Mounting and Installation

Wiring
!Connector pin assignment and circuit diagram
•Connector pin assignment
Configuration Pin
Signal name
BUS IN BUS OUT number
1 DRAIN
2 V+
3 V-
4 CAN_H

 5 CAN_L
: If you are concerned about disruption of “downstream” device whilst replacing the SI unit, use a DeviceNet™ tap rather than
marking connections to the BUS OUT connector.

•Circuit diagram
The product has T branching internally in the unit as shown in the circuit diagram below.
It can be extended by connecting the DeviceNet™ slave with BUS OUT.

"Precautions for handling


•Be sure to fit a seal cap on any unused connectors. Proper use of the seal cap enables the
enclosure to achieve IP67 specification.
•Please connect the terminator with both ends of the DeviceNet trunk line.