Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

2015 American Control Conference

Palmer House Hilton


July 1-3, 2015. Chicago, IL, USA

Master-Slave Second Order Sliding Mode Control for Microgrids


Michele Cucuzzella, Gian Paolo Incremona and Antonella Ferrara

Abstract— This paper deals with the design of advanced are proposed in [12]. In particular, a Plug-and-Play (PnP)
control strategies of sliding mode type for microgrids. Each algorithm is introduced, but traditional not robust local
distributed generation unit (DGu), constituting the considered controllers are used.
microgrid, can work in both grid-connected and islanded
operation mode. The DGu is affected by load variations, nonlin- In this paper, a master-slave scheme with advanced control
earities and unavoidable modelling uncertainties, because of the strategies, which belong to the class of the so-called Sub-
presence of a voltage-sourced-converter (VSC) as interface with optimal Second Order Sliding Mode (SOSM) algorithms, is
the main grid. This kind of uncertainty terms makes the sliding proposed [13]–[16]. The SOSM algorithm has good properties
mode controller perfectly fitting the control problem to solve. in terms of chattering alleviation and stability performance.
In particular, a second order sliding mode (SOSM) control
scheme, belonging to the class of Suboptimal SOSM control, is The sliding mode is enforced on a suitable designed sliding
proposed. Moreover, in order to face some undesired overshoot manifold from a reaching time after which the robustness of
on the currents fed into the load, due to the reconnection to the the controlled system is proved. In order to alleviate some
main grid, as well as to step variations of current references, overshoot of the currents fed into the load, also a constrained
a constrained SOSM control is designed. Simulation results version of Suboptimal SOSM control for microgrids is
confirm that the proposed robust controllers provide closed-
loop performance complying with the IEEE recommendations designed in analogy with [17]. The effectiveness of the
for power systems. proposed approaches has been assessed in simulation, relying
on a model of a microgrid with three DGus.
I. I NTRODUCTION The present paper is organized as follows. In Section II the
Recently, the increasing of energy sources of renewable considered DGu architecture is described, while in Section III
type has given rise to a new paradigm in the power generation the control problem is formulated. The proposed master-
and in the realization of plants. Particularly, much smaller slave Suboptimal SOSM control strategies are presented in
and geographically distributed generation units (DGus) are Section IV. The stability analysis is discussed in Section V,
realized [1]. Moreover, this new technological alternative al- while simulation results are presented in Section VI. Some
lows one to achieve technical, economical and environmental conclusions (Section VII) end the paper.
benefits, in terms of energy efficiency and reduced carbon
II. P RELIMINARY I SSUES
emissions [2]. DGus also improve the service quality and
continuity [3], by supplying at least a portion of the load, For the readers’ convenience, a brief description of the
even after being disconnected from the main grid [4]. so-called DGu is hereafter reported.
In the literature, a set of multiple mutual connected DGus, A. The Distributed Generation Unit (DGu)
which are usually strictly close to the energy consumers, is
identified as a “microgrid” [5]–[7] . The latter, characterized
by some intelligent computation and metering capability,
can be considered as the basic unit of the so-called “smart
grid" [8]. Because of the intermittence, randomness and the
uncertainty caused by meteorological factors, it is difficult
to integrate renewable energy sources directly into the main
grid. This is the reason why voltage control, fault detection,
reliability, and power losses are among the issues to solve in
order to integrate DGus into the distribution network [9].
In [10], a structurally simple controller is proposed to
stabilize a DGu in spite of the presence of some uncertainties. Fig. 1. Simplified schematic single-line diagram of a DGu.
Moreover, an integral oscillator to control the frequency and
a voltage closed-loop control in islanded mode are used. A
master-slave configuration of two degree-of-freedoms with Consider the schematic representation of a typical DGu in
optimal control is considered in [11], while recently, new Fig. 1. The first element (VDC ) is typically an energy source
decentralized control schemes for islanded configurations of renewable type, which can be represented by a direct
current (DC) voltage source. The latter is connected to the
M. Cucuzzella, G. P. Incremona and A. Ferrara are with the Dipartimento di so-called voltage-sourced-converter (VSC). In our case this
Ingegneria Industriale e dell’Informazione, University of Pavia, via Ferrata 1,
27100 Pavia, Italy (e-mail: {michele.cucuzzella@gmail.com, is a pulse width modulation (PWM) inverter. The VSC and a
gp.incremona@gmail.com, a.ferrara@unipv.it). resistive-inductive (Rt Lt ) filter, able to extract the fundamental

978-1-4799-8684-2/$31.00 ©2015 AACC 5188


TABLE I
with a constant angular frequency equal to the nominal one,
E LECTRICAL PARAMETERS OF THE DG U IN F IG . 1
namely ω0 = 2π f0 , to generate the modulating signals. The
Quantity Value Description VSC is controlled by the voltage controller, according to the
synchronous reference dq-frame. The voltage control signals
VDC 1000 V DC voltage source
fc 10 kHz PWM carrier frequency are transformed back into the stationary abc-frame according
Rt 40 mΩ VSC filter resistance to the inverse Park’s transformation, and used by the VSC.
Lt 10 mH VSC filter inductance The transition from the GCOM to the IOM has to be
R 4.33 Ω Load resistance
L 100 mH Load inductance smoothly performed to avoid system performance degradation.
C 1 pF Load capacity Thus, when the voltage control is activated, the instantaneous
Rs 0.1 Ω Grid resistance phase angle, provided by the PLL, in the current control mode,
f0 60 Hz Nominal grid frequency
Vn 120 V Nominal grid phase-voltage (RMS) must be used as the initial condition for the internal oscillator.
To avoid hard transients, also before the reconnection to the
main grid, the PCC voltage must be resynchronized with the
frequency of the converter output voltage, are the interface grid voltage, for instance as proposed in [19].
medium with the main grid. The electrical connection point III. P ROBLEM F ORMULATION
of the DGu to the main grid is the point of common
Consider the scheme of the DGu in Fig. 1 and assume the
coupling (PCC) where a local three-phase parallel resistive-
system symmetric and balanced. Moreover, consider the DGu
inductive-capacitive (RLC) load is connected. The main grid
in IOM, such that, according to the abc-frame, the model is
is represented by a resistive-inductive (Rs Ls ) impedance and 
1 dvabc
by an alternate current (AC) voltage source. The parameters it,abc = R vabc + iL,abc +C dt

of the system considered in this paper (see Fig. 1) are reported dit,abc
vt,abc = Lt dt + Rt it,abc + vabc (1)
in Table I. The latter have been selected in analogy with a 
 diL,abc
vabc = L dt + Rl iL,abc
realistic case (see for instance [19]).
where iL,abc is the current flowing on the load inductance,
B. Grid-Connected Operation Mode (GCOM) while vt,abc is the VSC output voltage. System (1) can be
In this operation mode, the PCC voltage magnitude and referred to the synchronous rotating dq-frame by applying
frequency are dictated by the main grid. Thus, the system the Clarke’s and Park’s transformations. Then, the state-space
operates in stiff synchronization with the grid by using representation of (1) results in being
the so-called phase-locked-loop (PLL), which provides the  1 1 1
reference angle θ for the Park’s transformation [18]. In order ẋ1 (t) = − RC x1 (t) + ω0 x2 (t) + C x3 (t) − C x5 (t)

1 1 1
ẋ2 (t) = −ω0 x1 (t) − RC x2 (t) + C x4 (t) − C x6 (t)


to operate the lock with the main grid, a proportion-integral

1 R 1
ẋ3 (t) = − Lt x1 (t) − Lt x3 (t) + ω0 x4 (t) + Lt u1 (t)
t


(PI) controller steers to zero the quadrature voltage component

R
ẋ4 (t) = − L1t x2 (t) − ω0 x3 (t) − Ltt x4 (t) + L1t u2 (t)


Vq . In such a case, the active and reactive power are equal to (2)
P = 3/2Vd Itd and Q = −3/2Vd Itq respectively, with Vd being ẋ5 (t) = 1 x1 (t) − Rl x5 (t) + ω0 x6 (t)
 L L
ẋ6 (t) = L1 x2 (t) − ω0 x5 (t) − RLl x6 (t)

the direct component of load voltage vabc , Itd and Itq being




the direct and quadrature components of the current it,abc . y (t) = x1 (t)

 1



Hence, the DGu works in current control mode in order to y2 (t) = x2 (t)
supply Pre f and Qre f , which are the corresponding active and
reactive power references, depending only on the direct and where x = [Vd Vq Itd Itq ILd ILq ]T ∈ X ⊂ R6 is the state
quadrature current component, respectively. variables vector, u = [Vtd Vtq ]T ∈ U ⊂ R2 is the input vector
According to the Park’s transformation, the AC currents and yIOM = [Vd Vq ]T ∈ R2 is the output vector. Likewise, it
generated by the VSC are referred to a synchronous rotating can be found the state space model for the system in GCOM,
dq-frame and regulated like DC signals. The direct and the output vector of which is yGCOM = [Itd Itq ]T ∈ R2 .
quadrature components are compared with the corresponding The control objective consists in designing a robust control
references to compute the errors, which are sent to the current strategy, so as to guarantee that the controlled electrical signals
controller in order to generate the voltage references. The follow their references, while ensuring satisfactory closed-
latter are transformed back into the stationary abc-frame loop performance even in presence of uncertainties.
according to the inverse Park’s transformation, and used by IV. T HE P ROPOSED SOSM C ONTROL S TRATEGY
the VSC.
The adopted methodology to solve the aforementioned
C. Islanded Operation Mode (IOM) control problem is SOSM control [20]. In particular, a strategy
In this case, the circuit breaker (named SW in Fig. 1) is of suboptimal type is designed.
open. Because of the power mismatch between the DGu and In Fig. 2, the proposed control scheme with two DGus is
the load, the PCC voltage and frequency could deviate from illustrated. It has a master-slave structure. Indeed, the DGu
the rated values. Therefore, in IOM the DGu must switch to with the most energy capacity acts as a Master (DGuM ), while
the voltage control mode and provide a constant voltage to the the other as a Slave (DGuS ). In GCOM, all DGus regulate
local load. The control scheme employs an internal oscillator their own active and reactive power with the conventional

5189
Fig. 2. Representation of the master-slave system with SOSM controllers.

dq current control. When an islanding event occurs, only the terms of harmonics affecting the electrical signals, the SOSM
DGuM switches to the voltage control mode and becomes control is used also in this case, by artificially increasing
responsible to keep the microgrid voltage constant with the relative degree of the system. Specifically, by defining
respect to its reference value. Note that, this architecture can the sliding variables as σ1GCOM (t) = y1GCOM ,re f − y1GCOM (t),
be extended to the case with several DGus, each of which is σ2GCOM (t) = y2GCOM ,re f − y2GCOM (t) and the auxiliary variables
independently controlled in a decentralized manner [21]. as ξ1,1GCOM (t) = σ1GCOM (t), ξ2,1GCOM (t) = σ2GCOM (t), one has
Consider the IOM state-space model (2) and assume that
ξ˙i,1GCOM (t) = ξi,2GCOM (t)

the so-called “sliding variables” are equal to σ1IOM (t) =
y1IOM ,re f − y1IOM (t) and σ2IOM (t) = y2IOM ,re f − y2IOM (t). Since ξ˙ (t) = fiGCOM (x(t), u(t)) + giGCOM wiGCOM (t) i = 1, 2
 i,2GCOM
the relative degree r of the system is equal to 2, a SOSM u̇iGCOM (t) = wiGCOM (t)
control naturally applies [13], [14]. According to SOSM (5)
control theory, we need to define the so-called auxiliary
variables ξ1,1IOM (t) = σ1IOM (t) and ξ2,1IOM (t) = σ2IOM (t) such where ξi,2GCOM (t), i = 1, 2, are assumed unmeasurable, and
that the corresponding auxiliary systems can be expressed as
f1GCOM (x(t), u(t)) = −( RL1t C + LR2t )x1 (t) + 2ω
Lt x2 (t)
˙ t
ξi,1IOM (t) = ξi,2IOM (t) 2
i = 1, 2 (3) +(ω 2 + L1t C − RL2t )x3 (t) + 2ωRt
Lt x4 (t)
ξ˙i,2IOM (t) = fiIOM (x(t)) + giIOM uiIOM (t) t
− L1t C x5 (t) − L1t C x7 (t) + LR2t u1 (t) − Lωt u2 (t)
t
where ξi,2IOM (t), i = 1, 2, are assumed unmeasurable, and Rt
f2GCOM (x(t), u(t)) = − 2ω 1
Lt x1 (t) − ( RLt C + L2 )x2 (t)
t
1 1 1 2ω0 2
f1IOM (x(t)) = (ω02 − (RC)2 + Lt C + LC )x1 (t) + RC x2 (t) − 2ωR 2 1 Rt
Lt x3 (t) + (ω + Lt C − L2 )x4 (t)
t
t
+( RC1 2 + LRt Ct )x3 (t) − 2ω 0
C x4 (t) − L1t C x6 (t) − L1t C x8 (t) + Lωt u1 (t) + LR2t u2 (t)
1 Rl 2ω0 t
−( RC2 + LC )x5 (t) + C x6 (t) giGCOM = 1
, i = 1, 2
Lt
f2IOM (x(t)) = − 2ω 0 2 1 1 1
RC x1 (t) + (ω0 − (RC)2 + Lt C + LC )x2 (t) (6)
+ 2ω 0 1 Rt
C x3 (t) + ( RC2 + Lt C )x4 (t)
Rl are allowed to be uncertain with bounds | fiGCOM (·)| ≤ FiGCOM
− 2ω 1
C x5 (t) − ( RC2 + LC )x6 (t)
0
and Gi,mGCOM ≤ |giGCOM | ≤ Gi,MGCOM , FiGCOM , Gi,mGCOM and
1
giIOM = Lt C , i = 1, 2 Gi,MGCOM being positive constants. Note that, the existence
(4) of these bounds is true in practice due to the fact that fiν (·),
ν being the subscript IOM or GCOM, depend on electrical
are allowed to be uncertain with bounds | fiIOM (·)| ≤ FiIOM
signals related to the finite power of the system and giν are
and Gi,mIOM ≤ |giIOM | ≤ Gi,MIOM , FiIOM , Gi,mIOM and Gi,MIOM
constants. The control laws proposed to steer ξi,1ν (t) and
being positive constants.
ξi,2ν (t) to zero in a finite time in spite of the uncertainties,
Analogously, in GCOM, the sliding variables are chosen by
in analogy with [13], can be expressed as follows
considering the error of Itd and Itq . In this case, the natural rel-
ative degree of the system is equal to 1. So, a first order sliding uiIOM (t) = −αiIOM UiIOM,max sgn(ξi,1IOM (t) − 21 ξi,1IOM,max ) (7)
mode controller would be adequate. Yet, in order to alleviate
the chattering phenomenon [22]–[26], i.e. high frequency os-
wiGCOM (t) = −αiGCOM UiGCOM,max sgn(ξi,1GCOM (t)− 12 ξi,1GCOM,max )
cillations of the controlled variable, which can be dangerous in

5190
(8) F̄iν , F̄iIOM and F̄iGCOM being positive constants. Now, the
following result can be proved.
with bounds
! Theorem 3: System (11) in IOM and in GCOM, controlled
Fiν 4Fiν by applying (7) and (8) with bounds (9)-(10), respectively,
Uiν,max > max ; (9)
αi∗ν Gi,mν 3Gi,mν − αi∗ν Gi,Mν with Uiν,max in (9) replaced by Ūiν,max , ∀t ≥ tr and x(tr ) ∈ X ,
  is robust with respect to the uncertain term hV SC .
∗ 3Gi,mν
αiν ∈ (0, 1] ∩ 0, (10) VI. S IMULATIONS
Gi,Mν
Note that, in GCOM, the SOSM algorithm requires that the In this section, the proposed control strategies are tested
discontinous controls are wiGCOM , i = 1, 2, which only affect in simulation relying on a microgrid with three DGus, under
σ̈iGCOM , but not σ̇iGCOM , so that the chattering is alleviated, different conditions. According to the values reported in
and the controls actually fed into the plant are continuous. To Table I, we obtain the bounds F̄1IOM = 1 × 1012 , F̄2IOM =
provide a similar chattering alleviation effect also in IOM, a 4 × 1010 , F̄1GCOM = 4.5 × 109 , F̄2GCOM = 2.5 × 107 , GiIOM =
first order linear filter is applied to the discontinuous control 1 × 108 and GiGCOM = 1 × 102 , i = 1, 2. The SOSM parameters
variable in practical implementation, so as to exploit the have been chosen equal to Ui,max = 5 × 107 , α = 1 and α ∗ =
“equivalent control” concept illustrated in [27]. Furthermore, 0.9 in both IOM and GCOM, and for all the simulations
in GCOM, in order to face some undesired overshoot on the the sampling time has been fixed equal to Ts = 1 × 10−6 s.
currents, due to the reconnection to the main grid, as well The considered additional load absorbs an active and reactive
as step variations of current references, a constrained SOSM power equal to P =25 kW and Q =1.5 kvar.
(SOSMc ) is used. According to [17], this is able to fulfill the A. Transition To and From an Islanding Event
constraints imposed on σiGCOM and σ̇iGCOM , which physically
The transition time instants are imposed equal to tisl =
represent the currents errors and their time derivatives.
0.1 s and tgrid = 0.3 s, in which the microgrid is islanded
V. S TABILITY A NALYSIS from and reconnected to the main grid, respectively. Fig. 3
With reference to the proposed SOSM control approach, illustrates the total currents injected into the main grid, both
the following result can be proved. For the sake of brevity in case of SOSM and SOSMc control. Note that, the SOSMc
the corresponding proofs are omitted. algorithm avoids undesired overshoot on currents at t = 0.3 s,
Theorem 1: In the IOM and GCOM case, by applying the when the microgrid is reconnected to the main grid, and at
control laws (7) and (8) with bounds (9)-(10), respectively, t = 0.35 s, when ItdM ,re f is stepped up from 60 A to 90 A. For
the sliding variables σ1ν (t) and σ2ν (t), ν being the subscript this reason, the following simulations have been performed
IOM or GCOM depending on the case, are steered to zero by using the SOSMc algorithm in GCOM and the SOSM
in a finite time. one in IOM. Finally, in Table II the root mean square error
Now, consider the IOM case. Let e = [e1 , e2 , e3 , e4 , e5 , e6 ]T of the controlled variables ItdM , ItqM in GCOM, and Vd and
denote the state of the error system, with e j = x j,re f − x j , j = Vq in IOM are reported, showing that the proposed SOSMc
1, . . . , 6, x j being the state variables of (2). With reference to controller in GCOM and the SOSM controller in IOM are
the error system, the following result can be proved. more robust and performant than the traditional PI controller.
Theorem 2: Consider system (2) in IOM and variables Note that the gains of PI controllers have been tuned relying
σ1IOM (t), σ2IOM (t) controlled via the SOSM algorithm in (7)
with bounds (9)-(10). ∀t ≥ tr , tr being the time instant when
S O S M C ont r ol
σ1IOM , σ̇1IOM , σ2IOM , σ̇2IOM are identically zero, ∀ x(tr ) ∈ X , 60

then the origin of the error system state space is a finite time 40
i g , a b c ( A)

stable equilibrium point. 20

0
By virtue of the use of the SOSM control approach, the −20

designed control system turns out to be naturally robust −40

tis l tg rid
with respect to any uncertainty included in fiν (·), giν , i = −60
0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
1, 2. It is furthermore interesting to analyze the robustness t i me ( s )

of the proposed control approach versus disturbances or C on s t r ai n e d S O S M C ont r ol


60
uncertainties, gathered in a signal udV SC (t), due to the presence 40

of the VSC in the DGu. To this end, let us consider the system
i g , a b c ( A)

20

in IOM and in GCOM expressed as 0

−20

ẋν (t) = Aν xν (t) + Bν uν (t) + udV SCν (t) (11) −40

−60 tis l tg rid


0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
where, we assume udV SCν (t) = Bν hV SC (t) and the physical t i me ( s )

bound khV SC (t)k ≤ hV SCmax with hV SCmax being a positive


constant. Note that, the associate auxiliary systems can be
Fig. 3. Performance evaluation of SOSM and SOSMc control, comparing
rewritten as in (3) and (5), replacing fiν (·) with f¯iν (·), i = 1, 2, the instantaneous currents injected into the main grid.
to include the additive term udV SC (t), with bounds | f¯iν (·)| ≤

5191
TABLE II
C u r r e nt s d e l i v e r e d by D G u M
RMS VALUES OF CURRENTS AND VOLTAGES ERROR 100

i t , a b c M ( A)
50

0
Configuration PI SOSM SOSMc
−50

GCOM 100% 65.2% 59.5% −100


0.1 0.12 0.14 0.16 0.18 0.2 0.22 0.24 0.26 0.28 0.3
IOM 100% 17.5% - t i me ( s )
L oad Vol t age s
200

v a b c ( V)
100

on the standard Ziegler-Nichols method to obtain a satisfactory −100

−200
behaviour, given the type of control, of the controlled system. 0.1 0.12 0.14 0.16 0.18 0.2
t i me ( s )
0.22 0.24 0.26 0.28 0.3

Vol t age i mb al an c e r at i o
6

V N /V P ( %)
4
B. Robustness to Unknown Load Dynamics
2 SOSM
PI
Under balanced conditions in IOM, consider the addition 0
(VN/VP)M

0.1 0.12 0.14 0.16 0.18 0.2 0.22 0.24 0.26 0.28 0.3
of a purely resistive load which absorbs an active power of t i me ( s )
3 kW. The resistive load is equally added in the three phases,
such that the resulting load is still balanced. The load increase
is imposed from t = 0.15 s to t = 0.25 s. Fig. 4 shows that Fig. 5. From the top: instantaneous currents delivered by the DGuM ; load
voltages under unbalanced load conditions; performance evaluation of PI
the designed controller is robust with respect to unknown and SOSM control with respect to the voltage imbalance ratio.
load dynamics. Indeed, the DGuM increases the delivered
current to supply the added load, while keeping the load
voltage constant equal to its reference value.
Moreover, to evaluate the voltage imbalance at the PCC, the
C. Performance under Unbalanced Load Conditions percentage ratio VN /VP , where VN and VP are the magnitudes
While the system is operating in IOM under balanced load of negative and positive sequence components of PCC voltage,
conditions, at t = 0.15 s resistive and inductive loads are is calculated with the approximate formula proposed in [28].
added, such that the resulting load becomes unbalanced. The Note that the voltage imbalance ratio obtained by using the
relative values of the additional loads with respect to the SOSM control is almost equal to 2.5%, which is less than the
nominal three-phase parallel RLC load are given in Table III. maximum permissible value (3%) recommended by IEEE [29].
In Fig. 5, the instantaneous currents delivered by the DGuM The imbalance ratio with PI control results almost equal
and the three-phase load voltage are depicted from the top. to 3.9%, which is greater than the maximum permissible
value. However, the proposed SOSM control strategy cannot
TABLE III necessarily cope with more unbalanced load conditions, but
U NBALANCED LOAD PARAMETERS it always results significantly better than the PI control.

Phase a Phase b Phase c D. Performance under Nonlinear Load Conditions


R (Ω) 5R 4R 2R During IOM, from t = 0.1 s to t =0.2 s a three-phase six-
L (mH) - - L pulse diode-bridge rectifier is connected to the PCC. The
rectifier feeds a purely resistive load with R = 80 Ω. In Fig. 6
the instantaneous currents supplying the nonlinear load and
100
C u r r e nt s d e l i v e r e d by D G u M the three-phase voltage at PCC are reported, confirming the
robust stability of the proposed controller in spite of the
50
nonlinearities introduced by the rectifier. Moreover, the Total
i t , a b c M ( A)

0 Harmonic Distortion (THD) of load voltage is calculated.


−50
Note that the voltage THD obtained by using the SOSM
control is almost equal to 1% in both transient and steady state
−100
0.1 0.12 0.14 0.16 0.18 0.2
t i me ( s )
0.22 0.24 0.26 0.28 0.3 conditions, which is less than the maximum permissible value
L oad Vol t age s (5%) defined by IEEE [29]. The THD with PI control in the
200
steady state condition is almost equal to that of SOSM, while
100 during transient the voltage THD reaches values which are
v a b c ( V)

0
greater than the maximum permissible. However, the proposed
SOSM control strategy cannot necessarily cope with highly
−100
nonlinear load conditions, but it always results significantly
−200
0.1 0.12 0.14 0.16 0.18 0.2 0.22 0.24 0.26 0.28 0.3 better than the PI control during transients. Finally, in Table IV
t i me ( s )
the root mean square errors of the controlled variable Vd and
Vq are reported. The error is evaluated by using SOSM and
Fig. 4. Instantaneous currents delivered by the DGuM and three-phase load PI control in IOM. The first one results in being more robust
voltage under unknown load dynamic (balanced conditions).
and performant than the traditional PI control.

5192
L oad C u r r e nt s [6] E. Planas, A. G. de Muro, J. Andreu, I. Kortabarria, and I. M. de Alegría,
5
“General aspects, hierarchical controls and droop methods in microgrids:
i t , a b c M ( A)
A review,” Renewable and Sustainable Energy Reviews, vol. 17, no. 0,
0
pp. 147 – 159, 2013.
[7] O. Palizban, K. Kauhaniemi, and J. M. Guerrero, “Microgrids in
−5
0.1 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18 0.19 0.2 active network management—part i: Hierarchical control, energy
t i me ( s )
L oad Vol t age s storage, virtual power plants, and market participation,” Renewable
200
and Sustainable Energy Reviews, vol. 36, no. 0, pp. 428 – 439, 2014.
v a b c ( V)

100
[8] S. Amin and B. Wollenberg, “Toward a smart grid: power delivery for
0
the 21st century,” IEEE Power Energy Mag., vol. 3, no. 5, pp. 34–41,
−100
Sep. 2005.
−200
0.1 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18 0.19 0.2 [9] P. Piagi and R. Lasseter, “Autonomous control of microgrids,” in Power
t i me ( s )
Vol t age T HD Eng. Society General Meeting, 2006, p. 8.
8
SOSM
[10] H. Karimi, E. Davison, and R. Iravani, “Multivariable servomechanism
T HD ( %)

PI
6
T HDM controller for autonomous operation of a distributed generation unit:
4 Design and performance evaluation,” IEEE Trans. Power Syst., vol. 25,
2 no. 2, pp. 853–865, May 2010.
0
0.1 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18 0.19 0.2 [11] M. Babazadeh and H. Karimi, “A robust two-degree-of-freedom control
t i me ( s ) strategy for an islanded microgrid,” IEEE Trans. Power Del., vol. 28,
no. 3, pp. 1339–1347, Jul. 2013.
[12] S. Riverso, F. Sarzo, and G. Ferrari-Trecate, “Plug-and-play voltage
Fig. 6. From the top: instantaneous load currents; load voltages under and frequency control of islanded microgrids with meshed topology,”
nonlinear load conditions; performance evaluation of PI and SOSM control CoRR, vol. abs/1405.2421, 2014.
with respect to the voltage THD. [13] G. Bartolini, A. Ferrara, and E. Usai, “Chattering avoidance by second-
order sliding mode control,” IEEE Trans. Automat. Control, vol. 43,
no. 2, pp. 241–246, Feb. 1998.
TABLE IV [14] ——, “Output tracking control of uncertain nonlinear second-order
RMS VALUES OF VOLTAGES ERROR systems,” Automatica, vol. 33, no. 12, pp. 2203 – 2212, Dec. 1997.
[15] G. Bartolini, A. Ferrara, E. Usai, and V. Utkin, “On multi-input
chattering-free second-order sliding mode control,” IEEE Trans. Au-
Case PI SOSM tomat. Control, vol. 45, no. 9, pp. 1711–1717, Sep. 2000.
Balanced 100% 18.5% [16] G. Bartolini, A. Ferrara, and E. Usai, “On boundary layer dimension
Unbalanced 100% 18.8% reduction in sliding mode control of siso uncertain nonlinear systems,”
Nonlinear 100% 20.9% in Proc. IEEE Int. Conf. Control Applications, vol. 1, Trieste, Italy,
Sep. 1998, pp. 242 –247 vol.1.
[17] M. Rubagotti and A. Ferrara, “Second order sliding mode control of a
perturbed double integrator with state constraints,” in Proc. American
VII. C ONCLUSIONS Control Conf., Baltimora, MD, USA, Jun. 2010, pp. 985–990.
[18] R. H. Park, “Two-reaction theory of synchronous machines - generalized
In this paper a second order sliding mode control, belonging method of analysis - part i,” Trans. American Instit. Electr. Eng., vol. 48,
to the class of the so-called Suboptimal algorithms, has no. 3, pp. 716 – 727, 1929.
[19] I. Balaguer, Q. Lei, S. Yang, U. Supatti, and F. Z. Peng, “Control for
been proposed to regulate the voltage and current signals grid-connected and intentional islanding operations of distributed power
of a microgrid. A master-slave scheme has been designed generation,” IEEE Trans. Ind. Electron., vol. 58, no. 1, pp. 147–157,
and the control algorithms have been suitably tuned to Jan. 2011.
[20] G. Bartolini, A. Ferrara, A. Levant, and E. Usai, On second order
guarantee good performance in case of islanded configuration sliding mode controllers, ser. Lecture Notes in Control and Information.
and grid-connected mode. The stability analysis has been London, UK: Springer-Verlag, 1999, pp. 329–350.
discussed, and satisfactory performances have been obtained [21] M. Babazadeh and H. Karimi, “Robust decentralized control for
islanded operation of a microgrid,” in Power and Energy Society
in simulation relying on a three degree-of-freedoms microgrid. General Meeting, 2011 IEEE, July 2011, pp. 1–8.
The proposed SOSM control strategies ensure closed-loop [22] L. Fridman, “Singularly perturbed analysis of chattering in relay control
performance complying with the IEEE recommendations systems,” IEEE Trans. Automat. Control, vol. 47, no. 12, pp. 2079 –
2084, Dec. 2002.
for power systems and resulting in being more robust than [23] I. Boiko, L. Fridman, A. Pisano, and E. Usai, “Analysis of chattering
traditional PI control. in systems with second-order sliding modes,” IEEE Trans. Automat.
Control, vol. 52, no. 11, pp. 2085 –2102, Nov. 2007.
R EFERENCES [24] A. Levant, “Chattering analysis,” IEEE Trans. Automat. Control, vol. 55,
[1] H. B. Puttgen, P. MacGregor, and F. Lambert, “Distributed generation: no. 6, pp. 1380 –1389, Jun. 2010.
Semantic hype or the dawn of a new era?” Power and Energy Magazine, [25] I. Boiko, “Analysis of chattering in sliding mode control systems with
IEEE, vol. 1, no. 1, pp. 22–29, Jan 2003. continuous boundary layer approximation of discontinuous control,” in
[2] R. Lasseter and P. Paigi, “Microgrid: a conceptual solution,” in Proc. Proc. American Control Conf., San Francisco, CA, USA, Jul. 2011,
35th IEEE Power Electron. Specialists Conf., vol. 6, June 2004, pp. pp. 757 –762.
4285–4290 Vol.6. [26] H. Lee and V. I. Utkin, “Chattering suppression methods in sliding
[3] J. Guerrero, P. C. Loh, T.-L. Lee, and M. Chandorkar, “Advanced mode control systems,” Annual Reviews in Control, vol. 31, no. 2, pp.
control architectures for intelligent microgrids - part ii: Power quality, 179 – 188, Oct. 2007.
energy storage, and ac/dc microgrids,” IEEE Trans. Ind. Electron., [27] V. I. Utkin, Sliding Modes in Optimization and Control Problems.
vol. 60, no. 4, pp. 1263–1270, Apr. 2013. New York: Springer Verlag, 1992.
[4] F. Katiraei, M. Iravani, and P. Lehn, “Micro-grid autonomous operation [28] P. Pillay and M. Manyage, “Definitions of voltage unbalance,” IEEE
during and subsequent to islanding process,” IEEE Trans. Power Del., Power Engineering Review, vol. 21, no. 5, pp. 50–51, 2001.
vol. 20, no. 1, pp. 248–257, Jan. 2005. [29] IEEE, “Recommended practice for monitoring electric power quality,”
[5] R. Lasseter, “Microgrids,” in Power Engineering Society Winter Meeting, IEEE Std 1159-2009 (Revision of IEEE Std 1159-1995), pp. c1–81,
2002. IEEE, vol. 1, 2002, pp. 305–308 vol.1. Jun. 2009.

5193

You might also like