1 Code FP 400E-7DM-G-C-A5-ER-4DC-NN-PW

2 Type Elastomeric Globe Valve


3 Fluid Type Fresh Firewater

4 Pressure Rating 16 barg, max working pressure


GENERAL

5 Pressure Test / Design 32 barg / 25 barg

6 Required Air Pressure Supply Restricted and regulated pneumatic device, 2-3 barg
7 Temp. Rating Amb. 0.5 to 55°C Amb.
8 Normal Position De-energized and Air Pressurized to close the main valve
9 Approvals UL Listed, ABS & Llyods Registered

10 Material: Body Cover Ductile Iron ASTM A536 65-45-12 Ductile Iron ASTM A536 65-45-12
11 End Connections ANSI 150#RF Intent / Grooved outlet
MAIN VALVE

12 Body Pattern Globe Line serviceable type

13 Leakage Class Drip tight Class VI


14 Valve Internals Elastomer Reinforced VRSD
15 Coating Color Type Red, RAL 3002 High Built Epoxy Coat
16 Elastomers Type Diaphragm: NR Fabric reinforced Polyisoprene

EMR-B EasyLock Manual Reset


VALVE

17 Model Description
PILOT

PORV-L, opens below 1.5 bar (air) Air Pressure Operated Valve, Latching

18 Body Materials Internals Nickel plated Brass Stainless Steel & NBR
19 Control Filter Material Y type (for water control line) Nickel plated Brass
ACCESSORIES

20 Ball Valves Material Floating ball type, PN40 Brass


CONTROL

21 Manual Release Material Model D Brass valve, SST Box

22 Tubing Fittings Stainless steel 316 Stainless Steel 316


23 Drain Valve Material 2 units Ball type Nickel plated Brass
24 Other Material In-Line Air Swing Check valve Ductile Iron Body, EPDM seal

25 Pressure Gauge Material 3 units, 0-20 barg & 300 psi, 4” x ¼” Brass wetted parts, ABS case
INDICATORS

26 Pressure Switch Material 2 unit, PS-10 (PSL & PSH), ½” hole entry Aluminum Alloy Housing

27 Terminal Box Material -

28 Water Motor Alarm Material Water Motor Alarm, (Loose Item) Gong & Housing: Aluminum
29 Brand Model Bermad 5281A-UL
SOLENOID

30 Type Normally 2-way De-energized To Closed Deluge Valve


31 Electric Rating Power 24V DC 8 Watts Epoxy Molded

32 Body Materials Enclosure Brass Epoxy Molded

33 Class Entry NEMA-4, IP65 PA Cable Pluge½” NPT

Notes: Client: PT. Kotaminyak Internusa Project: Pakugajah Development Project


Price Proposal No. 304486
Designed by: Drawn by: Approved by: File Name:
K.A. E.C. K.G. FP-400E-7DM-CER-PW
Design Date: Drawing Date: Approved date: Status:
09/03/2007 02/10/2014 02/10/2014 Rev. 00

appliceng@bermad.com ● www.bermad.com
The information contained in this document is subject to change without notice. BERMAD shall not be liable for any errors contained herein.
All Rights Reserved. © Copyright by BERMAD Control Valves.
Data Sheet

Bermad Pre-Action Deluge Valve & AMD

Air Maintenance Device


Model: AMD74
1 Code AMD-74-PSV
2 Media Instrument Air
3 Main Pressure Connections ½”NPT
GENERAL

4 Pressure Rating 10 barg


5 Pressure Test / Design 16 barg
6 Factory Setting TBA
7 Temp. Rating Amb. 60°C Amb.
8 Normal Position Air Maintained via Restriction Orifice
9 Model Description LR-¼ Air Pressure Regulator
PCV

10 Body Materials Internals Aluminum Stainless Steel and Aluminum


11 Filter Material Y Strainer Nickel Plated Brass
12 Check Valves Material Spring Loaded ¼” Stainless Steel 316
13 Orifice Material RO, Fitting insertion type Stainless Steel 316
ACCESSORIES

14 Tubing Fittings Stainless Steel 316L Stainless Steel 316


CONTROL

15 Tank Material -
16 Safety Valve Material -
17 Isolated Valves Material 2/2 Ball Valves Nickel Plated Brass
18 Back plate panel Material -
19 Other Material -
18 Pressure Gauge Material -
INDICATORS

19 Pressure Switch Material -


20 Terminal Box Material -
21 Others Material -

Notes: Client: PT. Kotaminyak Internusa Project: Pakugajah Development Project


Price Proposal No. 304486
Designed by: Drawn by: Approved by: File Name:
K.A. E.C. K.G. AMD-74
Design Date: Drawing Date: Approved date: Status:
09/03/2007 02/10/2014 02/10/2014 Rev. 00

appliceng@bermad.com ● www.bermad.com
The information contained in this document is subject to change without notice. BERMAD shall not be liable for any errors contained herein.
All Rights Reserved. © Copyright by BERMAD Control Valves.

You might also like