Data List Tram 110kV

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

DATA LIST: TRẠM 110kV NGHĨA LỘ (E12.

2)
KHU VỰC: YÊN BÁI

TRANSF PRIMERY SIDE

TRANSF PRIMERY SIDE


TRANSF SECOND SIDE

TRANSF SECOND SIDE

CHÊNH LỆCH
TRANSF THIRD SIDE

TRANSF THIRD SIDE


TRANSFOMER

TRANSFOMER

TRANSFOMER
SIGNAL NAME

COM S/S COMMON


TYPE No DATA TYPE

Signal Total

FEEDER

FEEDER
BAY REFERENCE (MARK OF C.B.)

171

131

331

931

172

132

332

932

112
T1

T2
1 F FREQUENCY 0
2 A AMPERE 8 1 1 1 1 1 1 1 1
3 KV VOLTS 8 1 1 1 1 1 1 1 1
4 MW MEGAWATTS 8 1 1 1 1 1 1 1 1
ATM 5 MX MEGAVARS 8 1 1 1 1 1 1 1 1
6 TC TEMPARATURE 0
7 TPI TAP CHANGER 2 1 1
TOTAL PER BAY : 34 0 4 4 4 4 1 4 4 4 4 1 0
ATM-Total 34
1 FAULT DC SYSTEM 48V 1 1
2 FAULT DC SYSTEM 220V 1 1
3 FAULT AC SYSTEM 220V/ 380 1 1
4 ACTIVATED FIRE ALARM (When applicable) 1 1
5 REMOTE OPERATION MODE REMOTE / SUPERVISORY 8 1 1 1 1 1 1 1 1
6 BLOCKED CIRCUIT BREAKER (AIR / OIL / SF6) 8 1 1 1 1 1 1 1 1
7 NOT READY CIRCUIT BREAKER NOT READY 8 1 1 1 1 1 1 1 1
8 TRIP - 21-1 LINE DISTANCE PROTECTION ZONE 1 2 1 1
9 TRIP - 21-2 LINE DISTANCE PROTECTION ZONE 2 2 1 1
10 TRIP - 21-3 LINE DISTANCE PROTECTION ZONE 3 2 1 1
11 TRIP - 21-4 LINE DISTANCE PROTECTION ZONE 4 2 1 1
12 TRIP - 21-5 LINE DISTANCE PROTECTION ZONE 5 2 1 1
13 TRIP - 21-6 LINE DISTANCE PROTECTION HIGH ZONE 2 1 1
14 TRIP - 51 LINE OVER CURRENT INSTANTANEOUS 2 1 1
15 TRIP - 50 LINE OVER CURRENT TIME-DELAYED 2 1 1
16 TRIP - 50BF BREAKER FAILURE INSTANTANEOUS OVERCURRENT 4 1 1 1 1
17 TRIP - 67 LINE DIRECTIONAL OVERCURRENT 2 1 1
18 TRIP - 67N LINE DIRECTIONAL OVERCURRENT EARTH FAULT 2 1 1
19 TRIP - 87L LINE DIFFERENTIAL 0
TSS-1B 20 TRIP - 87T TRANSFO. DIFFERENTIAL 2 1 1
21 TRIP - 87N TRANSFO. RESTRICTED EARTH FAULT 2 1 1
22 TRIP - 51 TRANSFO. OVERCURRENT INSTANTANEOUS 2 1 1
23 TRIP - 50 TRANSFO. OVERCURRENT TIME-DELAYED 2 1 1
24 TRIP - 51 GN TRANSFO. EARTH FAULT 2 1 1
25 ALARM - 49 TRANSFO. OVERLOAD 2 1 1
26 TRIP - 49 TRANSFO. OVERLOAD 2 1 1
27 ALARM - 96 TRANSFO. BUCHHOLZ 2 1 1
28 TRIP - 96 TRANSFO. BUCHHOLZ 2 1 1
29 TRIP - 63 TRANSFO. PRESSURE 2 1 1
30 TRIP - 26 TRANSFO. OIL TEMPERATURE 2 1 1
31 TRIP - 26 TRANSFO. WINDING TEMPERATURE 2 1 1
32 FAULT TAP CHANGER 2 1 1
33 TRIP TAP CHANGER OIL PRESSURE 2 1 1
34 TRIP - 87B1 BUSBAR PROTECTION - MAIN 1 1
35 TRIP - 87B2 BUSBAR PROTECTION BACK-UP 1 1
36 ALARM RTU FAULT 1 1
37 DISABLE RTU REMOTE CONTROL 1 1
TOTAL PER BAY : 84 6 14 4 3 3 14 14 4 3 3 14 2
TSS - TOTAL : 84
1 OPEN / CLOSE LINE EART. SWTCH (-76)/TRANSFOR EART. SWITCH(-38) 8 1 1 1 1 1 1 1 1
2 OPEN / CLOSE LINE DISCONNECTOR (-7)/TRANSFOR DISCONNECT(-3) 4 1 1 1 1
3 OPEN / CLOSE CB EARTHING SWTCH LINE SIDE (-75)/CB EARTHING SWITCH TRANSFOR SIDE (-35) 4 1 1 1 1
4 OPEN / CLOSE CIRCUIT BREAKER 9 1 1 1 1 1 1 1 1 1
TSD-2B 5 OPEN / CLOSE CB EARTHING SWTCH BUSBAR SIDE (-15/25) 5 1 1 1 1 1
6 OPEN / CLOSE BUS BAR DISCONNECTOR-1/2 1 1
7 OPEN / CLOSE BUS BAR EARTHING SWTCH(-14/-24/-74) 2 2
TOTAL PER BAY : 33 0 5 5 2 2 0 5 5 2 2 0 5
TSD - TOTAL : 33
1 OPEN / CLOSE LINE DISCONNECTOR (-7)/TRANSFOR DISCONNECT(-3) 4 1 1 1 1
2 OPEN / CLOSE CIRCUIT BREAKER 9 1 1 1 1 1 1 1 1 1
3 OPEN / CLOSE BUS BAR DISCONNECTOR-1/2 1 0 0 0 0 1
RCD-2B 4 RAISE / LOWER TAP CHANGER 2 1 1
TOTAL PER BAY : 16 0 2 2 1 1 1 2 2 1 1 1 2
RCD - TOTAL : 16