Professional Documents
Culture Documents
Short-Circuit Calculations: 4.1 Symmetrical Components
Short-Circuit Calculations: 4.1 Symmetrical Components
Short-Circuit Calculations: 4.1 Symmetrical Components
Short-Circuit Calculations
4.1 Symmetrical Components
Symmetrical components are the traditional method used to calcu-
late short-circuit currents and voltages for AC power systems. Dr. C. L.
Fortescue developed this method while investigating problems of single-
phase railway systems in 1918. Symmetrical components allow the use of
single-phase “loop” or “node” equations to develop short-circuit currents
and voltages on single-phase, two-phase, or three-phase systems. The big
advantage of symmetrical components is the elimination of the need to
include transformer turns ratios and winding connections in calculations.
(Transformer data is used to develop base values and to incorporate phase
shifts into calculations.)
Three-phase loop or node equations can be used to calculate short-circuit
values on simple power systems (one machine, one line, one transformer).
However, for the typical power system, loop and node equations become
unwieldy, even with today’s computing capability, because transformer
turns ratios and transformer winding connections need to be included
when traditional loop (Kirchoff’s Laws) and node (Norton’s Laws) calcula-
tions are used for circuit analysis.
When unusual power system configurations, such as a single-phase
transformer connected line-to-line on the primary and line-to-ground on
the secondary, are addressed, it is a good idea to use symmetrical compo-
nents to calculate short-circuit values and loop or node equations to verify
the results.
The fundamental principles of symmetrical components are as follows:
57
© 2009 by Taylor & Francis Group, LLC
58 Protective Relay Principles
Generator 1
320 MVA, 23 KV Generator 2
Xd = 18.5% 410 MVA, 13.8 KV
Xd´ = 52.3% Xd = 20.2%
Xd = 104% Xd´ = 56.4%
Bus 1 Bus 2
Xd = 108%
Z1L = 1.7 + j 19.0 Ω
Z0L = 15.1 + j 62.8 Ω
Transformer 1 Transformer 2
300 MVA, 23–230 KV 400 MVA, 13.8–230 KV
X = 12.35% X= 13.21%
23 KV: ∆ 13.8 KV: ∆
230 KV: Y-Grd 230 KV: Y-Grd
Figure 4.1
One-line diagram showing transformer connections and component impedances.
Bus 1 Bus 2
Z1 Gen 1 Z1 Gen 2
RB1 RB1
Z1 Trans 1 Z1 Line Z1 Trans 2
Figure 4.2
Positive sequence network for the system shown in Figure 4.1.
reference bus, RB1, the common point to which one terminal of all power
sources in the positive sequence are connected, is needed for network
analysis.
Bus 1 Bus 2
Z2 Gen 1 Z2 Gen 2
Figure 4.3
Negative sequence network for the system shown in Figure 4.1.
Bus 2
Z0 Gen 1 Z0 Gen 2
Figure 4.4
Zero sequence network for the system shown in Figure 4.1.
4.5 Operators
Symmetrical components utilize a unit vector, designated “a”, to trans-
form phase quantities to sequence quantities and to transform sequence
quantities to phase quantities.
a0 = 1 @ 0°
a1 = 1 @ 120° = –.5 + j.866
a2 = 1 @ 240° = –.5 – j.866
a3 = 1 @ 360° = a
a2 – a = 1 @ 240° – 1 @ 120° = –j√3 = √3 @ –90°
a – a2 = 1 @ 120° – 1 @ 240° = j√3 =√3 @ 90°
1 + a + a2 = 1 + 1 @ 120° + 1 @ 240° = 0
Ea1 = 1/3 (Ea + aEb + a2Ec) Ia1 = 1/3 (Ia + aIb + a2Ic)
Ea2 = 1/3 (Ea + a2Eb + aEc) Ia2 = 1/3 (Ia + a2Ib + aIc)
Ea0 = 1/3 (Ea + Eb + Ec) Ia0 = 1/3 (Ia + Ib + Ic)
Ec1
Ea1 = Ea1
Eb1 = a2Ea1 = Ea1 @ 240° Ea1
Ec1 = aEa1 = Ea1 @ 120°
Eb1
Figure 4.5
Positive sequence voltage vectors.
Eb2
Ea2 = Ea2
Eb2 = aEa2= Ea2 @ 120° Ea2
Figure 4.6
Negative sequence voltage vectors.
Ea0 = Ea0
Eb0 = Ea0
Ec0 = Ea0
Ea0
Ea0
Ec0
Figure 4.7
Zero sequence voltage vectors.
Bus 1 Bus 2
RB1 Z1 Gen 1 Z1 Gen 2 RB1
Figure 4.8
Positive sequence network for a three-phase fault at Bus 1.
Bus 1 Bus 2
RB1 Z1 Gen 1 Z1 Gen 2 RB1
Z1 Trans 1 Z1 Line I1
X Z1 Trans 2
Figure 4.9
Positive sequence network for a three-phase fault at Bus 2.
Bus 1
RB1
RB1
I1
Z1 Trans 1 X Z1 Line Z1 Trans 2
Bus 1 Bus 2
Z2 Gen 1 X Z2 Gen 2
I2
Figure 4.10
Positive and negative sequence networks for a phase-to-phase fault at Bus 1.
4.9 Per-Unit Quantities
When developing power system calculations, per-unit quantities are used
because per-unit quantities are simpler to use than amperes, ohms, and
volts. (Percent quantities are per-unit quantities multiplied by 100.) This is
Bus 1 Bus 2
Z1 Gen 1 Z1 Gen 2
RB1 I1 RB1
Z1 Trans 1 X Z1 Line Z1 Trans 2
Bus 1 Bus 2
Z2 Gen 1 Z2 Gen 2
RB2 I2 RB2
Z2 Trans 1 X Z2 Line Z2 Trans 2
Bus 1 Bus 2
Z0 Gen 1 Z0 Gen 2
RB0 I0 RB0
Z0 Trans 1 X Z0 Line Z0 Trans 2
RB0 RB0
Figure 4.11
Positive, negative, and zero sequence networks for a phase-to-ground fault at Bus 1.
due to the fact that per-unit quantities can be manipulated for transformer
turns ratios or connections after circuit analysis has been completed.
Therefore, all impedances, currents, and voltages are converted to per-
unit quantities using the following rules.
Base Impedance =
Base MVA
KV 2 (given )
pu (new) = pu (given) ×
KV 2 ( new)
4.10 Sample Calculations
Using the information presented in Figure 4.1, short-circuit currents
will be calculated through the use of symmetrical components and per
unit impedances.
The base MVA will be 100 MVA (100 MVA is closer to the generator and
transformer MVA ratings in Figure 4.1 than is 10 MVA) and base voltages
will be 230 KV for the transmission system, 23 KV for Generator 1, and
13.8 KV for Generator 2.
One of the first steps is to place all impedances on a common, 100 MVA
base. For transformers and generators, this is accomplished by normal-
izing published values:
{
I 3 ϕ = 251 ÷ j.058 + j.041 .003 + j.036 + j.033 + j.049}
I3ϕ = 251 ÷ {.099 ∠90° .118 ∠88.5°}
System voltages, phase to neutral, can be calculated using per unit, per-
cent, or ohmic impedances. Phase-to-phase voltages are calculated after
phase-to-neutral voltages have been determined. In this calculation, the
Figure 4.12
Positive sequence network for a three-phase fault at Bus 1.
For three-phase faults, phase current and voltage are balanced; there-
fore, voltage and current magnitudes apply to all three phases.
I1
Z1 Trans 1 X Z1 Line Z1 Trans 2
j.041 .003 + j.036 j.033
Figure 4.13
Positive and negative sequence networks for a phase-to-phase fault at Bus 1.
100 MVA
Ia1 = Ia 2 = Ia0 =
3 × 230 KV × (Z1 + Z 2 + Z 0 )
Ia1 = 251 ÷ { 0.054 ∠89.3° + 0.054 ∠89.3° + (j.041 0.028 + j.119 + j.033)}
Ia1 = 251 ÷ {0.054 ∠89.3° + 0.054 ∠89.3° + 0.032∠87.8°}
Ia1 = 251 ÷ 0.1140∠89°
Ia1 = 1790 amps ∠–89° Ia2 = 1790 amps ∠–89° Ia0 = 1790 amps ∠–89°
Ia1 = 7.13 pu ∠–89°
Iφg = Ia1 + Ia2 + Ia0 = 3 × 1790 amps ∠–89° = 5372 amps ∠–89°
3I0 Gen 1 source = 5372 amps ∠–89° × 0.155 ∠79.6° ÷ 0.193 ∠81.7° =
4258 amps ∠–91.7°
3I0 Gen 2 source = 5372 amps ∠–89° × 0.041 ∠90° ÷ 0.193 ∠81.7° =
1129 amps ∠–80.7°
Note that for three-phase faults, the division of current is 55% from
Generator 1 source and 45% from Generator 2 source, but for single phase-
to-ground faults, the division of current is 79% from Generator 1 source
and 21% from Generator 2 source.
When calculating phase voltages for phase-to-ground faults, positive
sequence, negative sequence, and zero voltages must be calculated as is
shown for Bus 1.
RB1 I1 RB1
Z1 Trans 1 X Z1 Line Z1 Trans 2
j.041 .003 + j.036 j.033
Bus 1 Bus 2
Z0 Gen 1 Z0 Gen 2
RB0 RB0
Z0 Trans 1 X I0 Z0 Line Z0 Trans 2
RB0 j.041 .028 + j.119 RB0
j.033
Figure 4.14
Positive, negative, and zero sequence networks for a phase-to-ground fault at Bus 1.
Bus 2 Z1 Gen 2
j.049
I1 RB1
X Z1 Line Z1 Trans 2
.003 + j.036 j.033
Bus 1 Bus 2
Z0 Gen 2
Figure 4.15
Positive, negative, and zero sequence networks for a single phase-to-ground fault at Bus 1
with generator 1 and transformer 1 off-line.
3I0 Gen 1 source = 2804 amps ∠–88.5° × 0.155 ∠79.6° ÷ 0.193 ∠81.7° =
2222 amps ∠–90.6°
3I0 Gen 2 source = 2804 amps ∠–88.5° × 0.041 ∠90° ÷ 0.193 ∠81.7° =
589 amps ∠–80.2°
Bus 2 Z1 Gen 2
j.049
Bus 1 Bus 2
Z0 Gen 2
Figure 4.16
Positive, negative, and zero sequence networks for a single phase-to-ground fault at Bus 1
with generator 1 off-line.
Bus 1 Bus 2
Generator 1 Generator 2
Z1L = 1.7 + j 19.0 Ω
320 MVA, 23 KV 410 MVA, 13.8 KV
Z0L–S = 15.1 + j 62.8 Ω
Xd˝ = 18.5% Xd˝ = 20.2%
Z0L–M = 12.7 + j 38.2 Ω
Transformer 1 Transformer 2
300 MVA, 23–230 KV 400 MVA, 13.8–230 KV
X = 12.35% X= 13.21%
23 KV: ∆ 13.8 KV: ∆
230 KV: Y-Grd 230 KV: Y-Grd
Figure 4.17
One-line diagram showing transformer connections and component impedances, second
transmission line on same structures as first transmission line.
Z1 Line
Bus 1 .003 + j.036 Bus 2
Z1 Gen 1 Z1 Gen 2
j.058 j.049 RB1
RB1
Figure 4.18
Positive sequence network for a three-phase fault at Bus 1.
Bus 1 Bus 2
Z0L-S – Z0L-M
Z0L-M
Z0L-S – Z0L-M
Figure 4.19
Zero sequence equivalent for two parallel transmission lines, all circuit breakers closed.
Z1eq = 0.050 ∠89.6°, which is slightly less than the positive sequence imped-
ance for the network with one line (Z1eq = 0.054 ∠89.5°).
The zero sequence representation of two parallel, mutually coupled
transmission lines, for through faults, such as a fault at Bus 1 with all
circuit breakers closed, is shown in Figure 4.19 and the zero sequence net-
work for this fault is shown in Figure 4.20.
The zero sequence impedance of this network for a fault at Bus 1 is
Z0eq = 0.031 ∠87.3°, which is almost the same as the zero sequence imped-
ance for the network with one line (Z0eq = 0.032 ∠87.8°). Taken together, the
change in positive and zero sequence impedance will have little effect on
Z0L-S – Z0L-M
Bus 1 .026 + j.047 Bus 2
Z0 Gen 1 Z0 Gen 2
Figure 4.20
Zero sequence network for the system shown in Figure 4.17 with per-unit impedances.
the total fault current. However, the current through each line will change
significantly.
3I0 Gen 1 source = 5755 amps ∠–89° × 0.131 ∠78.6° ÷ 0.172 ∠81.3° =
4401 amps ∠–91.7°
3I0 Gen 2 source = 5755 amps ∠–89° × 0.041 ∠90° ÷ 0.172 ∠81.7° =
1375 amps ∠–80.3°
3I0 Each Line = 688 amps ∠–80.3°
With one line in service, the zero sequence current through the line to
the fault at Bus 1 was 1129 amps. When the second line was installed, the
zero sequence current through each line was only 60% of that value.
The zero sequence representation of two parallel, mutually coupled
transmission lines for a line-end fault near Bus 2 with the circuit breakers
open at Bus 2 (Figure 4.21) is shown in Figure 4.22 and the zero sequence
network for this fault is shown in Figure 4.23.
The positive sequence impedance to this line-end fault is Z1eq = 0.068
∠88.4°, the zero sequence impedance is Z0eq = 0.094 ∠84.2°.
Bus 1 Bus 2
Generator 1 Generator 2
320 MVA, 23 KV Z1L = 1.7 + j 19.0 Ω 410 MVA, 13.8 KV
Xd˝ = 18.5% Z0L-S = 15.1 + j 62.8 Ω Xd˝ = 20.2%
Z0L-M = 12.7 + j 38.2 Ω
X
Open
Transformer 1 Transformer 2
300 MVA, 23–230 KV 400 MVA, 13.8–230 KV
X= 12.35% Line End X = 13.21%
Fault
Figure 4.21
One-line diagram showing line-end fault with circuit breaker open at Bus 2.
Z0L-M
Z0L-S – Z0L-S M
X
Figure 4.22
Zero sequence equivalent for two parallel transmission lines, line-end fault, one circuit
breaker open.
Z0L-S – Z0L-M
Bus 1 .026 + j.047 Bus 2
Z0 Gen 1 Z0 Gen 2
Figure 4.23
Zero sequence network for the system shown in Figure 4.21 with per-unit impedances,
circuit breaker at Bus 2 open.
3I0 Gen 1 source = 3277 amps ∠–86.7° × 0.080 ∠87.1° ÷ 0.195 ∠81.7° =
1243 amps ∠–81.3
3I0 Gen 2 source = 3277 amps ∠–86.7° × 0.116 ∠78.0° ÷ 0.195 ∠81.7° =
1.945 amps ∠–90.4°