS 6 NOS. EACH INNER FACE
300 40MM CONC. COVER
NOTES-
1:-ALL DIMENSIONS ARE IN MM.
1200 2:-FIGURED DIMENSIONS TO BE FOLLOWED.
4800 4800
3:-MEDIUM STRENGTH RIBBED TOR BARS CONFORMING TO I:S:
1786 SHALL BE USED IN FRUSTUM AND CHIMNEY.
4:-CONCRETE IN FRUSTUM AND CHIMNEY SHALL BE (1:1.5:3)
5:-CLEAR CONC.COVER IN CHIMNEY AND FRUSTUM SHALL BE 40
MM AND 50 MM RESPECTIVELY.
300 40MM CONC. COVER
6:-ANCHOR BOLTS SHALL BE GROUTED DURING CASTING ITSELF.
300 1200 300
7:-MIN.EXCAVATION SHALL BE1.00 M FROM NGL
8:-PCC SHALL BE IN 1:4:8 IN STONE BALLAST
4800 4800
SECTION AT A1 - A1 PROJECT:- 132 /33 KV SUBSTATION,RANIGANJ,PRATAPGARH
BOTTOM REINFORCEMENT TOP REINFORCEMENT
CLIENT: UTTAR PRADESH POWER TRANSMISSION CORPORATION LTD.
CONTRACTOR:
PRIME
GROUP
TITLE- OPEN TYPE FOUNDATION FOR DRY SOIL FOR GANTRY ATMS
SUB DIVISION OFFICER EXECUTIVE ENGINEER
(UPPTCL) (UPPTCL)
DATE REV. SHT.
DRG.NO: 01/UPPTCL/RANIGANJ/PRATAPGARH
......... 00 00