Ø150 FIRE WATER PIPE H/L@PCL=FF

E2
12000
E1
SHOP DRAWING
PROJECT TITLE

G ADDIS ABABA BOLE INTERNATIONAL AIRPORT


MATCHLINE REFER FW/01-02 OWNER
STAFF
ACCESS
STAFF ENTRY TURNSTILES
730 SECURITY CHECK

9000
9000
Ø150 FW PIPE T/A
FIRE
COMMAND GATE VALVE
CENTRE
FIRE
HC
ESCAPE

F ETHIOPIAN AIRPORT ENTERPRISE


FIREMAN
ACCESS/
FIRE ESCAPE
ST7 CONTRACTOR
Ø200 FIRE WATER PIPE TO CV ROOM
SEE SPK LAYOUT FOR REFERNCE
FIRE TO/FROM
ESCAPE BASEMENT PIPE DROP
ONLY

9000
9000

@PCL=FFL+2900
LIFT 7

PIPE DROP
(STAFF LIFT) CHINA COMMUNICATIONS CONSTRUCTION COMPANY (LTD)
Ø150 FW PIPE
T/A & T/B TO HOSE STATION CHECKED BY DU ZHI QIANG
(TO BASEMENT STAIR HALF E

998
LANDING LEVEL) APPROVED BY SHI LIN Charles
FIRE
GATE VALVE

UTILITY ROOM
ESCAPE
ONLY
ENGINEER

@PCL=FFL+3650
FIRE DEPARTMENT CONNECTION
@PCL=FFL+2850

FAN ROOM
FOR SPRINKLER RISER
4525
REMOTE BUS PARKING

9000
9000
2773 @PCL=FFL+3375
Ø200 SLUICE VALVE CHAMBER ELECT

Ø100 FIRE WATER PIPE H/L@PCL=FFL+3650


EXTERNAL DIMENSION 1050mm X 1005mm DATA
(TYP.)
851
NEW Ø200MM 3293
UNDERGROUND FIRE WATER PIPE Aéroports de Paris
(DUCTILE IRON)
CHECK BY
FIRE DEPARTMENT CONNECTION M (PUBLIC)
D
FOR STAND PIPE
C RM
5069
PR

9000
TD
FOR ENGINEER

UTILITY
INV

ROOM
APPROVAL BY

9000
F (PUBLIC)

1418
HC
C
ST B7 FOR ENGINEER

PRINCIPAL CONSULTANT

9000
9000
1 GATEWAY DRIVE, #21-01
WESTGATE TOWER
SINGAPORE 608531
TEL: 65 65475080 FAX: 65 65420406

PROJECT DIRECTOR LEE NGAI HUNG


CONSULTANT KHIN MAUNG LIN
2500 HIGH
FRESH AIR SHAFT
2500 HIGH
EXHAUST AIR SHAFT B
PRINCIPAL MECHANICAL ENGINEER GOH LAY TIN

BUS WAITING LOUNGE DESIGN REPRESENTATIVE

9000
9000
ARRIVAL BUS PICK-UP STAND

1500
D 2017-12-22 ISSUED FOR APPROVAL
C 2017-11-22 ISSUED FOR APPROVAL
B 2016-11-27 ISSUED FOR APPROVAL
A 2015-02-10 ISSUED FOR APPROVAL
REV. DATE DESCRIPTION
- This shop drawing is approved subject to approval of coordination drawing and mock-up installation.
- Submit control room detail drawings .
- Submit schematic and riser diagram. 12000
CP05
- Any additional/new items due to difference between construction drawing rev. B and rev. E1 ( this shop FH MECHANICAL,ELECTRICAL,FIRE,P&S
drawing) required Employer/Engineer approval.Refer letter ADPI/CCCC/EAE/OP/1611, dated Nov.
KEY PLAN
03,2017.
- Approval of this shop drawing will not relief the contractor/designer from their responsibilities and
obligations.
MESFIN ALEMU
17/01/2017 N

MAIN TERMINAL T1

01-01 01-02 01-03 01-04 01-05 01-06

Provide/indicate Information of the following: 01-07 01-08 01-09 01-10 01-11 01-12
- All lowest portions shall be provided with drain, end of cross mains shall be provided
also with drain valve as required in the construction drawings.
- Indicate directional Flow. 01-13 01-14
- Submit systems schematic diagram.
- Automatic air vent locations.
MATCHLINE REFER FW/01-07

MATCHLINE REFER FW/01-09


- Flexible connection within building expansion joints and other locations. JOB TITLE :
- Calculation of loads for sizing and details of sway bracing and branch line restraint. DEVELOPMENT OF ADDIS ABABA BOLE INTERNATIONAL AIRPORT
ETHIOPIA, AFRICA
- Complete legend and notes
- Fire extinguisher locations
TERMINAL 2 EXPANSION
DRAWING NO : REV.
DE MESA Dennis JINGOLD/M&E/BOLE/ME/FC/01-08 D
15/01/2018 DRAWING TITLE :

FIRE STAND PIPE AND HOSE SYSTEM


- GROUND FLOOR (GRIDS A-G/E1-E2)

SIGN BAR

NOTES LEGEND Design Basis DRAWN BY SURAJ KUMAR


1. ALL DIMENSIONS IN THIS DRAWING ARE IN MILLIMETERS, ELEVATIONS ARE IN MILIMETERS. FW FIRE WATER FIRE HOSE VALVE 1. THE FIRE STANDPIPE AND HOSE SYSTEM IS DESIGNED BASED ON NFPA 14. CHECKED BY XIA HAIBO
2. ABOVE GROUND FIRE WATER PIPES AND FITTINGS FOR WET STANDPIPE SYSTEM ARE GALVANIZED STEEL. SP STANDPIPE ABOVE GROUND FIRE WATER PIPE 2. FOR THE FIRE HOSE CONNECTION A MINIMUM RESIDUAL PRESSURE OF 6.9 BAR AT THE
3. MECHANICAL GROOVE COUPLING WILL BE USED FOR PIPE Ø50 AND LARGER, AND THREAD JOINT CONNECTION HC HOSE CABINET UNDERGROUND FIRE WATER PIPE OUTLET OF THE HYDRAULICALLY MOST REMOTE HOSE STATION SHALL BE PROVIDED. APPROVED BY LI DEJUN
WILL BE USED FOR HOSE CONNECTION. FFL FLOOR FINISHED LEVEL 3. ALL FIRE HOSE VALVES IN THE STAIR SPACE ARE Ø65 MM IN SIZE.
4. PIPE HANGERS MAXIMUM HORIZONTAL SPACE OF SPRINKLER SYSTEM SHALL FOLLOW NFPA 13 SECTION 9, TABLE 9.2.2.1. MECHANICAL
SFL STRUCTURE FLOOR LEVEL
5. PIPE CLAMPS SHALL BE PROVIDED FOR PIPE DROPS TO HOSE STATIONS AND STANDPIPE. PCL PIPE CENTER LEVEL STRUCTURAL
6. SEE THE FIRE PROTECTION SYSTEM INSTALLATION DRAWING FOR MORE DETAIL. IL INVERT LEVEL
7. SEE THE EXTERNAL DRAWINGS FOR THE UNDERGROUND SYSTEM. H/L HIGH LEVEL ELECTRICAL
L/L LOW LEVEL ARCHITECTURAL
RED. CONCENTRIC REDUCER
ISOLATION VALVE SCALE: 1:200