Download as pdf or txt
Download as pdf or txt
You are on page 1of 47

MEGA-GUARD Ship Automation and Navigation System

Operator Guide – Fire Alarm Panel

CONVENTIONAL
FIRE ALARM PANEL

OPERATOR GUIDE
MEGA-GUARD E-Series

CONVENTIONAL
FIRE ALARM SYSTEM

OPERATOR GUIDE

MEGA-GUARD E-Series
Ship Automation and Navigation System

Title : Fire Alarm Panel Page 1 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

TABLE OF CONTENT
1) Overview .............................................................................................................................4
1.1) Fire Alarm Overview Drawing ........................................................................................... 4
1.2) Functional Overview ......................................................................................................... 5
1.3) Detectors and Manual Call Points ..................................................................................... 7
1.4) Operation and Configuration (set-up) Modes .................................................................. 8
1.5) Fire Alarm procedure ........................................................................................................ 9
1.6) Fault procedure .............................................................................................................. 10
1.7) Both power supplies failing and internal faults procedure ............................................ 11
1.8) Dimming and background illumination........................................................................... 12
1.9) Lamp test......................................................................................................................... 12
1.10) LCD Display ...................................................................................................................... 13
1.11) USB Host.......................................................................................................................... 14
1.12) Ethernet failure ............................................................................................................... 14
1.13) “Remote” panel failure ................................................................................................... 14
1.14) NMEA output message ................................................................................................... 14
1.14.1) Example of Status message ................................................................................ 16
1.14.2) Example of Event message ................................................................................. 16
1.14.3) Example of Fault message .................................................................................. 16
1.14.4) Example of Disable message............................................................................... 16
1.15) Fire Alarm Repeater Panel .............................................................................................. 17
2) Entering Operator Mode Level 2 .......................................................................................18
3) Setup and Configuration Level 3 .......................................................................................19
3.1) General usage notes ....................................................................................................... 19
3.2) Entering the setup mode password ................................................................................ 19
3.3) Setup screen: Change level passwords ........................................................................... 20
3.4) Setup screen: Enter new password for level 2 and 3 ..................................................... 20
3.5) Setup screen: Background illumination level and Maximum dimming level.................. 21
3.6) Setup screen: FireAlarm LED dimming............................................................................ 22
3.7) Setup screen: LED dimming ............................................................................................ 22
3.8) Setup screen: Adjust backlight ........................................................................................ 22
3.9) Setup screen: Dimming of the LCD ................................................................................. 23
3.10) Setup screen: link alarms ................................................................................................ 23
3.11) Setup screen: Panel ID .................................................................................................... 24
3.12) Setup screen: Master-Slave system ................................................................................ 24
3.13) Setup screen: Remote panel ID....................................................................................... 25
3.14) Setup screen: NMEA communication speed .................................................................. 25
3.15) Setup screen: Synchronizing dimming level between Control Panels ............................ 26
3.16) Setup screen: Fault handling options.............................................................................. 26
3.17) Setup screen: Fire Alarm handling options ..................................................................... 26
3.18) Setup screen: Fire Alarms Relay timeout ........................................................................ 27
3.19) Setup screen: Siren output delay .................................................................................... 27
3.20) Setup screen: Zone location ............................................................................................ 27
3.21) Setup screen: Manual Call Point resistance .................................................................... 28
4) Save and load configurations to/from USB drive ..............................................................29
Title : Fire Alarm Panel Page 2 of 47
Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

4.1) Save 1131 program to USB drive .................................................................................... 29


4.2) Load 1131 program from USB drive ............................................................................... 29
4.3) Save configuration to USB drive...................................................................................... 29
4.4) Load configuration from USB drive ................................................................................. 29
5) Ethernet communication with other panels .....................................................................31
6) Software upgrades using the USB drive ............................................................................32
6.1) Panel USB Bootloader upgrade ....................................................................................... 32
6.1.1) Upgrading the panel USB bootloader for panels that are already
programmed with panel bootloader versions older than 1.21.0.0 .................... 32
6.1.2) Upgrading the panel USB bootloader for panels that are already
programmed with panel bootloader versions 1.21.0.0 or higher ...................... 32
6.2) Panel Firmware Upgrade ................................................................................................ 34
7) Hardware Specifications ....................................................................................................35
7.1) Fire Alarm Panel .............................................................................................................. 35
8) Connection Drawings and Project Engineering .................................................................35
8.1) Example Project drawings ............................................................................................... 36
8.2) Standard drawings.......................................................................................................... 38
9) Maintenance .....................................................................................................................41
9.1) System status checks....................................................................................................... 41
9.2) Failure test....................................................................................................................... 43
9.3) Earth Fault ....................................................................................................................... 45
10) Mini-Guard, Maxi-Guard and Mega-Guard E-Series .........................................................46
11) Naming conventions and company information ...............................................................47

Title : Fire Alarm Panel Page 3 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

1) Overview
1.1) Fire Alarm Overview Drawing

Title : Fire Alarm Panel Page 4 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

1.2) Functional Overview

The Fire Alarm panel is a conventional marine fire detection system in accordance with
classification requirements and EN54-2.

The Fire Alarm Panel, which is flush mounted in console, contains operator push-buttons and
LEDs. The rear side of the Fire Alarm Panel is equipped with detachable terminal strips for field
wiring. The Fire Alarm Panel has standard DIN size 144 x 144 mm for flush panel console
mounting.

The basic Fire Alarm Panel is designed for 4 zones and can be extended for up to 8 zones (2 x
Fire Alarm Panel) and for up to 12 zones (3 x Fire Alarm Panel).

The Fire Alarm Panel can be also configured as a Repeater panel connected via Ethernet to a
Master Fire Alarm Panel.

A text sheet with description for each Alarm and each Fault is inserted from the top of the panel.

The Fire Alarm Panel is equipped with the following operator lamps and buttons:

- 4x Fire Alarm lamp (red) for each zone. The lamp is also a pushbutton in order to
disable a zone in level 2 mode.

- 4 x Line Fault LED (yellow) for each zone, indicating a line failure

- 4 x Disable LED (yellow) for each zone, indicating that a zone has been disabled

- 1 x Fire Alarm LED (red) general, activated when one of the 4 zones is in alarm
condition

- 1 x General Fault LED (yellow) general, activated when internal or external fault is
detected

- 1 x Main supply fail LED (yellow), activated when mains supply is failing

- 1 x Back-up supply fail LED (yellow), activated when back-up supply is failing

- 1 x Earth failure LED (yellow), activated when one of the zone inputs or Fire Alarm
output is connected to earth

- 1 x Siren Output fail LED (yellow), activated in case line fault is detected in Fire Alarm
output

- 1 x System On LED (green), activated in case no internal errors are detected

- 1 x Fault LED (red), activated in case internal error is detected

- A Stop Horn button for silencing the internal buzzer and external sirens

- A Panel Reset button for resetting Fire Alarm and Faults

- Left Arrow and Right Arrow buttons, for various uses

Title : Fire Alarm Panel Page 5 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

- LCD display with 2x16 characters with 3.5mm height.

The Fire Alarm Panel is equipped with the following connection terminals:

- 4 monitored zones and in each zone a maximum of 32 detectors and/or manual call
points. An end of line resistor of 3300 ohm has to be mounted. Maximum current per
zone: 100mA (protected by fuse)

- External monitored 24VDC output for Sirens. An end of line resistor of 3300 ohm has to
be mounted. In case of fire alarm/manual call point or faults (if siren for fault is enabled in
configuration) this output is activated until Stop Horn pressed. The command of the siren
output can be delayed with 0…120s (configurable from setup) in case of fire alarms or
faults. Manual call points will always trigger the siren output at once. Fire detectors from
machinery space, if they are placed in one zone and that zone is configured as “machinery
area”, will also trigger the siren output without delay. For zones which are installed in
“general area” space and if a detector is already in alarm, a second detector in alarm (or
a third detector in alarm) will also trigger the siren output without delay if the zone current
is bigger than 100mA. In case siren output is not activated, the 24VDC polarity will be
reversed so that end of line resistor is monitored. External Sirens and Bells have to include
a diode, blocking the reversed 24V voltage. Maximum current: 500mA (protected by fuse)

- External fire alarm relay output which is activated when after a Fire Alarm, the Fire Alarm
Panel has not been reset (Stop Horn or Panel Reset) within 2 minutes. Activation means:
De-energize the relay so also in case no power available this output will give alarm
condition.

- External fail relay output which is activated when internal fault or external fault (line faults)
will be detected. Activation means: De-energize the relay so also in case no power
available this output will give alarm condition

- NMEA output. A NMEA-0183 serial output is available for connecting to the VDR

- Main power supply 19-31VDC / 1A maximum (4 x 100mA for zones and 500mA for Fire
Alarm output, 100mA for Fire Alarm Panel)

- Back-up power supply 19-31VDC / 1A maximum


If Fire Alarm Panel is configured as Repeater panel, then only the Main power supply
and the Back-up power supply must be connected to Repeater panel terminals and
all the other terminals must be disconnected/not connected.

Title : Fire Alarm Panel Page 6 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

1.3) Detectors and Manual Call Points

The Fire Alarm Panel is designed to work with the following detectors and manual call points:
Type/Manufacturer Tyco/600 Apollo / Orbis series(5) Consilium

Optical smoke detector 601-M ORB-OP-42003-MAR (2) (4) N1115

Multi-sensor smoke detector 601PH(2) ORB-OH-43003-MAR (2) (4)

Class A2S Heat detector 58degC. 601H-F(2) ORB-HT-41014-MAR (2) (4) 038000
Fixed temperature

Class A1R Heat detector 58degC. 601H-R(2) ORB-HT-41001-MAR(4)


Fixed temp + rise

Class BS Heat detector 65degC. - ORB-HT-41016-MAR(2) (4)


Fixed temperature

Class BR Heat detector 65degC. - ORB-HT-41015-MAR(2) (4)


Fixed tem + rise

Class CS Heat detector 80degC. 631H-F(2) ORB-HT-41018-MAR(2) (4) 038015


Fixed temperature

Class CR Heat detector 80degC. 631H-R(2) ORB-HT-41017-MAR(2) (4)


Fixed tem + rise

Detector Base 5B 5” (3) ORB-MB-00001-MAR(3) (4)

Detector Alarm Resistance 450 ohm 600 ohm 430

Manual Call Point CP250M 55100-021 MAR N1301

Manual Call Point IP55 MCP260M 55100-022 MAR N1305

Manual Call Point Resistance 470 ohm (1) 470 ohm (1) 266 ohm

Fire Alarm Bell 6” - 29600-534 -

Fire Alarm Bell 6” IP55 - 29600-535 -

Electronic Sounder - 29600-623 -

(1)
In case the resistor will be replaced by a resistor of 266 ohm, the Fire Alarm Panel is able to
distinguish between fire alarms caused by detectors or by manual call points. The cause (manual
call point alarm) will then be displayed on the display of the Fire Alarm Panel.
(2)
Detector is equipped with a local led indicator.
(3)
Detector base must be equipped with an anti-tamper facility. The detector base must be wired
in such a way, that the fire detector loop is interrupted.
(4)
These detectors have type approval
(5)
If only Apollo Orbis series detectors are used in the system, then it is possible to use a Manual
Call Point with 470 ohm resistance and still the Fire Alarm Panel will be able to distinguish
between fire alarms caused by detectors or by manual call points. The cause (manual call point
alarm) will then be displayed on the display of the Fire Alarm Panel. In order to do that the Fire

Title : Fire Alarm Panel Page 7 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

Alarm Panel must be properly configured (see chapter Setup screen: Manual Call Point
resistance).

1.4) Operation and Configuration (set-up) Modes

The Fire Alarm Panel knows 3 levels of operation:

- Level 1, which is normal operation mode and this mode is entered as soon as one of the
power supplies becomes available.

- Level 2, which is operation mode protected by a password.

- Level 3, which is configuration (set-up) mode protected by a password. In this level,


operator functions can be defined which are either accessible only in Level 2 or both in
Level 1 and Level 2.

Level 1 operator functions:

o Stop Horn for Fault (in case defined in Level 3 that is allowed in Level 1).

o Stop Horn for Fire Alarm (in case defined in Level 3 that is allowed in Level 1).

o Panel Reset for Fault (in case defined in Level 3 that is allowed in Level 1).

o Dimming, with Arrow Left (more dimming) and Arrow Right (less dimming).

Level 2 operator functions (protected by password):

o Stop Horn for Fault

o Stop Horn for Fire Alarm

o Panel Reset for Fault

o Panel Reset for Fire Alarm

o Disable/enable zone

o Re-activate Siren output and internal buzzer

Level 3 configuration functions (protected by password):

o Configure the panel type: Standalone/Master or Repeater (slave) Panel. Default


Standalone panel

o In case of Fault: internal buzzer only or internal buzzer + Siren output activated.
Default: Internal buzzer and Siren output activated

o Stop Horn for Fault allowed in Level 2 or in Level 1+2 or Automatic. Default: Level
1+2
Title : Fire Alarm Panel Page 8 of 47
Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

o Panel Reset for Fault allowed in Level 2 or in Level 1+2 or Automatic. Default: Level
2

o Stop Horn for Fire Alarm allowed in Level 2 or in Level 1+2. Default: Level 2

o Fire Alarm relay timeout adjustment

o Siren output delay adjustment

o Manual call point resistance value

o Background illumination adjustment

o Password changes for level 2 and for level 3

o Dimming distribution over Ethernet network

o Enable/disable Ethernet link failures

o Define the communication speed used for NMEA output messages

1.5) Fire Alarm procedure

A Fire Alarm is generated when one or more of the detectors and/or manual call points
connected to the zone inputs come into alarm condition. The Fire Alarm Panel can distinguish
between detector alarms and manual call point alarms, in case a 266 ohm resistor is
mounted in the manual call point or in case only Apollo Orbis series detectors are used and
the panel is configured to recognize 470 ohm manual call points (see chapter Setup screen:
Manual Call Point resistance).

Fire Alarms procedure:

o Fire Alarm lamp 1…4 (pushbutton) is flashing and internal buzzer (2Hz) and Siren
(continuous) are activated and Fire Alarm LED steady on

o Siren activation in case of Fire Alarm is according with the following rules:

▪ At once, if the siren output delay configured is 0s (see Setup screen: Siren
output delay)
▪ At once, if a manual call point is pressed in that zone
▪ At once, if a detector enters in alarm condition and the zone is
configured as “machinery area” space (see Setup screen: Zone location)
▪ Delayed with siren output delay value, if a detector enters in alarm
condition and the zone is configured as “general area” space (see Setup
screen: Zone location)
▪ Immediately after the zone current reaches 100mA, if we already have a
detector in alarm in a zone configured as “general area” space and a
second detector comes in alarm state in the same zone (depending on
Title : Fire Alarm Panel Page 9 of 47
Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

detector’s alarm resistance the overall zone current can reach the
maximum allowed current of 100mA/per zone)

o When Stop Horn pressed (Level 2 or in Level 1+2), the Internal Buzzer and
external Sirens are silenced.

o When Panel Reset pressed (in Level 2 only), the 24V from zone is removed for
5 seconds and then comes back, resetting the connected detectors. Fire Alarm
lamp and Fire Alarm LED remain ON when the alarm is still there. Fire Alarm
lamp and Fire Alarm LED will extinguish when fire alarm condition has
disappeared. The Panel Reset procedure has to be repeated until the detector
or manual call point does not give alarm anymore. If after the Panel Reset
procedure the zone current is still above 100mA, a line fault will be generated
(short circuit condition in that zone is met).

o Internal buzzer and Siren can be activated again when in Level 2 by pressing
Stop Horn for more than 2 seconds.

If there is in one zone more than one detector in alarm or more than one manual
call pressed and the overall zone current exceeds 100mA, then after pressing the

 Panel Reset button a Zone Line Fault will be generated as long as the zone current
stays above 100mA (as long as detectors are maintaining the alarm current).
During this period of time no new Fire Alarms can be detected in that zone. Only
after the zone returns to quiescent, new Fire Alarms can be detected in that zone.

1.6) Fault procedure

A Fault alarm is generated on one of the following conditions:


o Line Fault 1...4.
1. Indicated by Yellow LED
2. Fault in case of open circuit or short circuit of zone input connection
wires
o Siren fault
1. Indicated by Yellow LED
2. Fault in case of open circuit or short circuit of Siren output connection
wires
o Earth Failure
1. Indicated by Yellow LED
2. Fault in case the connection wires of zone inputs or siren output make
a connection to Earth.
o Mains supply failure
1. Indicated by Yellow LED
2. Fault in case the mains supply voltage is failing
o Backup supply failure
1. Indicated by Yellow LED
2. Fault in case the backup supply voltage is failing
Title : Fire Alarm Panel Page 10 of 47
Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

Fault procedure:
o Corresponding Fault LED is activated and internal buzzer and Siren output
(when selected in Level 3) are activated and Fault output activated (= de-
energized) and General Fault LED steady on

o Siren activation in case of Fault is enabled via option Setup screen: Fault
handling options and is according with following rules:

▪ At once, if the siren output delay configured is 0s (see Setup screen: Siren
output delay)
▪ Delayed with siren output delay value (if value is different than 0s)

o When Stop Horn pressed (Level 2 or in Level 1+2), the Internal Buzzer and
external Sirens are silenced

o In case of automatic Panel Reset for Faults (set-up in Level 3): silence buzzer
and silence Siren Output and de-activate Fault output (=energize) and
extinguish corresponding Fault LED’s when Fault disappears

o In case of manual Panel Reset for Faults (by pressing the Panel Reset button),
two conditions can be distinguished:

▪ When fault is still active when Panel Reset pressed (in Level 2 or in Level
1+2), corresponding Fault LED will remain activated and Fail Output
remains active and General Fault LED remains steady until the fault
disappears. When the fault disappears: Fault LED’s will extinguish and
Fail Output will be de-activated (= energized)

▪ when fault is not active any more when Panel Reset pressed (in Level 2
or in level 1+2): Fault LED’s will extinguish and Fail Output will be de-
activated (= energized)

1.7) Both power supplies failing and internal faults procedure

When both power supplies are failing, the following will happen:
o Fail output is activated (de-energized).

o In case one of the power supplies is restored, the Fire Alarm Panel enters the
normal operation mode and Fire Alarms and Faults are detected.

When internal failure is detected the following will happen:

o Fail output is activated (de-energized).

o System On LED (green) will extinguish

Title : Fire Alarm Panel Page 11 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

o Fault LED (red) will be activated in some internal fault conditions

In case internal failure is detected, the unit needs to be repaired or replaced.

1.8) Dimming and background illumination

The activated lamps/buttons and the LCD display on the panel can be dimmed during the night,
except for the Fire Alarm lamps/LED which cannot be dimmed. The dimmed illumination level
can be adjusted in normal operation mode by pressing the Left Arrow button for more dimming
(= less brightness), or Right Arrow button for less dimming (= more brightness), in 8 steps. At
power-up the dimming is set to no dimming.

The panel has background illumination, which shines through the text sheet for night visibility of
the text. The background illumination level can be adjusted in setup mode (level 3), and upon
power up the background illumination is set to this level.

The brightness of the maximum dimming level (=minimum brightness) will be considerably
higher than the background illumination level in order to avoid confusion if a lamp is activated or
not. The background illumination level and the maximum dimming level can be adjusted in
setup mode.

1.9) Lamp test

A Lamp Test of the unit can be performed by pressing the PANEL RESET and STOP HORN buttons
at the same time during normal operation; as long as both buttons are kept pressed, all buttons
and all LEDs will be illuminated at maximum brightness and the firmware version and 1131 file
version are displayed on LCD:

CPL 1.31.1.0
Vm file 1.01

or (if an older 1131 file without version number is stored in panel):

CPL 1.31.1.0
Vm file ver N.A.

or (if no 1131 file is stored in panel):

CPL 1.31.1.0
No Vm file!

If PANEL RESET & STOP HORN are kept pressed for more than 5s, then the internal buzzer and
horn relay are also activated. When PANEL RESET & STOP HORN buttons are released, the
previous state is restored (for LCD, LEDs, backlight levels, buzzer & horn relay).

Title : Fire Alarm Panel Page 12 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

1.10) LCD Display

The panel has 2x16 character display, with a character height of 3.5mm, and with dimming.
During normal operation, the display shows level and “quiescent”.

Immediately after power-up, the LCD will be illuminated at 100% brightness and will display the
following logo message:

1. If the panel has a valid configuration:


Fire Alarm XX
Fw vAA.BB.CC.DD

where XX is the ID of the panel, as configured in Setup mode. vAA.BB.CC.DD is the


firmware revision number.
2. If the panel does not have a valid configuration:
No config!
Fw vA.BB.CC.DD
On the second line, the letters will be replaced as follows:

- “A” is the major build version of the firmware;


- “BB” is the minor build version of the firmware;
- “CC” is the update number on the minor build
- “DD” is a special customer build number (usually zero).

This logo message will remain on the screen for at least 3 seconds, even if alarms are generated
during these 3 seconds. If no alarms are generated, the logo message will remain on the screen
for 10 seconds, after which the screen will be erased.

If the 1131 file is missing, the following message will be displayed:

No Vm file!
Fw v1.31.1.0

Note: The current firmware version will be displayed on second line.

If the 1131 file is present, but the version of 1131 file is not compatible with current firmware
version, the following message will be displayed:

Update Vm file
to v1.05 or high

Note: The minimum supported 1131 file version will be displayed on second line.

During normal operation and when no alarms and faults are present, the display will indicate:

Level 1
QUIESCENT

In Level 1 and 2 the display will indicate the following:

Title : Fire Alarm Panel Page 13 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

- In case of manual call point alarms:

o Display will indicate: Manual Call Point

- In case of detector alarms:

o Display will indicate: Fire Alarm

1.11) USB Host

The USB Host has one USB port which can be used for attaching USB drives.

It can be used either for updating the firmware or for saving and loading panel configurations.

To save or load a configuration the USB drive can be inserted any time during normal operation.
Details about the saving and loading procedure are in chapter “Save and load configurations
to/from USB drive”.

1.12) Ethernet failure

In case the Fire Alarm Panel is connected to other panels to distribute the dimming level, the
following will be indicated on the LCD display in case of Ethernet failure:

The alarm text for this failure is “LINK A FAIL” or “LINK B FAIL” (“A” for the first Ethernet port, “B”
for the second Ethernet port). If both ports have communication failures, display shows “LINK A
& B FAIL”. This alarm disappears if it is acknowledged and Ethernet communication is restored.

Usually, Ethernet Link Failures are detected instantaneously (the moment they happen, without
any delay). No further action will be taken: only indication on the display.

If the Ethernet link is still good but one of the RX/TX Ethernet wires is broken then the following
message will be displayed: “ETH A CABLE FAIL” or “ETH B CABLE FAIL” (“A” for the first Ethernet
port, “B” for the second Ethernet port). If both ports have communication failures, display
shows “ETH A & B CABLE FAIL”. This alarm disappears if it is acknowledged and Ethernet
communication is restored.

1.13) “Remote” panel failure

In case the Fire Alarm Panel is configured to be a part of a Master-Slave system (one
Repeater panel connected to one Master panel) and if the connection with the other panel
(also referred as “remote” panel) is lost, the following message will be displayed on LCD:
“MASTER xx FAIL” respectively “SLAVE xx FAIL”, where the xx is the ID of remote panel. This
alarm disappears if it is acknowledged and the communication with “remote” panel is restored.

1.14) NMEA output message

The Fire Alarm Panel has an RS485 interface for outputting NMEA FIR messages according
with IEC 61162-1 standard. Only the Standalone Fire Alarm Panel or the Fire Alarm Master
Panel have this interface enabled (see chapter Fire Alarm Repeater Panel).

The FIR sentence has the following format:


Title : Fire Alarm Panel Page 14 of 47
Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

$--FIR,a,hhmmss.ss,aa,cc,xxx,xxx,a,a,c--c*hh<CR><LF>

Where:

- $--FIR = message tag, $FRFIR for Fire Alarm Panel,

- a = message type:

o S - status message (summary of faulty and activated fire detector conditions),

o E – event message (status of fire detector changed),

o F – fault in system message

o D – disabled message (fire detector is disabled)

- hhmmss.ss = time of alarm condition change in UTC format; because Fire Alarm Panel
doesn’t include a UTC time information, this field is left blank,

- aa = type of fire detection system, FD (Generic fire detector) in our case

- cc = first division indicator, zone number in our case (e.g. Z2), skipped for S messages

- xxx = second division indicator, indicates the loop number where the detector is
located; the loop number is 1 for Fire Alarm Panel

- xxx = fire detector number for E messages/activation detection count for S messages,
skipped for other messages; in case of Fire Alarm Panel, the fire detector number is
always 1

- a = condition (A=Activation, V=Non-activation, X=Fault), skipped for S messages

− a = alarm’s acknowledge state (A=Alarm acknowledged, V=Alarm unacknowledged),


skipped for S or D messages
− c--c = descriptive text/sensor location tag; for the FireAlarm Panel the following format is
used:
o Status Summary – for S messages
o Detector in Zone x – for E messages (x=zone number 1…4)
o Line Fault in Zone x – for F messages (x=zone number 1...4)
o Zone x disabled – for D messages (x=zone number 1...4)
- hh – checksum

The Fire Alarm Panel is a conventional fire alarm system, not an addressable fire alarm system.
For that reason, all NMEA out messages are referring to zone status, not to detector status.
Following an example for each message type will be detailed.

Title : Fire Alarm Panel Page 15 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

1.14.1)Example of Status message


The status message (S type) is sent by Fire Alarm Panel every minute, when we have a fire alarm
or a fault in a zone. First is reported the summary status sentence, which tell us how many zones
are in alarm. After that, the detailed condition messages are reported for zones in alarm and
zones in fault.

$FRFIR,S,,FD,,,002,,,Status summary*7E
$FRFIR,E,,FD,Z1,001,001,A,A,Detector in Zone 1*5B
$FRFIR,E,,FD,Z2,001,001,A,A,Detector in Zone 2*5B
$FRFIR,F,,FD,Z3,,,,,Line fault in Zone 3*06
$FRFIR,F,,FD,Z4,,,,,Line fault in Zone 4*06


If no zone is in fire alarm, only the zone in fault info is sent as status report, the
summary status sentence (S message) and zone in alarm info (E message) being
removed from status report.

1.14.2)Example of Event message


The event message (E type) is sent by Fire Alarm Panel every time when a change is detected in
fire alarm condition of a zone. Also, the event messages are sent every minute as a part of
detailed status report if the zone is still in fire alarm.

$FRFIR,E,,FD,Z1,001,001,A,V,Detector in Zone 1*4C


$FRFIR,E,,FD,Z2,001,001,A,V,Detector in Zone 2*4C
$FRFIR,E,,FD,Z1,001,001,A,A,Detector in Zone 1*5B
$FRFIR,E,,FD,Z2,001,001,A,A,Detector in Zone 2*5B
$FRFIR,E,,FD,Z1,001,001,V,A,Detector in Zone 1*4C
$FRFIR,E,,FD,Z2,001,001,V,A,Detector in Zone 2*4C

1.14.3)Example of Fault message


The fault message (F type) is sent by Fire Alarm Panel every time when a change is detected in
fault condition of a zone. Also, the fault messages are sent every minute as a part of detailed
status report if the zone is still in fault.

$FRFIR,F,,FD,Z3,,,,,Line fault in Zone 3*06


$FRFIR,F,,FD,Z4,,,,,Line fault in Zone 4*06

1.14.4)Example of Disable message


The disable message (D type) is sent by Fire Alarm Panel every time when a zone is disabled.

$FRFIR,D,,FD,Z3,,,,,Zone 3 disabled*57
$FRFIR,D,,FD,Z2,,,,,Zone 2 disabled*57

Title : Fire Alarm Panel Page 16 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

1.15) Fire Alarm Repeater Panel

The Fire Alarm Panel can be configured as a Standalone Panel or as a part of a Master-Slave
system (one Master panel and one Repeater panel). Up to four Standalone Fire Alarm Panels
or up to two Fire Alarm Master Panels and two Fire Alarm Repeater Panels can be configured
on the same Ethernet network.
The Repeater Panel shows on LCD and status LED’s the same active fire alarms/manual call
points/faults as they are (displayed) on the Master panel. The only exceptions are the faults
which are locally processed by Repeater panel:
- Main Supply fail
- Back-up supply fail
- Ethernet link failures

Only Main & Back-up supply terminals must be connected to Repeater Panel, all the others
remain un-connected. Also, the RS-485 interface is disabled on Repeater Panel. It’s no need for
an 1131 program to be loaded in a Repeater panel and even if it’s loaded it will not be started by
the panel SW.

All operations (operator functions) which are available on Level 1 & Level 2 of security on Master
panel can be also invoked from Repeater Panel. The security level can also be changed in the
same way (see chapter Entering Operator Mode Level 2) from the Master or from Repeater
panel if the proper password is provided.
Level 2 and Level 3 passwords are shared by Master & Repeater panels but can only be
modified from Master panel via setup menu.

The Repeater panel has a reduced setup menu which can be used to control the following
operations:
- Changing of panel’s backlight and dimming levels
- Enabling/disabling of Ethernet link failures
- Panel ID setup
- Master-Slave system configuration
- Sending/receiving dimming levels to/from Ethernet
Chapter Setup and Configuration Level 3 will describe in detail the setup menus available on
Master panel and on Repeater panel.

Title : Fire Alarm Panel Page 17 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

2) Entering Operator Mode Level 2

When the operator wants to execute functions which are only allowed in operator mode Level
2, first a password has to be entered as follows:

To enter operator mode Level 2, Left Arrow and Right Arrow must be pressed at the same time,
then this screen appears in which the operator is asked to enter the password (as a sequence of
4 keys).

ENTER PASSWORD
****

The second row will start blank and an asterisk will be added for each pressed key.

When the correct sequence is entered, the following text is displayed on the LCD display as long
as Level 2 mode is active: “Level 2”.

When an incorrect sequence is entered, the following text is displayed briefly: “Incorrect
password”. Then normal operation is resumed. To prevent an operator from guessing the
password too easily, the “Incorrect password” text is not displayed when the first incorrect key is
pressed; it is displayed only after the 4th key was pressed.

Exit from Level 2 is done by pressing Arrow Left and Arrow Right pushbutton at the same time;
you go then to Level 1 mode.

Exit from level 2 is done automatically when no pushbutton is pressed for 5 minutes.

In case of a Master-Slave system, switching from Level 1 to Level 2 and back to Level 1 it’s
always possible from Master panel and it’s also possible from Repeater panel as long as
communication with Master panel is working (see chapter “Remote” panel failure).

At delivery of the Fire Alarm Panel the passwords are:

Level Defaults passwords using Arrow keys:


2 Right, Left, Right, Left
3 Left , Left, Right, Right
Supervisor 2 Right, Right, Left, Left
Supervisor 3 Left , Right, Left, Right

At delivery of the Fire Alarm Panel the default password for Level 2 is:

 Arrow Right, Arrow Left, Arrow Right, Arrow Left


The password can be changed in Level 3

Title : Fire Alarm Panel Page 18 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

3) Setup and Configuration Level 3


The system can be configured using the buttons and the LCD in Level 3 configuration mode – the
setup mode.

Normal operation is stopped when setup mode is entered, and is reinitialized when setup mode
is exited.

3.1) General usage notes

On a blank panel (a panel without a configuration), a temporary configuration with default


values is created when entering setup mode for the first time. In each setup screen, the initially-
displayed setting will be the default one.

On a non-blank panel, the existing configuration can be altered. In each setup screen, the
initially-displayed setting will be the one from the existing configuration.

The Left Arrow or Right Arrow buttons can be used to change the displayed setting. Then Panel
Reset (Ack) can be pressed to store the changed setting, or Stop Horn can be pressed to leave
the default setting unaltered. After pressing Panel Reset (Ack), the text “Stored!” is display
briefly; then the next setup screen is displayed.

To exit the setup mode and return to normal operation, Left Arrow + Right Arrow can be
pressed at the same time, from any setup screen (except where explicitly mentioned otherwise).
When exiting the setup mode this way, the altered configuration is permanently stored in the
Flash memory.

If the panel is powered down while in setup mode, no change will be written in the Flash
memory.

In the following paragraphs, unless otherwise mentioned, the setup screens are described in the
order in which they appear when the operator navigates through them.

3.2) Entering the setup mode password

The procedure to enter configuration Level 3 mode is the same by entering a password:

To enter setup mode, Left Arrow and Right Arrow must be pressed at the same time, then this
screen appears in which the operator is asked to enter the password (as a sequence of 4 keys).

ENTER PASSWORD
****

The second row will start blank and an asterisk will be added for each pressed key.

If no key is pressed for 10 seconds, the panel will automatically exit this screen and resume
normal operation.

When the correct sequence is entered, the following text is displayed briefly: “Operation Mode
Level 2” or ‘Set-Up Mode Level 3”. Then the first setup screen is displayed (where password can
be changed).
Title : Fire Alarm Panel Page 19 of 47
Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

When an incorrect sequence is entered, the following text is displayed briefly: “Incorrect
password”. Then normal operation is resumed. To prevent an operator from guessing the
password too easily, the “Incorrect password” text is not displayed when the first incorrect key is
pressed; it is displayed only after the 4th key was pressed.

Exit from Level 3 is done by pressing Arrow Left and Arrow Right pushbutton at the same time;
you go than to Level 1 mode.

Exit from Level 3 is done automatically when no pushbutton is pressed for 5 minutes.


At delivery of the Fire Alarm Panel the default password for supervisor level 3 is:
Arrow Left, Arrow Right, Arrow Left, Arrow Right
The password can be changed in Level 3

3.3) Setup screen: Change level passwords

This menu is available only for Standalone Fire Alarm Panel or for Fire Alarm Master Panel (in
case of Master-Slave system).

In this setup screen, the operator can choose to change the password. The following screen is
displayed:

Change LEVEL 2
password? <N>

The initially displayed value is N.

With the arrow buttons, the displayed value can be changed between Y and N.

If Panel Reset (Ack) is pressed while Y is displayed, a setup screen is displayed where a new
password can be introduced. If Panel Reset (Ack) is pressed while N is displayed, the next setup
screen is displayed (background illumination settings).

If Stop Horn is pressed, the setup screen for LEVEL 3 password is displayed.

3.4) Setup screen: Enter new password for level 2 and 3

This menu is available only for Standalone Fire Alarm Panel or for Fire Alarm Master Panel (in
case of Master-Slave system).

In this setup screen the password can be changed. The following is displayed:

Enter LEVEL 2
password:

The password length is 4 keys, so the panel will wait for the operator to press any 4 keys. An
asterisk will be added to the second line with each key press.

Title : Fire Alarm Panel Page 20 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

After the 4th key has been pressed, the new password is stored and the text “Password
changed” is displayed briefly, then the setup screen for LEVEL 3 password is displayed. After that
the background illumination settings menu starts.

3.5) Setup screen: Background illumination level and Maximum dimming level

In this setup screen the background illumination level and the maximum dimming level for
buttons can be adjusted both at the same time.

 Fire Alarm lamps and LED will illuminate full if a fire alarm occurs.

To give a better idea of how the illumination looks like, half of the buttons are illuminated at
background level (simulating “off” buttons), and the other half are illuminated at dimming level
(simulating “on” buttons). The operator can adjust both levels with the arrow buttons, and this
will immediately be reflected in the illumination of the buttons. Stop Horn can be used to toggle
what should be adjusted: background or dimming. When both levels are set at the desired
levels, Panel Reset (Acknowledge) can be pressed for going to the next setup screen.

Upon entering this setup screen, the illumination of the buttons on the left half of the front
panel is set at the currently-configured background illumination level, and the illumination of the
buttons on the right half of the front panel is set at the currently-configured maximum dimming
level. If the panel is blank, the background is set to 10% and the dimming is set to 30% (=70%
brightness).

The following text is displayed:

Adjust bkgnd
(StopHorn-dim)

When the arrow keys are pressed, the background illumination level is adjusted between 0%
and 20%, in increments of 5%; the illumination of the “off” buttons (1, 3, 5 etc) is also adjusted
accordingly.

If Panel Reset (Ack) is pressed the currently-selected settings are stored, the illumination for all
buttons is set to the background level, and the next setup screen is displayed.

If Stop Horn is pressed the following text is displayed:

Adjust dimming
(StopHorn–bkgnd)

When the arrow keys are pressed, the dimming level is adjusted between 0% dimming (=100%
brightness) and 80% dimming (=20% brightness), in increments of 5%; the illumination of the
“on” buttons (2, 4, 6 etc) is also adjusted accordingly.

Although the background brightness can be set as high as 20% and the dimmed brightness can
be set as low as 20%, the panel will always keep a 20% “distance” between the two brightness
levels. If, for instance, the operator sets the background brightness to 15%, the panel will force

Title : Fire Alarm Panel Page 21 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

the dimmed brightness to at least 35%. If the operator sets the dimmed brightness to 25%, the
panel will force the background brightness to at most 5%.

If Panel Reset (Ack) is pressed the currently-selected settings are stored, the illumination for all
buttons is set to the background level, and the next setup screen is displayed.

If Stop Horn is pressed, the text “Adjust backgnd” is displayed again, and the operator can
continue to adjust both settings.

3.6) Setup screen: FireAlarm LED dimming

Fire Alarm lamps and LED will illuminate full if a fire alarm occurs. The dimmed status of the fire
alarm lamps and LED will only be used after the user has pressed the ‘Stop Horn’ button while
the sensor is still giving a fire alarm. In the setup screen the following text is displayed:

Adjust FireAlarm LED


DIMMING

With the arrow buttons the dimming can be adjusted between 0% dimming (=100% brightness)
and 80% dimming (=20% brightness), in increments of 5%.

With the Panel Reset (Ack) button the current setting is stored and the next setup screen is
displayed.

With the Stop Horn button the current setting is discarded, the previously-configured setting is
retained, and then the next setup screen is displayed.

 Fire Alarm lamps and LED will illuminate full if a fire alarm occurs.

3.7) Setup screen: LED dimming

The following text is displayed:

Adjust LED
DIMMING

With the arrow buttons the dimming can be adjusted between 0% dimming (=100% brightness)
and 80% dimming (=20% brightness) with increments of 5%.

With the Panel Reset (Ack) button the current setting is stored and the next setup screen is
displayed.

With the Stop Horn button the current setting is discarded, the previously-configured setting is
retained, and then the next setup screen is displayed.

3.8) Setup screen: Adjust backlight

The following text is displayed:

Title : Fire Alarm Panel Page 22 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

Adjust
backlight

With the arrow buttons the dimming can be adjusted between 0% dimming (=100% brightness)
and 80% dimming (=20% brightness) with increments of 5%.

With the Panel Reset (Ack) button the current setting is stored and the next setup screen is
displayed.

With the Stop Horn button the current setting is discarded, the previously-configured setting is
retained, and then the next setup screen is displayed.

3.9) Setup screen: Dimming of the LCD

This is the illumination level that is used for the LCD when alarms are displayed.

Upon entering this setup screen, the illumination of the LCD is set to the currently-configured
level. If the panel is blank, the illumination is set to 100% (no dimming).

The following text is displayed:

ADJUST LCD
DIMMING

With the arrow buttons the dimming can be adjusted between 0% dimming (=100% brightness)
and 80% dimming (=20% brightness) in increments of 5%.

With the Panel Reset (Ack) button, the current setting is stored and the next setup screen is
displayed.

With the Stop Horn button, the current setting is discarded, the previously-configured setting is
retained, and then the next setup screen is displayed.

3.10) Setup screen: link alarms

The following text is displayed:

Enable LINK DOWN


alarms <Y>

Default is Yes. With the arrow buttons the displayed value can be changed between Y (Yes) and
N (No).

With the Panel Reset (Ack) button the current setting is stored and the next setup screen is
displayed.

With the Stop Horn button, the current setting is discarded, the previously-configured setting is
retained, and then the next setup screen is displayed.

Title : Fire Alarm Panel Page 23 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

3.11) Setup screen: Panel ID

The panel ID can be changed here. The initially-displayed ID is the previously-configured one. If
there is no previous configuration, the initially-displayed ID is 41.

The following text is displayed:

Panel ID: <41>

With the arrow buttons the value can be increased/decreased within the limits 41 (inclusive)
and 44 (inclusive).

With the Panel Reset (Ack) button the currently-displayed ID is stored, and then the next setup
screen is displayed.

With the Stop Horn button the currently-displayed ID is discarded, and the previously-
configured ID is retained, then the next setup screen is displayed.

The Panel ID for various types of panels is listed below for informational purposes:

− Alarm Panel 1 to 12 (max 12 units);


− Group Alarm Panel 13 to 16 (max 4 units);
− Navigation Light Control Panel33 to 36 (max 4 units);
− Wiper Control Panel 37 to 40 (max 4 units);
− Fire Alarm Panel 41 to 44 (max 4 units);
− BNWAS Panel 45 to 48 (max 4 units);
− LCD Operator Panel 64 to 80 (max 16 units).

(The LCD Operator Panel includes the Battery Monitoring Panel, the PMS Control Panel, and the
Tank Monitoring Panel.)

In case of a Master-Slave system, ID’s 41 and 42 are reserved for Master panel and ID’s 43 and
44 are reserved for Repeater panel.

3.12) Setup screen: Master-Slave system

The system type can be changed here. The options are: Master-Slave system or Standalone
panel. The initially-displayed system type is the previously-configured one. If there is no previous
configuration, the initially-displayed system type is Standalone panel.

The following text is displayed:

Is MASTER-SLAVE

system? <N>

Pressing Left Arrow or Right Arrow will change the displayed option between “Y” and “N”. If the
option is “N” then is a Standalone panel and if the option is “Y” then is a part of a Master-Slave
system. In this case the previously configured panel ID determine if it is a Master panel (for 41 or
42 panel ID) or a Repeater Panel (for 43 or 44 panel ID). Next setup menu selects the ID of the
remote panel (“paired” panel), see chapter Setup screen: Remote panel ID.
Title : Fire Alarm Panel Page 24 of 47
Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

Pressing Panel Reset (Ack) will store the currently-displayed option.

Pressing Stop Horn will discard the currently-selected option and will retain the previously-
configured option.

3.13) Setup screen: Remote panel ID

If the panel is part of a Master-Slave system, the ID of the remote panel (“paired” panel) can be
changed here. The initially-displayed ID is the previously-configured one. If there is no previous
configuration, the initially-displayed ID is “none”.

The following text is displayed if the panel is a Master panel (panel ID is 41 or 42):

Slave panel: <43>

Or the following text if the panel is a Repeater panel (panel ID is 43 or 44),

Master panel: <41>

With the arrow buttons the value can be adjusted accordingly:

- If the panel is Master panel, available options for (remote) Slave panel ID are: None, 43,
44.

- If the panel is Slave panel, available options for (remote) Master panel ID are: 41, 42.

With the Panel Reset (Ack) button the currently-displayed ID is stored, and then the next setup
screen is displayed.

With the Stop Horn button the currently-displayed ID is discarded, and the previously-
configured ID is retained, then the next setup screen is displayed.

3.14) Setup screen: NMEA communication speed

This menu is available only for Standalone Fire Alarm Panel or for Fire Alarm Master Panel (in
case of Master-Slave system).

In this screen the communication speed for NMEA output interface is adjusted. The initially-
displayed NMEA speed is the previously-configured one. If there is no previous configuration,
the initially-displayed NMEA speed is 4800 bps.

The following text is displayed:

NMEA Speed:

<4800> bps

With the arrow buttons the value can be adjusted to 4800, 9600 or 19200 bps.

With the PANEL RESET button the currently-displayed NMEA speed is stored, and then the next
setup screen is displayed.

Title : Fire Alarm Panel Page 25 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

With the STOP HORN button the currently-displayed speed is discarded, and the previously-
configured NMEA speed is retained, then the next setup screen is displayed.

3.15) Setup screen: Synchronizing dimming level between Control Panels

During normal operation the operator can increase/decrease the dimming level. It might be
desirable to set the dimming level for multiple panels at once from a single location. This
synchronization can be turned on or off here.

The following is displayed:

Send dimming
to bus? <Y>

Pressing Left Arrow or Right Arrow will change the displayed option between “Y” and “N”.

Pressing Panel Reset (Ack) will store the currently-displayed option.

Pressing Stop Horn will discard the currently-selected option and will retain the previously-
configured option.

Then the following screen is displayed:

Receive dimming
from bus? <Y>

The buttons have the same usage as above.

 Background illumination is set for each panel individually in set-up mode.

3.16) Setup screen: Fault handling options

o In case of Fault: internal buzzer only or internal buzzer + Siren output activated.
Default: Internal buzzer and Siren output activated

o Stop Horn for Fault allowed in Level 2 or in Level 1+2 or Automatic. Default: Level
2

o Panel Reset for Fault allowed in Level 2 or in Level 1+2 or Automatic. Default: Level
2

This menu is available only for Standalone Fire Alarm Panel or for Fire Alarm Master Panel (in case
of Master-Slave system).

3.17) Setup screen: Fire Alarm handling options

o Stop Horn for Fire Alarm allowed in Level 2 or in Level 1+2. Default: Level 2

This menu is available only for Standalone Fire Alarm Panel or for Fire Alarm Master Panel (in case
of Master-Slave system).

Title : Fire Alarm Panel Page 26 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

3.18) Setup screen: Fire Alarms Relay timeout

This menu is available only for Standalone Fire Alarm Panel or for Fire Alarm Master Panel (in
case of Master-Slave system).

The following text is displayed:

FireAlarm relay
timeout <60>s

Default is 60 seconds. With the arrow buttons the displayed value can be changed between 0
and 120 seconds with intervals of 1 second.

With the Panel Reset (Ack) button the current setting is stored and the next setup screen is
displayed.

With the Stop Horn button the current setting is discarded, the previously-configured setting is
retained, and then the next setup screen is displayed.

3.19) Setup screen: Siren output delay

This menu is available only for Standalone Fire Alarm Panel or for Fire Alarm Master Panel (in
case of Master-Slave system).

The following text is displayed:

Siren output
delay <60>s

Default is 60 seconds. With the arrow buttons the displayed value can be changed between 0
and 120 seconds with intervals of 1 second.

With the Panel Reset (Ack) button the current setting is stored and the next setup screen is
displayed.

With the Stop Horn button the current setting is discarded, the previously-configured setting is
retained, and then the next setup screen is displayed.

3.20) Setup screen: Zone location

This menu is available only for Standalone Fire Alarm Panel or for Fire Alarm Master Panel (in
case of Master-Slave system).

The following text is displayed:

Zone2 location
<General area>

Default option is “General area”. With the arrow buttons the displayed value can be changed
between “General area” and “Machinery area”. If zone location is “Machinery area”, then any
fire detector from this zone which coming in alarm state will trigger the siren output at once,

Title : Fire Alarm Panel Page 27 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

without siren output delay. Detectors from “General area” zones will trigger the siren output in
case of fire alarm after the siren output delay elapsed.

Selected zone is shown on screen with the text “ZoneN”, where N=1...4 is the zone number.
Selected zone is also indicated by switching ON the corresponding Zone lamp LED (red).

With the Panel Reset (Ack) button the current zone location of selected zone is stored and the
next zone is selected. If no zones are to be selected anymore, then the next setup screen is
displayed.

With the Stop Horn button the current zone location of selected zone is discarded, the previously-
configured setting is retained, and the next zone is selected. If no zones are to be selected
anymore, then the next setup screen is displayed.

3.21) Setup screen: Manual Call Point resistance

This menu is available only for Standalone Fire Alarm Panel or for Fire Alarm Master Panel (in
case of Master-Slave system).

The following text is displayed:

MCP Rvalue
<266> Ohm

Default option is “266 ohm”. With the arrow buttons the displayed value can be changed
between “266 ohm” and “470 ohm”.

If selected option is “266 ohm” then the Fire Alarm panel will be able to detect a sensor in alarm
regardless of their family (Tyco series 65, Apollo Orbis series or Consilium), but will detect
manual call points only if resistance of manual call point is 266 ohm (for some manual call points
will be necessary to replace the default built-in resistor with a 266 ohm resistor).

If selected option is “470 ohm” then the Fire Alarm panel will be able to detect a sensor in alarm
only if it’s an Apollo Orbis series detector and will detect manual call points only if resistance of
manual call point is 470 ohm (which is the default built-in resistor used by Apollo manual call
points).

With the Panel Reset (Ack) button the current manual call point resistance value is stored and
then the next setup screen is displayed.

With the Stop Horn button the current manual call point resistance value is discarded, the
previously-configured setting is retained, and the next setup screen is displayed.

Title : Fire Alarm Panel Page 28 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

4) Save and load configurations to/from USB drive


During normal operation, if an USB drive is inserted, the panel will stop the normal operation
and will enter USB Load/Save mode.

4.1) Save 1131 program to USB drive

The following will be displayed if the panel has an 1131 program:

Save VM File
to USB drive?

This screen is skipped if the panel does not have a valid 1131 program.

If Panel Reset (Ack) is pressed the 1131 program will be saved to the root directory of USB drive,
under the name VM_XX.XCP. The characters XX are replaced by the panel ID. Any existing file
with the same name will be overwritten.

4.2) Load 1131 program from USB drive

The following will be displayed if the USB drive holds an 1131 program:

Load VM File XX
from USB drive?

This screen is skipped if the USB drive does not have a valid 1131 program (a 1131 program
stored in VM_XX.XCP file, where XX can be 41…44).

If Panel Reset (Ack) is pressed the 1131 program will be saved to the panel.

4.3) Save configuration to USB drive

The following will be displayed if the panel has a configuration:

Save config
to USB drive?

This screen is skipped if the panel does not have a configuration. The screen in next paragraph is
also displayed if Stop Horn is pressed.

If Panel Reset (Ack) is pressed, the configuration will be saved to the USB drive, in the root
directory, under the name FALR_XX.CFG, where XX is panel ID. Any existing file with the same
name will be overwritten.

The panel will exit USB mode and will restart normal operation if the USB drive is unplugged.

4.4) Load configuration from USB drive

In this step the panel will look for valid configuration files in the root directory of the USB drive.
A valid configuration file has a filename of the form FALR_XX.CFG (where XX is the panel ID). It

Title : Fire Alarm Panel Page 29 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

also has an internal signature, to prevent random files renamed as FALR_XX.CFG to be


interpreted as configuration files.

The following will be displayed on the LCD:

Load
<FALR_XX.CFG>?

XX is the panel ID of a configuration file which was found in the root directory.

If Right Arrow is pressed, the panel will look for the next valid configuration file and will display
its corresponding ID. If Left Arrow is pressed, the panel will look for the previous valid
configuration file and will display its ID.

If Panel Reset (Ack) is pressed the selected configuration file is loaded and immediately stored in
the Flash memory. Then the panel will restart normal operation.

If Stop Horn is pressed the file will not be loaded and the old configuration will remain in the
Flash memory. Then the panel will restart normal operation.

The panel will exit USB mode and will restart normal operation if the USB drive has been
removed.

Title : Fire Alarm Panel Page 30 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

5) Ethernet communication with other panels


For Standalone panels the Ethernet communication has only one purpose: sending the backlight
dimming level to other panels when the operator changes it on one panel.

For Master-Slave systems (see chapter Fire Alarm Repeater Panel) the Ethernet communication
is also used to synchronize the Master and Repeater panels.

Each panel has two Ethernet ports, and redundancy is ensured by connecting all panels in an
Ethernet ring. One of the panels normally “splits” the ring in order to prevent loops. When one
Ethernet cable is interrupted, or when one panel is malfunctioning or missing, the splitting is
automatically removed, so all the panels will continue to see each other.

Title : Fire Alarm Panel Page 31 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

6) Software upgrades using the USB drive


Software upgrades can be done using the USB bootloader on the panel.

The USB bootloader is capable of upgrading the following pieces of software:

1. Panel USB bootloader (self-upgrade);


2. Panel firmware;

The software must always be upgraded in the order given above, always to the most recent
versions received from Praxis, otherwise the panel might enter an irrecoverable state, after
which only the serial bootloader can be used for writing software.

1. The panel might not recognize a USB drive that has too many files/directories
in the root directory. Make sure you are using a USB drive with at most 10-20
 files/directories in the root directory.
2. Older firmware versions don’t recognize certain types of USB sticks. If you
have problems with a USB stick, try another one.

6.1) Panel USB Bootloader upgrade

The USB bootloader can be started by keeping the ACK button pressed during panel power-up.
After the bootloader starts, and before a USB drive is inserted, the version number of the
existing panel bootloader is displayed on the LCD. The upgrade process is described below.

For panels and already programmed with old software, the upgrade process is slightly different.

The bootloader upgrade process sometimes deletes the panel configuration (the

 settings made in setup mode). If you intend to keep the panel configuration, save it to
a USB drive before upgrading the bootloader, then upgrade the bootloader, then
upgrade the firmware, and then load the configuration back from the USB drive.

6.1.1) Upgrading the panel USB bootloader for panels that are already programmed with panel
bootloader versions older than 1.21.0.0
Currently, the panel cannot be upgraded if it has an USB bootloader older than 1.21.0.0.

Only the serial bootloader can be used for this.

6.1.2) Upgrading the panel USB bootloader for panels that are already programmed with panel
bootloader versions 1.21.0.0 or higher

Title : Fire Alarm Panel Page 32 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

The panel bootloader can be upgraded as follows:

Put the Panel USB bootloader file on a USB drive (USB hard-disk or USB memory stick), in
the root directory. The bootloader file has this filename:
o UniversalUsbBootloader.bin
− Start the bootloader on the panel (by keeping PANEL RESET (ACK) pressed during
power-up).
− Insert the USB drive. Within a few seconds, you are prompted with Update panel
bootloader? Answer Yes by pressing PANEL RESET (ACK).
− The panel starts start looking for binary files in the root directory, and will display the
name of the first file it finds (on the first row), together with a few details about the
file (on the second row). The filename is truncated to 8.3 DOS filename format; this
is a limitation of the software. Here you can:
o Press LEFT / RIGHT to see different details on the second row. You can see
the following (not necessarily in this order):
▪ The binary type name. For the USB bootloader, this is “CPL-BL-USB”.
Don’t load a file whose binary type name is different.
▪ The panel type name. For the USB bootloader, this is “ALL-PANELS”.
▪ The release version of the bootloader file, with the form X.Y.Z.W. This
must be the latest version you received from Praxis.
o Press PANEL RESET (ACK) to load the bootloader from the USB drive and
write it into the panel.
o Press STOP HORN to go to the next binary file from the root directory.
− Once you found your bootloader file, press PANEL RESET (ACK) to load it on the
panel. The update process takes a few seconds, and then the panel restarts itself and
the new bootloader executes.

Title : Fire Alarm Panel Page 33 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

6.2) Panel Firmware Upgrade

The firmware can be upgraded as follows:

Put the firmware file on a USB drive (USB hard-disk or USB memory stick), in the root
directory. The firmware file has a name such as
Fire-AP-RevB-Firmware.bin.
− Start the USB bootloader on the panel (by keeping PANEL RESET (ACK) pressed
during power-up).
− Make sure the panel is already running the latest version of the USB bootloader. You
can check this by starting the bootloader without inserting the USB drive: the
bootloader version is displayed on the LCD. This must be the latest version received
from Praxis.
− Insert the USB drive. Within a few seconds, you are prompted with Update panel
bootloader? Answer No by pressing STOP HORN.
− You are prompted with Update panel firmware? Answer Yes by pressing PANEL
RESET (ACK).
− The panel starts looking for binary files in the root directory, and will display the
name of the first file it finds (on the first row), together with a few details about the
file (on the second row). Note that the filename is truncated to 8.3 DOS filename
format; this is a limitation of the software. Here you can:
o Press LEFT / RIGHT to see different details on the second row. You can see
the following (not necessarily in this order):
▪ The binary type name. For the firmware, this is “CPL-FW”. Don’t load
a file whose binary type name is different.
▪ The panel type name. For the Fire-Alarm Panel, this is “FIRE-AP”.
Don’t load a file whose panel type name is different.
▪ The hardware revisions recognized by the firmware file.
▪ The release version of the firmware file, with the form X.Y.Z.W. This
must be the latest version you received from Praxis.
o Press PANEL RESET (ACK) to load the firmware from the USB drive and write
it into the panel.
o Press STOP HORN to go to the next binary file from the root directory.
− Once you found your firmware file, press PANEL RESET (ACK) to load it on the panel.
The update process takes a few seconds, the panel will inform you when the update
process has finished.
− Remove your USB drive and reboot the panel.

Title : Fire Alarm Panel Page 34 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

7) Hardware Specifications
8) Connection Drawings and Project Engineering
Drawings can be divided in two groups:

- Projects drawings; as part of the Engineering work.

o Project drawings include the text sheet for zone description as adapted for the
particular vessel. .

o The Fire Alarm Panel has to be set-up (see chapter 3) in accordance with the
requirements of the particular vessel.

Engineering work and project drawings are not included in the scope of supply of a
Fire Alarm Panel.

An example project drawing is part of this manual.

- Standard drawings; these are standard mounting, dimension and connection drawings
which are applicable for all vessels. These drawings are part of this manual.

Title : Fire Alarm Panel Page 35 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

8.1) Example Project drawings

Title : Fire Alarm Panel Page 36 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

Title : Fire Alarm Panel Page 37 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

8.2) Standard drawings

Title : Fire Alarm Panel Page 38 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

Title : Fire Alarm Panel Page 39 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

Title : Fire Alarm Panel Page 40 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

9) Maintenance
Unless specified otherwise the annual check of below checks applies.

Panel software version: __.__.__.__

9.1) System status checks

1 System healthy start-up Comments


1.1 System status
• Verify panel LED “System On” on [ ] OK
• Verify panel LED “Main Supply Fail” off [ ] OK
• Verify panel LED “Backup Supply Fail” off [ ] OK
• Verify panel LED “Fire Alarm” off (all zones) [ ] OK

• Verify panel LED “Earth Failure” off [ ] OK

• Verify panel LED “General Fault” off [ ] OK

• Verify panel LED “Siren Output Fail” off [ ] OK

• Verify panel LED “Fault” off [ ] OK

• Verify panel display no alarms [ ] OK


[ ] OK
• Verify “Siren” output Positive Voltage
[ ] OK
• Verify “Fail” output Normally Closed
[ ] OK
• Verify “Fire” output Normally Closed

2 System testing Comments


2.1 Panel LED Test (Buttons Ack. + Stop Horn)
• Verify LED indication on the control panel [ ] OK
2.2 Panel dimming (Buttons “<” or “>”)
• Verify panel dimming [ ] OK

Title : Fire Alarm Panel Page 41 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel
3 Fire Alarm testing – fire detector Comments
3.1 Simulate fire detector alarm
• Verify LED “Fire Alarm Acc.” on [ ] OK
• Verify LED “Fire Alarm” on [ ] OK
• Verify Panel alarm message [ ] OK
• Verify Panel Horn [ ] OK

• Verify “Siren” output negative Voltage [ ] OK

3.2 Wait for siren output delay


• Verify “Fire” output Normally Open [ ] OK
After delay (can be set for 0 ~ 180 sec)
• Verify Acknowledgement (with password) [ ] OK
• Verify Stop Horn [ ] OK
3.3 Reset fire alarm
• Verify no Panel alarm message [ ] OK

4 Fire Alarm testing – manual call point Comments


4.1 Simulate manual call alarm
• Verify LED “Fire Alarm Acc.” on [ ] OK
• Verify LED “Fire Alarm” on [ ] OK
• Verify Panel alarm message [ ] OK
• Verify Panel Horn [ ] OK

• Verify “Siren” output negative Voltage [ ] OK

• Verify “Fire” output Normally Open (No [ ] OK


delay)
• Verify Acknowledgement (with password) [ ] OK
• Verify Stop Horn [ ] OK
4.2 Reset fire alarm
• Verify no Panel alarm message [ ] OK

Title : Fire Alarm Panel Page 42 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

9.2) Failure test

1 Wire Break Test Comments


1.1 Simulate siren output wire break
Disconnect wire of siren output
• Verify Panel alarm message [ ] OK
• Verify LED “Siren Output Fail” on [ ] OK
• Verify LED “General Fault” on [ ] OK
• Verify “Fail” output Normally Open [ ] OK

• Verify Acknowledgement [ ] OK

• Verify Stop Horn [ ] OK

1.2 Reset siren output wire break


• Verify no Panel alarm message [ ] OK
1.3 Simulate fire detector wire break
Disconnect wire of a fire detector
• Verify Panel alarm message [ ] OK
• Verify LED “Line Fault” on [ ] OK
• Verify LED “General Fault” on [ ] OK
• Verify “Fail” output Normally Open [ ] OK

• Verify Acknowledgement [ ] OK

• Verify Stop Horn [ ] OK

1.4 Reset fire detector wire break


• Verify no Panel alarm message [ ] OK
1.5 Simulate fire detector short circuit
Disconnect wire of a manual call point
• Verify Panel alarm message [ ] OK
• Verify LED “Line Fault” on [ ] OK
• Verify LED “General Fault” on [ ] OK
• Verify “Fail” output Normally Open [ ] OK

• Verify Acknowledgement [ ] OK

• Verify Stop Horn [ ] OK

1.6 Reset manual call point wire break


• Verify no Panel alarm message [ ] OK

Title : Fire Alarm Panel Page 43 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel
2 Power Redundancy Panel Comments
2.1 Simulate main supply failure
Switch off main supply
• Panel operate on backup supply [ ] OK
• LED “Main Supply Fail” on [ ] OK
• Alarm message [ ] OK
• Verify “Fail” output Normally Open [ ] OK

• Verify Acknowledgement [ ] OK

• Verify Stop Horn [ ] OK

2.2 Restore main supply


Simulate backup supply failure
Switch off backup supply
• Panel operates on main supply [ ] OK
• LED “Main Supply Fail” on [ ] OK
• Alarm message [ ] OK
• Verify “Fail” output Normally Open [ ] OK

• Verify Acknowledgement [ ] OK

• Verify Stop Horn [ ] OK

3 Panel Failure and Recovery Comments


3.1 Simulate Panel failure
Switch off panel power
• Verify “Fail” output Normally Open [ ] OK
3.3 Panel recovery
Switch on panel power
• Verify panel start-up recovery [ ] OK
• Verify “Fail” output Normally Closed [ ] OK

Title : Fire Alarm Panel Page 44 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

9.3) Earth Fault

1 Panel Earth Fault Alarm Comments


1.1 Simulate Earth Fault
• Verify Panel alarm message [ ] OK
• Verify LED zone “Earth Failure” on [ ] OK
• Verify LED “General” on [ ] OK
• Verify “Fail” output Normally Open [ ] OK

1.3 Reset Earth Fault


• Verify no Panel alarm message [ ] OK

Title : Fire Alarm Panel Page 45 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

10) Mini-Guard, Maxi-Guard and Mega-Guard E-Series


The Fire Alarm Panel can be applied in the E-Series of Mini-Guard, Maxi-Guard, and Mega-Guard
product line.

Title : Fire Alarm Panel Page 46 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx
MEGA-GUARD Ship Automation and Navigation System
Operator Guide – Fire Alarm Panel

11) Naming conventions and company information

Naming Conventions:
Name of the Product Line: E Series of Mini-Guard, Maxi-Guard, Mega-Guard
Product Name Fire Alarm Panel

Company Information:
Company Name: Praxis Automation Technology
Company Address: Zijldijk 24A
Company Zipcode: 2352 AB
Company City: Leiderdorp
Company Country: The Netherlands
Company Phone: (31) 71-5255353
Company Fax: (31) 71-5224947
Company E-Mail: info@praxis-automation.nl

Title : Fire Alarm Panel Page 47 of 47


Date : 20 Nov 2020
File : PTD-Fire-Alarm-Panel-R1.23.docx

You might also like