ACCEPTANCE TEST REPORT.LIGHTNING ARRESTERS

Test Report No: LAMCO/RBAPPVATR/I2O Date: 02. tt.20L7

1. Customer : Vt/s, RBA POWER PRMTE LIMITED (CHENNAI).


Project : 63/2OKY Primary Station.
2. Customer PO. No. : RBAPPUDJII SS I 2OL6- L7 I Po-OTH I P -O LZ Dt : 09. 09. 2b 16

Material under above details


sl. Quantity ordered & Sampled Quantity
Rating Of Arrester Offered selected for testing
No
(Sl. Nos.) (Sl. Nos.)*
60 kV 10 kA Class-3 Porcelain M.O.L.A 13 Nos. 2 Nos.
1.
with Insulating base & Surge monitor. (677 rO 6Be) (683 & 687)
21 kV 10 kA Class-2 Porcelain M.O.L.A 07 Nos. 2 Nos,
2.
with Insulating base & Surge monitor. (101 TO 107) (101 & 104)
* (as per Cl 7.2.1 of IS 3070 (part -3) & Cl 9.2.1. of IEC 60099-4 of 2006)
3. Reference standards : IS 3070 (part-3) of 1993 & IEC 60099-4 of 2006
, 4. Acceptance Tests Performed :
a) Power Frequency reference voltage test.
b) Partial discharge test.l.
c) Lightning Impulse Residual voltage test. i
d) Galvanization test on exposed metal parts.
e) Visual examination and Dimensional verification.
0 Functional test on surge monitor.
5. Date of testing : 2nd NoVEMBER,2017

..--?l"tothistestatthereferencecurrentbyusingaPartial
discharge free 220Y1200kV Transformer and the reference voltage is measured in a digital kV meter and
the current in a storage oscilloscope and the results are as per column III of Table-l.

b) Partial discharoe test:


The voltage across the arrester is raised to rated voltage and within 10sec it was reduced to a value
equal to 1.05 times the Maximum Continuous Voltage. At this measuring voltage the partial
' discharge is measured and is recorded in columnOperating
IV of T;ble -1.-

c) Liohtnino Imputse Residual voltaqe test:


The nominal dischar.ge current of 10kA is applied by adjusting the Impulse voltale generator to deliver
the specified current at the required wave shape of B/20Us, The residual voltage across the arrester is
measured through a voltage divider. The peak value of voltage is directly measured in the kV. The
measured value of voltage is recorded in column V of Table-1.

lono t
H.O.
TEL
&Works: B 38, 39 & 40, lndustrial Estate, Sanathnagar,
: +91-40-23704293 , 23702089 , 23703486 , 23708044 , 238
E-mail : info@lamcoindia.com Web :www ffim
A QAD/3BZ Issue 02 (LZ- L2-2OOS)

Reference voltage Test Partial Discharge Residual Voltage test


@ Reference current test@MCovx1.05 @ nominal current

@1.05 x MCOV @1OkAp (B/20us)

151.2
155.5
21KV 1OKACL-2
Permissible value) @1.05 x MCOV @10kAp (B/20ps)

All the values are.. within the tolerance limits

zinc coating test:


Th-e uniformity of zinc coating was determined by teiting the selected sample with
the micro tester at
different places and the observed values of coating thickness indicated the uniformity
(>B5pm) of Zinccoating.

e) Visual examinatio tion:


i) The arresters were visually examined and l,arre no \risrral defects.
ii) All dimensions of the selected sample arresters are found to be within tolerances
as per the approved
drawings.

g) --
i)'Test on Milli Ammeter:
w.ith the arresters and the Mcov is apptied, at that
J:|?j""l",t*:0,^t-y::^ry:ll"^t_t^a_,:lLl"9,l..,seriesuii",i"i
fj:ip:*;::",f::".f::',,:T,f::,:: jl::s.h
monitor which was showing leakage current ofIl"
is measured in the ,,ii,""",,i#'Ji,=i;""l,illij
l-A
ii) Test on Surge counter (standard impulse current):
wi*r *rE arrGGr and surse current purse or lokA (8/20ps wave
:fl::,,T:ip:,111^r:::l11il :_"Ii:,_s
shape) is ailoweclP pass through the arrester and the counter recorded ior the"giirliliTrilS.
Tested l. Witnessed by

(Testing

k
Ul :2
6.o
od'