Professional Documents
Culture Documents
NTZ Danfoss
NTZ Danfoss
NTZ Danfoss
Reciprocating
Compressors
NTZ
R404A/R507A
Low temperature refrigeration RECIPROCATING COMPRESSORS
CONTENTS
SPECIFICATIONS ......................................................................................................................................................................................................................................... 5
Technical specifications and nominal ratings .................................................................................................................... 5
Approvals and certificates ............................................................................................................................................................................................... 5
Operating envelope ..................................................................................................................................................................................................................... 5
RECIPROCATING COMPRESSORS
MANEUROP® RECIPROCATING COMPRESSORS
Features The Maneurop® NTZ series from A liquid injection system is not re-
Danfoss Commercial Compressors quired. All components are of high
is a range of hermetic reciprocating quality and precision to assure a long
compressors for low evaporating tem- product life.
perature applications. These compres- NTZ compressors have a large internal
sors gradually replace the existing LTZ free volume that helps to reduce the
range. risk of liquid hammering. The electri-
The NTZ series is engineered as a true cal motor is fully suction gas cooled
low temperature compressor, opti- which means that no additional body
mised at –35°C with an extended cooling is required and it allows the
evaporating temperature range from compressor to be insulated with an
–45°C up to –10°C. The compressors acoustic hood when the installation
can be operated at a return gas tem- requirements call for extra low sound
perature (suction gas temperature) characteristics.
of 20°C even at low evaporating
temperatures.
indicating
Compressor reference
(indicated on the compressor NT Z 048 A 4 L R1 A
nameplate)
NT: New low A: Evolution index,
temperature indicating
reciprocating compressor
compressors modifications
Z: Polyolester lubricant R1: Equipment version
(R1: Rotolock connections,
oil equalisation connection
and sight glass)
048: Displacement in cm3 / rev. L: Motor protection
(L: Internal Motor Protection)
A: UL index indicator 4: Motor voltage code
(see table page 4)
3
RECIPROCATING COMPRESSORS
INTRODUCTION
Code numbers The code numbers for NTZ compres- At the publication date of this do-
sors are according to the standard cument NTZ compressors are only
(for ordering)
Danfoss numbering system. Below available with motor voltage code 4.
tables list the code numbers for NTZ For other motor voltage codes, please
compressors in single packs and check the availability.
industrial packs.
Packaging
Single pack* Multi pack** Industrial pack***
Compressor
model
Net weight Dimensions Net weight Dimensions Static Net weight Dimensions Static
Qty Qty
(kg) (mm) (kg) (mm) stacking (kg) (mm) stacking
4
RECIPROCATING COMPRESSORS
SPECIFICATIONS
Approvals Maneurop® NTZ compressors comply Certificates are listed on the product
with the following approvals and cer- datasheets:
and certificates tificates http://www.danfoss.com/odsg
CE
All models
(European Directive)
UL
Models with motor voltage code 4
(Underwriters Laboratories)
Gost
All models
certificate (for Russia)
Operating envelope
R404A / R507A 65
60
S.H. = 10 K
1 & 4 cyl
Condensing temperature (°C)
55
50
RGT 20
45 S.H. = 10 K
2 cyl
40
35
30
25
-50 -45 -40 -35 -30 -25 -20 -15 -10 -5
Evaporating temperature (°C)
5
RECIPROCATING COMPRESSORS
OUTLINE DRAWINGS
1 cylinder
ø 224
Suction rotolock
1"1/4
Schrader
1/4"
333
263
Discharge rotolock
Oil equalisation 1"
3/8"
98
68 68
25
109 118
37°
35°
Threaded oil
sight glass
68
39
Silent block HM8-40
Suction 147
Discharge 142
141 123
23
15
17
159
17°
NTZ048
1”1/4 1” 5/8” 1/2” V09 V06
NTZ068
6
RECIPROCATING COMPRESSORS
OUTLINE DRAWINGS
2 cylinders
ø 288
Suction rotolock
Schrader 1"3/4
1/4"
413
Discharge rotolock
1"1/4
252
265
Oil equalisation
3/8"
PTC
98
crankcase heater
74 68
32
Threaded oil 82
sight glass
60 156
8°
171
145 Suction 179
38° Discharge 176 Silent block HM8-40
21
125
8° 23
15
96
188
NTZ096
1”3/4 1”1/4 7/8” 3/4” V07 V04
NTZ108
7
RECIPROCATING COMPRESSORS
OUTLINE DRAWINGS
4 cylinders
ø 352
Suction rotolock
1"3/4
158
125
99 95
Threaded oil
sight glass 96
232 H M12-50
15°
246
15°
205
30
19
15
246
NTZ215
1”3/4 1”1/4 1"1/8” 3/4” V02 V04
NTZ271
8
RECIPROCATING COMPRESSORS
ELECTRICAL CONNECTIONS AND WIRING
Voltage application range Motor voltage code Nominal voltage Voltage application range
1 208-230 V / 1 / 60 Hz 187 – 253 V
3 200-230 V / 3 / 60 Hz 180 – 253 V
400 V / 3 / 50 Hz 360 – 440 V (50 Hz)
4
460 V / 3 / 60 Hz 414 – 506 V (60Hz)
5 230 V / 1 / 50 Hz 207 – 253 V
6 230 V / 3 / 50 Hz 207 – 253 V
500 V / 3 / 50 Hz 450 – 550 V (50 Hz)
7
575 V / 3 / 60 Hz 517 – 632 V (60 Hz)
9 380 V / 3 / 60 Hz 342 – 418 V
Electrical connections
Spade connectors
1/4” AMP-AWE
Earth M4-12
Models:
NTZ048 - NTZ068 - NTZ096 - Knock-out
NTZ108 - NTZ136 Ø 21 mm
Screw
10-32 UNF x 9,5
Ø 29 mm
Earth M4-12
Knock-out
Models: Ø 29 mm
NTZ215 - NTZ271
9
RECIPROCATING COMPRESSORS
ELECTRICAL CONNECTIONS AND WIRING
Three phase motor Three phase compressors are inter- current overload and locked rotor
nally protected by a temperature / conditions. If the motor were to be
protection and current-sensing bimetallic protector, overloaded and the protector trips, all
suggested wiring connected to the neutral point of 3-phases are cut out. It might take up
diagram the star-connected stator windings. to several hours to reset and restart
This internal overload line break pro- the compressor.
tects the motor against overheating,
L1
L2
L3
FU
FU
MS
TH
C1
Single phase electrical Single phase electrical characteristics available at the publication date of
and capacitor and relay data are not this document.
characteristics
Single phase motor Single phase compressor motors are The standard CSR wiring system pro-
internally protected by a temperature vides additional motor torque at start-
protection and / current-sensing bimetallic protector up, by the use of a start capacitor in
suggested wiring which senses the main and start win- combination with a run capacitor.
diagram ding current as well as motor winding The start capacitor is only connected
temperature. If the motor were to be during the starting operation and a
overloaded and the protector trips, it potential relay disconnects it after the
might take up to several hours to reset start sequence. This sytem can be used
and restart the compressor. for refrigerant circuits with capillary
tubes or expansion valves.
5
220 kΩ - 1 W C
IOL
2
"A + C"
IOL Motor protector S R
1
A+C Run capacitors
B Start capacitor
B µF
C Common
S Start winding (auxiliary)
R Run winding (main) 15 kΩ - 1 W
Capacitors A and C are replaced by a single ca-
pacitor of size A + C
10
RECIPROCATING COMPRESSORS
REFRIGERANTS AND LUBRICANTS
R404A 0.7
Recommended
11
RECIPROCATING COMPRESSORS
SYSTEM DESIGN RECOMMENDATIONS
Suction line Horizontal suction line sections shall U-trap is required at the foot of each
have a slope of 0.5% in the direction vertical riser. If the riser is higher than
of refrigerant flow (5 mm per meter). 4 m, additional U-traps are required for
The cross-section of horizontal suction each additional 4 meters.The length of
lines shall be such that the resulting each U-trap must be as short as pos-
gas velocity is at least 4 m/s. In vertical sible to avoid the accumulation of
risers, a gas velocity of 8 to 12 m/s is excessive quantities of oil (see figure
required to ensure proper oil return. A below).
To condenser
0.5 % slope,
4 m/s or more
max. 4 m
U-trap
8 to 12 m/s
max. 4 m
0.5 % slope, Evaporator
4 m/s or more
12
RECIPROCATING COMPRESSORS
SYSTEM DESIGN RECOMMENDATIONS
Gas velocities higher than 12 m/s will Danfoss as accessories, are designed
not contribute to significantly better for average pipe sizes, selected for sys-
oil return. However they will cause hi- tems running at nominal conditions.
gher noise levels and result in higher The pipe sizes selected for specific
suction line pressure drops which will systems may differ from these average
have a negative effect on the system sizes.
capacity. Note that the suction roto- The suction line must always be insu-
lock valves, which can be ordered from lated to limit suction gas superheat.
condenser
Discharge line When the condenser is mounted abo- compressor are required to prevent li-
ve the compressor, a loop above the quid draining from the condenser into
condenser and a U-trap close to the the discharge line during standstill.
ssible
porator
U-trap
Oil charge and oil separator In most installations the initial com- oil return such as in multiple evapora-
pressor oil charge will be sufficient. In tor or multiple condenser installations,
installations with line runs exceeding an oil separator is recommended. Also
20 m, or with many oil traps or an oil refer to the section "Oil charge and oil
separator, additional oil may be requi- level".
red. In installations with the risk of slow
Filter driers For new installations with NTZ com- containing activated alumina are
pressors Danfoss recommends using recommended.
the Danfoss DML 100% molecular
The drier is to be oversized rather than
sieve, solid core filter drier. Molecular
undersized. When selecting a drier,
sieve filter driers with loose beads from
always take into account its capacity
third party suppliers shall be avoided.
(water content capacity), the system
For servicing of existing installations refrigerating capacity and the system
where acid formation is present the refrigerant charge.
Danfoss DCL solid core filter driers
Suction pressure control An MOP-type expansion valve or suc- When compressors are mounted onto
tion pressure regulator (i.e. Danfoss a rack for a multi-evaporator system
KVL) must be used to limit suction (i.e. supermarket) or when evapora-
pressure at a maximum of 4 bar effec- tors operate at different temperatures,
tive (-5°C). Do not apply both of these use pressure regulators (Danfoss KVP)
devices in combination with one ano- without an MOP expansion valve.
ther.
Suction line heat exchanger A suction line heat exchanger is not re- tion gas superheat which can result in
commended for low temperature ap- too high discharge temperature.
plications as this may cause high suc-
13
RECIPROCATING COMPRESSORS
SYSTEM DESIGN RECOMMENDATIONS
Operating limits
High pressure A high-pressure (HP) safety switch is ted with a manual reset device to pre-
required to shut down the compressor vent cycling around the high pressure
should the discharge pressure exceed limit.
the values shown in the table below. If a discharge valve is used, the HP
This switch can be set at lower values switch must be connected to the ser-
depending on the application and vice valve gauge port, which cannot
ambient conditions. It must be either be isolated.
located in a lockout circuit or associa-
Low pressure A low-pressure (LP) safety switch must automatic LP safety switch wired into
also be used; deep vacuum opera- an electrical lockout circuit. LP switch
tions will result in failure. The mini- tolerance must not allow for vacuum
mum LP safety switch (loss of charge operation of the compressor. LP safety
switch) setting is 0 relative bar (0 bar switch settings for pump-down cycles
g). For systems without pump-down with automatic reset are listed in the
feature, the LP safety switch must be following table.
either a manual lockout device or an
Low ambient temperature At low ambient temperatures, the con- gerant charge. A non-return valve
operation densing temperature and condensing in the discharge line is required
pressure in air cooled condensors will and special care should be taken
decrease. This low pressure may be when designing the discharge line.)
insufficient to supply enough liquid ● Reduce air flow to condensors
refrigerant to the evaporator. As a re- ● Alternatively the condensor may be
sult the evaporating temperature will installed indoor.
decrease, leading to low capacity and When the compressor is located in a
eventual poor oil return. At start-up, low ambient temperature environ-
the compressor will pull into vacuum ment, increased refrigerant migration
and it will be switched off by the low will occur during shut down periods.
pressure protection. Depending on For such conditions an extra belt-type
how the low pressure switch and delay crankcase heater is strongly recom-
timer are set, short cycling can occur. mended.
To avoid these problems, several solu-
Note that with 100% suction gas coo-
tions are possible, based on reducing
led motors, Maneurop® compressors
condenser capacity:
can be externally insulated. Refer to
● Liquid flooding of condensors (note: section "Liquid refrigerant migration &
this solution requires extra refri- charge limits" for more details.
14
RECIPROCATING COMPRESSORS
SYSTEM DESIGN RECOMMENDATIONS
Motor protection Maneurop® NTZ compressors have a A thermal overload relay shall be se-
built-in motor protection which pro- lected to trip at not more than 140% of
Internal motor protection tects the motor against overheating, the RLA value. A circuit breaker shall be
current overload and locked rotor con- selected to trip at not more than 125%
ditions. Additional external overload of the RLA value. Further requirements
protection is not compulsory but may for the external protector are:
still be advisable for alarm function ● Over-current protection; the protec-
and to avoid the compressor tripping tor must trip within 2 minutes at 110%
on its internal protection. of the Maximum Continuous Current
Further an external safety cut-out can (MCC). The MCC value is listed in the
also de-energise the liquid line sole- table on page 9 and stamped as A-max
noid valve preventing liquid transfer on the compressor nameplate.
from the condenser to the evaporator. ● Locked rotor protection; the protec-
Such function can not be handled by tor must trip within 10 seconds on a
the built-in motor protector. start at locked rotor current (LRA)
For the selection of an external motor ● Single phasing protection; the pro-
protector the RLA (Rated Load Amps) tector must trip when one of the three
values from page 9 can be used. phases fails.
Voltage unbalance Operating voltage limits are shown Voltage unbalance causes high ampe-
in the table on page 9. The voltage rage on one or more phases, which in
applied to motor terminals must lie turn leads to overheating and possible
within these limits during both start-up motor damage.
and normal operation. The maximum The voltage unbalance is given by the
allowable voltage unbalance is 2%. following formula:
Vavg = Mean voltage of phases 1, 2 and 3 V1-3 = Voltage between phases 1 and 3
V1-2 = Voltage between phases 1 and 2 V2-3 = Voltage between phases 2 and 3.
Cycle rate limit No more than 12 starts per hour (6 proper oil return from the system to
when a soft start accessory is used) the compressor.
are allowed. A higher number would A 5-minute delay between two suc-
reduce the service life of the motor- cessive compressor starts is being pro-
compressor unit. If necessary, use an posed herein, with a 2-minute runtime
anti-short-cycle timer within the con- after each start and a 3-minute idle
trol circuit. time between each stop and start.
The system must be designed in a way Only during the pump-down cycle
that guarantees minimum compressor may the compressor run for much
running time so as to provide sufficient shorter intervals.
motor cooling after start-up as well as
Discharge temperature Even when the motor windings are is operated outside its application
protected against overheating by the envelope. The most effective protec-
protection internal motor protection, the com- tion against too high discharge gas
pressor discharge gas temperature temperature is to mount a discharge
could exceed the maximum allowed gas thermostat. An accessory kit is
value of 135°C when the compressor available from Danfoss which inclu-
15
RECIPROCATING COMPRESSORS
SYSTEM DESIGN RECOMMENDATIONS
Thermostat
Discharge line
Insulation
Bracket
Liquid refrigerant control Refrigeration compressors are basi- Liquid refrigerant will dilute the oil,
cally designed as gas compressors. wash out the bearings causing wear
and charge limits Depending on the compressor de- and eventually seizure. Furthermore,
sign and operating conditions, most high oil carry over will cause lack of oil
compressors can also handle a limited in the sump.
amount of liquid refrigerant. Maneu- Good system design can limit the
rop® NTZ compressors have a large in- amount of liquid refrigerant in the
ternal volume and can therefore handle compressor, which will have a positive
relatively large amounts of liquid refri- effect on the compressor service life.
gerant without major problems. Liquid refrigerant can enter a com-
However even when a compressor can pressor in various ways, with different
handle liquid refrigerant, this will not effects on the compressor as descri-
be favourable to its service life. bed in the following points.
Off-cycle migration During system standstill and after refrigerant. When the compressor is
pressure equalisation, refrigerant will started, the pressure in the crankcase
condensate in the coldest part of the decreases rapidly and refrigerant will
system which may be the compressor violently evaporate, causing the oil
when it is placed in a cold environ- to foam (boiling). Both dilution and
ment. Ultimately, the full system refri- foaming reduce the lubrication pro-
gerant charge can condensate in the perties of the oil. In extreme situations
compressor crankcase. A large amount liquid could enter the compressor cy-
will dissolve in the compressor oil un- linders with immediate compressor
til the oil is completely saturated with break-down as a result.
Liquid floodback during During normal and stable system ope- ● evaporator fan failure or frosted-up
operation ration, refrigerant will leave the eva- evaporator coils.
porator in a superheated condition In these situations, liquid refrigerant
and enter the compressor as a supe- will continuously enter the compres-
rheated vapour. Normal superheat sor. The negative effects from conti-
values at compressor suction are 5 to nuous liquid floodback are:
30 K. However the refrigerant leaving ● permanent oil dilution
the evaporator can contain an amount
● in extreme situations with high
of liquid refrigerant due to different
system refrigerant charge and large
reasons:
amounts of floodback, liquid slugging
● wrong dimensioning, wrong setting
could occur.
or malfunction of expansion device
16
RECIPROCATING COMPRESSORS
SYSTEM DESIGN RECOMMENDATIONS
Crankcase heater A crankcase heater protects against Under extreme conditions such as low
the off-cycle migration of refrigerant ambient temperature at –15°C or lower
and proves effective if oil temperature a belt type crankcase heater could be
is maintained 10 K above the satura- used in addition to the PTC heater, al-
ted LP temperature of the refrigerant. though this is not a preferred solution
Tests must thereby be conducted to for 1 and 2 cylinder compressors. The
ensure that the appropriate oil tempe- belt crankcase heater must be positio-
rature is maintained under all ambient ned on the compressor shell as close
conditions. A PTC crankcase heater as possible to the oil sump to ensure
is required with all Maneurop®‚ NTZ good heat transfer to the oil. The be-
compressors. PTC crankcase heaters low illustrated mounting positions are
are self-regulating. recommended:
Models Belt crankcase heaters are not self-re-
NTZ048 - NTZ068 - NTZ096 - gulating. Control must be applied to
NTZ108 - NTZ136 energise the belt heater once the com-
pressor has been stopped and then to
de-energise it while the compressor is
running. The belt heater must be ener-
gised 12 hours before restarting the
compressor following an extended
down period.
If the crankcase heater is not able to
Models maintain the oil temperature at 10 K
NTZ215 - NTZ271 above the saturated LP temperature
of the refrigerant during off cycles or
if repetitive floodback is present a the
Liquid Line Solenoid Valve (LLSV) +
pump-down cycle is required, even-
tually in conjunction with a suction
accumulator.
Liquid line solenoid valve & In refrigeration applications, the Li- LLSV in conjunction with the pump-
pump-down quid Line Solenoid Valve (LLSV) is hi- down cycle (especially in low-tempe-
ghly recommended. During the off-cy- rature applications), the quantity of
cle, the LLSV isolates the liquid charge refrigerant in the low-pressure side of
in the condensor side, thus preventing the system will be reduced.
against refrigerant transfer or exces- A pump-down cycle design is required
sive migration of refrigerant into the when evaporators are fitted with elec-
compressor. Furthermore, when using tric defrost heaters.
Suction accumulator A suction accumulator offers consi- The suction accumulator must be se-
derable protection against refrigerant lected in accordance with the accumu-
floodback both at start-up and during lator manufacturer recommendations.
operation or after the defrost opera- As a general rule, Danfoss Commercial
tion. This device also helps protect Compressors recommends to size the
against off-cycle migration by means accumulator for at least 50% of the to-
of providing additional internal free tal system charge. Tests however must
volume to the low pressure side of the be conducted to determine the opti-
system. mal size.
17
RECIPROCATING COMPRESSORS
SOUND AND VIBRATION MANAGEMENT
18
RECIPROCATING COMPRESSORS
INSTALLATION AND SERVICE
System cleanliness System contamination is one of the parts before brazing and always purge
main factors that affects equipment nitrogen or CO2 through the pipes
reliability and compressor service life. during brazing to prevent oxidation.
Therefore it is important to take care If flux is used, take every precaution
of the system cleanliness when assem- to prevent leakage into the piping. Be
bling a refrigeration system. During carefull not to drill holes in pipe-work
the manufacturing process, circuit (e.g. for schrader valves) in parts of the
contamination can be caused by: installation that are already comple-
● Brazing and welding oxides, ted when filings and burrs cannot be
removed. Carefully follow the instruc-
● Filings and particles from removing tions below regarding brazing, moun-
burrs from pipe-work, ting, leak detection, pressure test
● Brazing flux, and moisture removal. All installation
and service work shall only be done
● Moisture and air.
by qualified personnel respecting all
Only use clean and dehydrated, re- procedures and using tools (charging
frigeration-grade copper tubes and systems, tubes, vacuum pumps, etc.)
silver alloy brazing material. Clean all dedicated for R404A and R507A.
Compressor handling,
mounting
and connection
Compressor handling Maneurop® NTZ compressors must be Always use the proper tools for trans-
handled with care and all handling pro- porting the compressor. Keep the
cedures must be performed smoothly compressor in an upright position du-
and gently. Each NTZ has been fitted ring all handling tasks (manipulating,
with one lift ring which shall always be transport, storage). The angle off the
used to lift the compressor. Once the vertical must not exceed 15 degrees.
compressor is installed, the lift ring
shall never be used to lift the complete
installation.
Compressor mounting The compressor must be moun- grommets that are shipped with the
ted onto a horizontal surface with compressor. Mounting torques are lis-
a maximum slope of 3 degrees. ted in the below table.
Always use the rubber mounting
Torque (Nm)
Component
Min. Max.
Rotolock suction valve, NTZ048 - NTZ068 80 100
Rotolock suction valve, NTZ096 - NTZ271 100 120
Rotolock discharge valve, NTZ048 – NTZ068 70 90
Rotolock discharge valve, NTZ096 - NTZ271 80 100
Electrical T-block screws HN°10-32 UNF x 9.5 - 3
Earth screw - 3
Oil sight glass (with black chloroprene gasket) 40 45
3/8” flare oil equalisation nut 45 50
Schrader nut 11.3 17
Schrader valve (internal) 0.4 0.8
Mounting grommet bolt, NTZ048 – NTZ136 12 18
Mounting grommet bolt, NTZ215 - NTZ271 40 60
Belt crankcase heater - 4
19
RECIPROCATING COMPRESSORS
INSTALLATION AND SERVICE
Compressor connection New compressors have a protective or valves may be brazed to the pipes
to the system nitrogen holding charge. Only remove when mounted on the compressor. In
the suction and discharge plugs just this situation nitrogen or CO2 must be
before connecting the compressor to purged through the compressor via
the installation, so as to prevent air the schrader valve to prevent air and
and moisture from entering the com- moisture ingress. Purging must start
pressor. Remove the discharge plug when the plugs are removed and pro-
first and the suction plug next; by pro- ceeded during the brazing process.
ceeding as such, the nitrogen holding When rotolock valves are used on the
charge can escape via the discharge compressor, they shall be closed im-
connection and the risk of an oil mist mediately after mounting, thus kee-
blow-out via the suction connection ping the compressor isolated from
will be minimal. atmosphere or from a not yet dehy-
Whenever possible the compressor drated system.
must be the last component to be in- Note:
tegrated in the system. It is advisable when the compressor is built into a
to braze the solder sleeves or service «pack» or «rack» configuration which
valves to the pipework before the com- is not installed immediately on its fi-
pressor is mounted. when all brazing nal location, a vacuum pull-down and
is finished and when the total system moisture removal must be performed
is ready, the compressor plugs can be to the "pack" or "rack" as if it were a
removed and the compressor can be complete system (see below). the pack
mounted to the system with a mini- must be charged with nitrogen or CO2
mum exposure to ambient air. If this and open tubes must be blocked with
procedure is not possible, the sleeves caps or plugs.
Schrader
N2
System pressure test Always use an inert gas such as nitro- an inflammable mixture with the com-
gen for the pressure test. Never use pressor oil. The maximum allowed test
other gasses such as oxygen, dry air pressures for NTZ compressors are:
or acetylene. These gasses may form
20
RECIPROCATING COMPRESSORS
INSTALLATION AND SERVICE
Leak detection Whenever possible the compressor gen, dry air or acetylene as these gas-
must be kept isolated from the sys- ses can form an inflammable mixture
tem during leak detection by closing with the compressor oil. Never use CFC
the suction and discharge valves Use or HCFC refrigerants for leak detection
a mixture of nitrogen and the final re- of HFC systems. Leak detecting additi-
frigerant (eg. R404A or R507) and use ves shall not be used as they may af-
a leak detector for the applied refrige- fect the lubricant properties. Warranty
rant. A spectrometric detection system may be voided if leak detection additi-
using helium can also be applied. Note ves have been used.
that leak detection with refrigerant
may not be allowed in some countries. Eventual leaks shall be repaired respec-
Do not use other gasses such as oxy- ting the instructions written above.
Vacuum pump-down and Moisture obstructs proper operation However, if the pressure were to ra-
of the compressor and the rest of the pidly increase, the system would not
dehydration procedure refrigeration system. Air and moisture be leak-tight and leak detection and
reduce service life, increase conden- repair would have to be repeated;
sing pressure and cause excessively also, the vacuum pull-down proce-
high discharge temperatures, which dure would have to be restarted from
are capable of destroying the lubri- Step 1. A slowly-increasing pressure
cating properties of the oil. Air and would indicate the presence of mois-
moisture also increase the risk of acid ture, in which case Steps 2 and 3
formation, thus giving rise to copper should be repeated.
plating. All these phenomena can ul- 4. Connect the compressor to the sys-
timately induce mechanical and elec- tem by means of opening the valves.
trical compressor failure. To eliminate Repeat Steps 2 and 3.
these risks, it is recommended to per-
5. Break the vacuum with either nitro-
form the following vacuum pull-down
gen or the ultimate refrigerant.
procedure:
6. Repeat Steps 2 and 3 on the total
1. To the extent possible (i.e. if valves
system.
are present), the compressor must be
kept isolated from the system. Upon commissioning, the system
2. After leak detection, the system moisture content may be as high as
must be pulled-down under a vacuum 100 ppm. During compressor opera-
of 500 microns (0.67 mbar). A two-sta- tion, the filter drier must reduce this
ge vacuum pump shall be used with content to a level of 20 to 50 ppm.
a capacity appropriate for the system Warning:
volume. It is recommended to use Do not use a megohmmeter or apply
connection lines with a large diame- power to the compressor while it is
ter and to connect these lines to the under vacuum as this may cause mo-
service valves and not to the schrader tor winding damage, and never run
connection, so as to avoid excessive the compressor under vacuum as this
pressure losses. may cause the compressor motor to
3. Once the vacuum level of 500 mi- burnout.
crons has been reached, the system
must be isolated from the vacuum Refer to News bulletin "Vacuum pump
pump. Wait 30 minutes; during this down and dehydration procedure" for
time, system pressure should not rise. more complete information.
Start-up Before initial start-up or after a pro- ted in another way (for example with
longed shut-down period, energise an electric heater or flood light) to boil
the crankcase heater 12 hours prior to off refrigerant from the oil. This is par-
start-up. If the crankcase heater can- ticulary important when ambient tem-
not be energised long enough before perature is low at commissioning.
start-up, the compressor shall be hea-
21
RECIPROCATING COMPRESSORS
INSTALLATION AND SERVICE
Refrigerant charging For the initial charge, the compressor is a near-azeotropic mixture and must
must not run and service valves must be charged in the liquid phase. R507A
be closed. Charge refrigerant as close is an azeotropic mixture and can be
as possible to the nominal system charged either in liquid or gas phase.
charge before starting the compres-
sor. Then slowly add refrigerant on Warning:
the low pressure side as far away as When a liquid line solenoid valve is
possible from the compressor suction used, the vacuum in the low pressure
connection. The refrigerant charge side must be broken before applying
quantity must be suitable for both power to the system.
winter and summer operation. R404A
Oil charge and oil level The oil charge must be checked before into account oil contained in accesso-
commissioning (1/4 to 3/4 of the oil ries such as oil separators or oil traps.
sight glass). Check the oil level again If this amount has already been added
after a minimum of 2 hours operation and the oil level in the compressor
at nominal conditions. In most instal- keeps decreasing, the oil return in the
lations the initial compressor oil char- installation is insufficient. Refer to sec-
ge will be sufficient. In installations tion "Piping design". In installations
with line runs exceeding 20 m or with where slow oil return is likely such as
many oil traps or an oil separator, ad- in multiple evaporator or multiple con-
ditional oil may be required. Normally denser installations an oil separator is
the quantity of oil added should be no recommended. Always use Danfoss
more than 2% of the total refrigerant 160Z lubricant for systems with NTZ
charge. This percentage does not take compressors and R404A or R507A.
Installation checks After a few running hours the main the compressor. When a too high su-
system parameters shall be verified perheat is noted while the expansion
to ensure that the system is working valve setting is correct, the suction line
correctly or eventually to adjust the insulation between evaporator and
settings. compressor should be checked and
● The evaporating temperature and eventually replaced by a higher qua-
condensing temperature shall be com- lity insulation.
pared with the design conditions. ● A too high discharge gas tempe-
22
RECIPROCATING COMPRESSORS
Danfoss Commercial Compressors http://cc.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also
applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks
in this material are property of the respective companies. Maneurop® Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
FRCC.PC.002.A1.02 - May 2005 - Replace GA041 - 06/01 GB www.kraft.fr