Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Hierarchical Coordinated Control of DC Microgrid

with Wind Turbines


Lirong Zhang, Yi Wang, Heming Li, P in Sun
School of Electrical and Electronic Engineering, North China ElectricP ower University, Baoding, China
E-mail: zhanglr19850727@163.com

kinds of renewable energies, wind power generation with


Abstract-Control and operation of a DC microgrid under various power electronic interfaces is suited to be microgrid power
operating conditions are investigated in this paper. A wind supply, e.g., direct-drive permanent magnet synchronous
turbines based DC microgrid configuration is used to accurately
wind generator with simple structure and high efficiency has
describe different operation modes firstly. For a DC mcrogrid
system, an abnormal DC voltage caused by power fluctuations
faster response than miniature gas turbine and fuel cell. But
can disrupt normal operation or even cause the whole system to because of the high fluctuation of wind energy, it particularly
collapse. Therefore, to improve the system stability, this paper needs to coordinated control to ensure a stable operation
proposes a hierarchical coordinated control strategy according under the various conditions. Thus, this paper takes the DC
to the DC voltage variation range. Under any condition, there
microgrid using wind turbines as an example to develop new
must be at least one DC terminal being responsible for DC
voltage control. On this basis, the control method for each power
system operation and control method. However, the operation
electronic converter is described under different control levels. and control principles will be largely the same for the DC
Finally, the validity of the proposed hierarchical control strategy microgrids using other renewable energy generations.
is demonstrated by simulations on a DC microgrid with wind In the commonly used control schemes [7], the master­
turbines using MA TLAB/Simulink in different operation modes,
slave control method strongly relies on fast communication
considering various operating conditions, such as variations of
wind speed and load, AC grid fault, and load shedding.
between the master controller and slave controllers, once the
communication fails, the microgrid cannot work normally.
For a DC mcrogrid system, the DC voltage must be well
maintained with a limited variation band under all conditions.
I. INTRODUCTION
Abnormal DC voltage caused by power fluctuations can
Microgrid has become a main way for integrating disrupt normal operation or even cause the whole system to
distributed generation and loads, which can reduce the impact collapse. Therefore, this paper proposes a hierarchical
on power system caused by the penetration of renewable coordinated control strategy according to DC voltage
energy systems [ I]. In the microgrid, most of the distributed variation range. Under any condition, at least one converter is
power supplies and energy storage system adopt power responsible for DC voltage control.The DC voltage is used as
electronic converters to connect with grid or loads, which can the control signal for the operating mode switching. Each unit
improve the stability and flexibility of integrated system is controlled independently and each converter switches its
control [2]. Except for some DC sources such as solar cells control method by monitoring its own DC voltage instead of
and fuel cells, the AC sources with instable voltage or using other communication link. As a result, the central
frequency such as wind turbines and miniature gas turbines, manager in traditional control is omitted, the system control
also need DC link to connect to AC grid. A DC microgrid structure is simplified, the reliability is improved and the cost
refers to a DC distributed power system in which power is reduced.
sources, energy storage system and loads are connected The objective of this paper is to investigate new
together via DC transmission lines. Compared to AC coordinated control methods under different operation
microgrid, DC microgrid adopts one centralized AC grid­ conditions for DC microgrid to provide secure and reliable
connected inverter instead of the separate inverter for each supply to loads. Firstly, this paper presents a configuration of
power source, which reduces the cost and loss. Moreover, DC microgrid with wind turbines, and proposes and analyzes
there is no need to take reactive power and system frequency three different operation modes. Secondly, the three-level
into account. It is helpful to coordinately control system hierarchical coordinated control strategy is proposed. On this
operation and damp active power fluctuations. Therefore, the basis, the control method for each power electronic converter
study of DC microgrid has become a new development is described under different control levels, including the
direction for the microgrid technology [3]. control mode switching for each converter when DC voltage
At present, some research on structures, operation modes, is abnormal. Finally, the simulations are carried out in
and control methods for DC microgrid have been done [3-6]. different operation modes respectively, considering various
However, the different operation conditions have not been operating conditions such as variations of wind speed and
fully considered, especially the coordination control strategies load, grid AC fault, to validate the proposed hierarchical
under different conditions need further research. For all control for DC microgrid system.

978-1-4673-2421-2/12/$31.00 ©2012 IEEE 3547


II. SYSTEM CONFIGURATION AND OPERATION MODES where PG, PWT, and PB refer to the power input to the DC grid
The DC microgrid with wind turbines considered is from the G-VSC, the wind turbines, and the BES unit,
schematically shown in Fig. I. As for a typical DC microgrid, respectively. PL is the power consumed by DC and AC loads.
it consists of the following four elements. Under this mode, the wind turbines track maximum wind
(I) Generation unit. Each wind turbine using permanent power, the BES unit is charged with constant power in order
magnet synchronous generator (PMSG) is connected to the to store energy for other modes, and load shedding is not
DC bus via an AC/DC voltage source converter (VSC) W­ required.
VSC. They usually operate at the maximum power point B. Grid Integration-controlled Mode
tracking (MPPT) mode to extract maximum wind power, but This mode refers to the G-VSC limits the exchange power
generation curtailment might be required to protect the between the DC microgrid and the AC grid. The G-VSC
system under certain conditions. operates at current limit mode and becomes incapable of
(2) Energy storage unit. Battery energy storage (BES) unit regulating the DC voltage. Two possible conditions can be
is connected to the DC grid via a bidirectional DCIDC considered, i.e., the exchange power exceeds the G-VSC's
converter Bi-DCIDC. It can operate at charging mode, and maximum power limit, or a short period AC grid fault results
can also provide necessary DC voltage regulation if needed, in AC voltage dip and a significant reduction of the maximum
such as AC gird fault or islanding. power transferred by the G-VSc. In order to keep the system
(3) Energy consumption unit. DC load is connected to DC stable, the BES unit must switch its control from charging
grid directly or via a DCIDC converter. AC load is connected mode to DC voltage control mode to balance the power
to DC grid via an ACIDC converter L-VSC. Appropriate load fluctuation, stabilizing the system at a new operation
shedding based on predefined load priority levels may be condition.The power provided by the BES unit is
necessary to ensure normal operation during the conditions of (2)
insufficient power supply.
If PB is within the maximum power range of the BES unit,
(4) Grid-connected converter. The DC microgrid is
the DC voltage can be fully regulated. When the BES unit
connected to power distribution network via a bidirectional
cannot control the DC voltage because of the large variation
converter G-VSC and a circuit breaker. Grid integration and
of wind speed and loads or insufficient energy storage, load
islanding operation modes can be achieved by controlling the
shedding or generation curtailment of wind turbines will be
circuit breaker on-off. During normal grid integration mode,
required to keep the system stable.
the G-VSC is responsible to maintain a constant DC voltage.
Three different operation modes are proposed for the DC C. Islanding Mode
microgrid in this paper. This mode refers to disconnection with the AC grid, the
DC microgrid becomes an islanding system and the G-VSC is
A. Grid Integration-uncontrolled Mode
no longer in operation. The task of DC voltage control rests
This mode refers to AC grid connection operation via the
on the BES unit which can balance power fluctuations
G-VSc. As the balance node, the G-VSC controls the DC
through charge or discharge. The required power from the
voltage and can automatically balance any power surplus or
BES unit is
deficit within the DC microgrid through the connected AC
(3)
distribution grid, and the required power does not exceed G­
VSC's maximum power limit. Neglecting the power losses, However, during conditions of low wind or heavy load, the
the power provided by the G-VSC is battery discharging power may exceed the power rating of the
(1) BES unit, and the DC voltage will drop. So, load shedding is
implemented to prevent the system collapse. Moreover,
prolonged discharge may result in low battery energy storage
and in order to guarantee power supply to the most critical
loads, appropriate load shedding also becomes necessary.
Besides, during conditions of high wind or light load, the
battery charging power or energy storage capacity could also
exceed its rating value. The BES unit cannot regulate the DC
1--- - --------------------- - ------------

! PDC_L
voltage and, thus, the DC voltage increases. Consequently,
the wind turbines generation power should be reduced
initially by using the W-VSC and then the pitch control
mechanism of the wind turbine system.

: + III. HIERARCHICAL COORDINATED CONTROL


!VdC_T�I
Abnormal DC voltage indicates the power fluctuation
l _____ � � \I��
__ __
- _______________________

within DC microgrid. The DC voltage can determine the


Fig. 1. System structure of a DC microgrid with wind turbines
conversions of both system operation modes and converters'

3548
control methods.The proposed hierarchical control refers to a voltage source control strategy based on AC voltage d-q
multilevel coordination control according to the DC voltage components regulation. Because there is no power source
variation range (LlVdc) of each DC terminal as shown in Fig. 2, voltage for vector orientation, from Fig. 3(d), the voltage
which consists of three control levels. Under each control phase angle Bs used for reference frame transformation is
level, at least one converter is responsible for DC voltage achieved by integrating a constant frequency ill; rather than
control. Each DC terminal works independently and each using conventional phase-locked-loops.
converter switches its control method by monitoring its
B. The Second Control Level
own DC voltage instead of using other communication
The second control level happens during O.OS::S; III Vdcl<O. 1,
links. The three control levels and the control strategies for
corresponding to the situation that the G-VSC is not enable to
each converter under different control levels are described as
control the DC voltage under grid integration-controlled
following.
mode and islanding mode.
A. The First Control Level Under this level, the W-VSC operates at MPPT mode, the
The first control level happens during ILlVdcl<O.OS (in per G-VSC switches from DC voltage control mode to current
unit), corresponding to grid integration-uncontrolled mode. limit operation, and the BES unit must control the DC voltage
The W-VSC operates atMPPT mode. Using the stator flux within a certain level. It can be seen from Fig. 4, a hysteresis
oriented control, the decoupling control of the stator active band is used to avoid unnecessary repetitive control mode
and reactive power is achieved by regulating the q- and d-axis switching during operation. Once the DC voltage at the BES
rotor currents respectively [8]. Fig. 3(a) shows the dual unit terminal exceeds its normal variation band (±O.OS), the
closed-loop control strategy. The inner-loop regulates the BES unit regulates the charging/discharging current in order
stator current, and the outer-loop generates the active power to maintain a constant DC voltage. The DC voltage controller
reference p*opt or the active power current reference tq is also designed using a dual close-loop structure. V*deB is set
according to MPPT control which depends on the rotating at l.OS p.u. or 0.9S p.u. for DC overvoltage or undervoltage
speed Wr ofPMSG.The reactive power current reference td is conditions, respectively, as shown in Fig. 2.
set at zero in stator flux oriented reference frame.
C. The Third Control Level
The G-VSC controls the DC voltage constant. Using the
The third control level happens during 0.1 qLlvdcl<O.IS,
grid voltage oriented control, the decoupling control of the
two conditions can be considered. 0.1 ::S; LlVdc<O.IS
active and reactive power is achieved by regulating the d- and
corresponds to the situation that the battery charging power
q-axis grid currents, respectively [9]. The outer-loop DC
exceeds its rating PB_max or the SOC reaches 80% in grid
voltage controller generates the active power current
reference signal for the inner-loop current regulation as
shown in Fig. 3(b). The reactive power current reference is in
generally set at zero according to the unity power factor
(a)
control.The DC voltage reference V*deG is 1 p.u..
The BES unit is charged with constant current. State of
charge (SOC) refers to energy storage capacity, defined as the
percentage of the rest storage capacity in the rate capacity. In
order to prolong the battery life, the battery energy
management system should limit energy storage and voltage
within a certain range [10-11].The SOC is set at 40%-80% in
this paper. When the SOC reaches 80%, the charging current
is set at zero. The charging control is achieved by regulating
the duty cycle of the Bi-DCIDC as shown in Fig. 3(c).
The aim of the L-VSC is to ensure the output voltage
amplitude and frequency constant. The L-VSC uses the
Fig. 3. Vector control diagrams under the first control level (a) W-VSC (b)

Vdc
G-VSC (c) Bi-DC/DC (d) L-VSC

1.15
Level 3 Wind turbines
1.1
Level 2 BES unit
1.05
1 --Level 1--- G-VSC (a)
0.95
Level 2 BES unit
0.9
Level 3 Load
0.85

(b)
Fig. 2. Hierarchical coordinated control strategy for DC microgrid Fig. 4. Vector control diagrams for Bi-DC/DC under the second control

3549
integration-controlled and islanding modes. Under this Simulation studies are carried out according to different
situation, the wind turbines generation power should be operation conditions under three operation modes, adopting
reduced. -0.15<LlVdc::S; -0.1 corresponds to the situation that the proposed control strategies for this DC microgrid system.
the battery discharging power exceeds its rating in grid In order to simulate the conditions of SOC reaching limitation
integration-controlled and islanding modes, and load (40% and 80%), during the simulation, the charging rate and
shedding should be implemented. Moreover, the SOC discharging rate of the battery are set at 1200 times the actual
reaching 40% also need appropriate load shedding. rate. In the simulation results, the voltage and rotating speed
Load shedding flowchart is shown in Fig. 5, taking four are given using per unit value, DC bus voltage and rated
loads as an example. When discharging power exceeds its rotating speed ofPMSG are selected as base values.
power rating, the BES unit operates at current limit and load
A. Simulation in Grid Integration-uncontrolled Mode
shedding is implemented based on the load terminal DC
As shown in Fig. 7, when the simulation starts, the wind
voltage VdeL. When VdeL is below 0.85 p.u., the load with
speed (v) is 8 m/s. The wind turbines rotor speed (cor) is
lowest priority is tripped immediately. When the SOC
around 0.92 p.u. and the wind turbines generate
becomes lower than 40%, V*dc_B decreases to 0.9 p.u. and
approximately 20 kW (PWT)' Ll and L3 are switched in, the
remains at this value for a certain period. Subsequently, when
total load is about 30 kW (Pd. The initial SOC is 55%, the
VdeL is below 0.9 p.u., the load with lower priority is tripped.
battery is charged with constant power about 9 kW (PB), so
After a certain period, if the SOC is still below 40%, another
the SOC increases accordingly. As the system is grid
load shedding becomes needed as well. V*deB can go back to
connected, the G-VSC outputs power 19 kW (PG) to
the original value 0.95 p.u. if no further load shedding is
compensate the energy deficits. The DC voltage Vdc_G is
required. A hysteresis band is also used to avoid unnecessary
controlled by the G-VSC at 1 p.u.
repetitive switching of the load shedding.
At 6s, the wind speed changes to 11 mls and PWT increases
The details of the generation curtailment control, using the
to 46 kW which is more than loads and battery demand, so
W-VSC and the pitch control mechanism to protect the
the surplus power 7 kW flows to the AC grid as shown in Fig.
system from overvoltage, will be reported in the future.
7(e). L2 and L4 are switched in at 8 s and 12 s, respectively.
IV. SIMULATION STUDIES But the wind speed reduces to 9 mls at 14 s and L3 is
In order to validate the proposed hierarchical control switched out at 16 s. It can be seen clearly from Fig. 7(e) that
strategy, simulation system has been built using the G-VSC adjusts its power output accordingly to maintain a
MATLAB/Simulink shown in Fig. 6. ThePMSG-based wind constant DC voltage of 1 p.u.. At about 12 s, the SOC reaches
turbines are rated at 60 kW. A 60 kW W-VSC and a 40 kW 80%, the charging power changes to 0, i.e., the charging is
G-VSC are used.The common DC voltage is set at 400 V. Ll stopped as predefmed. Through the effective control to each
and L2 are constant power type AC loads both rated at 15 kW, unit, the DC bus voltage Vdc_G is controlled at about Ip.u, and
while L3 and L4 are constant resistance type DC loads both the DC voltage regulation is less than 2%.
set at 10.6 n. The priorities of Ll-L4 decrease in turn. Ll is B. Simulation in Grid Integration-controlled Mode
the most important load and cannot be switched out during As shown in Fig. 8, the operation performances when the
operation.The BES unit consists of a 120 VIlOOO A'h nickel­ simulation starts are the same as that in the grid integration­
metal hydride battery and a 30 kW Bi-DCIDC. uncontrolled mode. But at 6 s, a 500 ms three-phase AC fault
results in a large AC voltage dip as shown in Fig. 8(c). This
reduces the exported power by the G-VSC to almost 0 and
causes the DC voltage to drop immediately. As shown in Fig.
8(g-h), once the undervoltage value 0.95 p.u. is detected by
the BES unit controller, its operation mode is automatically
switched to DC voltage control from charging mode and it is
discharged to compensate the power loss caused by the G­
VSC.The DC voltage Vdc_B is maintained at about 0.95 p.u..
At 6.5 s, the AC fault is cleared and the AC voltage quickly
recovers.This causes a rapid increase of the G-VSC exported
power and the DC voltage, as shown in Fig. 8(d-e).
Consequently, the BES unit switches back to charging mode
and the G-VSC regains DC voltage control, Vdc_G is
controlled at Ip.u. again.
At 8 s, the generated power of wind turbines decreases and
L2 and L4 are switched in at 10 s. The G-VSC increases its
power export to balance the extra power demand. However,
the G-VSC rapidly reaches its power limit of 40 kW and can
Fig. 5. Control flowchart for load shedding
no longer control the DC voltage, thus, the DC voltage droops.

3550
- �t- - 61
Grid

m �: �
Z, Z
PW"I j)G

2
11

+ l(
I
dc.... ---l t---.
2 ...-+-{
� � � B B3
t-----r- -,--------+-
I_V�k_WT --- ----I-V.
I _ -;-I
...-·-
-
11 kV
Wind turbines W-VSC G-VSC
60 kW 60kW 40kW

-
m
Fe

� : : :
+

Z 2
FL
I_V"'-R
I-----.... I--I•3 1--+-{I
120V IOOOkh
--;-
--.------
--'- -l
B i-DODC VdCL_I
30kW L-VSC
Fig. 6. The simulated system schematic diagram of the DC microgrid with wind turbines

Subsequently, the BES unit switches to DC voltage control As shown in Fig. 9, when the simulation starts, the loads
upon the detection of the low voltage value 0.95 p.u .. Vdc_B is L l-L4 are all switched in, PL is about 60 kW, and the wind
again kept at 0.95 p.u.. L4 and L3 are switched out at 14 s and turbine generates approximately 46 kW. The BES unit is
16 s respectively, which results in the total imported power to discharged to compensate energy deficits and controls VdcB
the DC microgrid being greater than the loads demand and at 0.95 p.u.. At 6 s, PWT drops, so the BES unit increases its
the DC voltage rises. Accordingly, the G-VSC and BES unit power output. At around 6.1 s, PB reaches the power limit of
switch back to DC voltage control mode and charging mode, 30 kW and cannot increase further. As PWT still decreases, the
respectively. DC voltage starts to drop due to the power imbalance. Once
the load terminal DC voltage Vdc_L drops to 0.85 p.u. at
C. Simulation in Islanding Mode
around 6.5 s, L4 is tripped immediately.This ensures that the

� : : tiiN! ! .! ! ..
� : t 1!=kill!lj
� : fi � iiii! 11
0'

I� :: f!
" 1 1
R i i � i·
,I �y1 l---,-1----
1

0.9 - ---,-- + t---- -'----1 1 I-'-----..


II· ·
60
· · · 1·· · · · .• . . . . · 1 · · · · .• . . . .· LJ · · · · '1 1
_

�: [ � TT l
"[i'

fl. I�..I[.; I;LI


� : tLl:
§ -10
c:j!
ll.'"" o, I
. _ _


o I

:;:;: 0.95
,�

2 4 6 10 12
Time (s)
14 16 18 20
�]. �i! II f 12 4 6 8 10
Time (s)
12 14 16 18

20

Fig. 7. System operation performances during grid integration-uncontrolled Fig. 8. System operation performances during grid integration-controlled
mode mode

3551
mode and islanding mode, are described. A hierarchical

t :: flEl+1111 1
coordinated control strategy according to DC voltage
variation range is investigated in order to maintain a constant
DC voltage under different operation conditions. AC grid­
connected converter (G-VSC) is responsible for DC voltage

! :: tiki! ;! !f 1 control and power balance under the first control level. The
battery energy storage (BES) unit replaces the G-VSC to
regulate DC voltage under the second control level.

� i::flvllcplll j
Appropriate load shedding and generation curtailment are
required under the third control level. Moreover, the control
method for each power electronic converter is analyzed,

� :� f� • · · · ·.) 1< s
especially the control method switching when DC voltage is

� 20 ••••••. .J 1.· · · ·I< • · · · ·l


.
· · · · · · · · · · · · .. · · · · · , · · · · · · · , · · · · · · .. · · · · · · · · , · · · · · .. · . . . . .
:
abnormal. System simulation results corresponding to the
three different operational modes have validated the
feasibility of the hierarchical control strategy proposed for

! .:fitIIHLirll
DC microgrid. Under various operating conditions, such as
variations of wind speed and load, grid AC faults, and

·
islanding, the system shows the satisfactory operation
performances, thereby improving DC microgrid stability and

1::�il !iJ supply quality.


ACKNOWLEDGMENT

�. °o�;f··· 1 ·Ivl··· ILfJ·I· 1··1··


This project is supported by National Natural Science
Foundation of China (50977028).
.�
:§ 0.8 5 L-_L-----L-_L-_L-_L-_L-_L-_L-----
2 4 6 8 10 12 14 16 18 20
-.J -l REFERENCES

Time (s) [1] N. Hatziargyriou, H. Asano, R. Iravani, and e. Mamay, "Microgrids,"


Fig. 9. System operation performances during islanding mode with load IEEE power and energy magazine, vol.5, no.4, pp. 78-94, Jul. 2007.
shedding [2] P. Biczel, "Power electronic converters in DC microgrid," in Proc.
IEEE Compatibility in Power Electronics Coni, pp. 1-6, May 2007.
total load demand is matched and the BES unit regains [3] A. Sannino, G. Postiglione, G. Postiglione, M. H. J. Bollen, "Feasibility
control Vdc_B at 0.95 p.u.. of a DC network for commercial facilities," IEEE Trans. Industry
Applications, vol. 39, no. 5, pp. 1499-1507, Sep.lOct 2003.
At around 10.5 s, the SOC is reduced to 40%, but the [4] Y. Ito, Z. Yang, and H. Akagi, "DC microgrid based distribution power
battery continues to discharge in order to protect the most generation system," in Proc. IEEE Power Electronics and Motion
important load LI. The BES unit controller thus reduces Control Coni, vol. 3, pp. 1740-1745, Aug. 2004.
[5] H. Kakigano, Y. Miura, T. Ise, and R. Uchida, "DC micro-grid for
V dc_B to 0.9 p.u. as shown in Fig. 9(g). When Vdc_L is less super high quality distribution-System configuration and control of
than 0.9 p.u., L3 is tripped. After tripping L3 for 1 s, the SOC distributed generations and energy storage devices," in Proc. IEEE
is still less than 40% and the battery is still discharged, so L2 Power Electronics Specialists Coni, pp. 1-7, Jun. 2006.
[6] D. Salomonsson, A. Sannino, "Low-voltage DC distribution system for
is tripped. This leaves only the most important load LI to commercial power systems with sensitive electronic loads," IEEE
remain connected to the DC microgrid. The battery can now Trans. Power Delivery, vol. 22, no. 3, pp. 1620-1627, .luI. 2007.
actually start to get charged as the wind turbines generate [7] S. Luo, Z. Ye, R.-L. Lin, and F. C. Lee, "A classification and
evaluation of paralleling methods for power supply modules," in Proc.
more power than the load demand, the SOC begins to IEEE Power Electronics Specialists Coni, vol. 2, pp. 901-908, Jun.
increase. At 13 s, after holding Vdc_B at 0.9 p.u. for 2 s, the 1999.
BES unit controller returns Vdc_B to 0.95 p.u.. When the [8] Zhao Rende, Wang Yongjun, Zhang Jiasheng, "Maximum power
point tracking control of the wind energy generation system with direct­
battery capacity returns to a relatively high level, some loads driven permanent magnet synchronous generators," Proceedings of the
can be reconnected to the microgrid depending on the specific CSEE, 2009, 29(27): 106-111.
system operation requirement. [9] M. Chinchilla, S. Arnaltes, 1.e. Burgos, "Control of permanent-magnet
generators applied to variable-speed wind-energy systems connected to
As seen from Figs. 7-9, the DC microgrid is well controlled the grid," IEEE Trans. Energy Conversion, vol. 21, no. 1, pp. 130-135,
during various operating conditions, and the proposed 2005.
hierarchical control strategy is satisfactory. [10] A. Jossen, V. Spath, H. Doring, 1. Garche, "Battery management
systems (BMS) for increasing battery life time," in Proc. IEEE
V. CONCLUSION Telecommunication Energy Conj, pp. 1-6, 1999.
[11] O. Tremblay, L. A. Dessaint, A. I. Dekkiche, "A generic battery model
This paper presents an operation and control strategy for for the dynamic simulation of hybrid electric vehicles," in Proc. IEEE
Vehicle Power and Propulsion Conj, pp. 284-289, Jun. 2007.
DC microgrid to provide secure and reliable supply to loads.
Taking a DC microgrid with wind turbines as an example, the
system configuration and three operation modes i.e. grid
integration-uncontrolled mode, grid integration-controlled

3552

You might also like