Calculation of SAFETY DISTANCE for pressure testing

§ 3.3
Pressure Test using liquids ( Hydro test / Water ) : bar PSI
bar to PSI 26.00 377.10

Test pressure Pt 16.00 [PSI]


Internal Diameter (in inches) Di 16.00 [inches] 406.4
Length of the system Li 10.00 [m]
Density - ρ (rho) Rho 1000.00 [kg/m3]
Factor alpha 24.61

Minimum Safety Distance: L 1.16 [m]


maxL 30.00 [m]

§ 4.3
Pressure Test using Gas ( Pneumatic test / Air ) :

Test pressure Pt 7.00 [bar]


Internal Diameter ( in milimeters) Di 298.40 [mm]
Length of the system Li 674.68 [m]
Density - ρ (rho) Rho 1.05 [kg/m3]
Volume V 47.15905899 [m3]

Minimum Safety Distance: L 19.57 [m]


maxL 30.00 [m]