Data List Tram 110kV
Data List Tram 110kV
Data List Tram 110kV
2)
KHU VỰC: YÊN BÁI
CHÊNH LỆCH
TRANSF THIRD SIDE
TRANSFOMER
TRANSFOMER
SIGNAL NAME
Signal Total
FEEDER
FEEDER
BAY REFERENCE (MARK OF C.B.)
171
131
331
931
172
132
332
932
112
T1
T2
1 F FREQUENCY 0
2 A AMPERE 8 1 1 1 1 1 1 1 1
3 KV VOLTS 8 1 1 1 1 1 1 1 1
4 MW MEGAWATTS 8 1 1 1 1 1 1 1 1
ATM 5 MX MEGAVARS 8 1 1 1 1 1 1 1 1
6 TC TEMPARATURE 0
7 TPI TAP CHANGER 2 1 1
TOTAL PER BAY : 34 0 4 4 4 4 1 4 4 4 4 1 0
ATM-Total 34
1 FAULT DC SYSTEM 48V 1 1
2 FAULT DC SYSTEM 220V 1 1
3 FAULT AC SYSTEM 220V/ 380 1 1
4 ACTIVATED FIRE ALARM (When applicable) 1 1
5 REMOTE OPERATION MODE REMOTE / SUPERVISORY 8 1 1 1 1 1 1 1 1
6 BLOCKED CIRCUIT BREAKER (AIR / OIL / SF6) 8 1 1 1 1 1 1 1 1
7 NOT READY CIRCUIT BREAKER NOT READY 8 1 1 1 1 1 1 1 1
8 TRIP - 21-1 LINE DISTANCE PROTECTION ZONE 1 2 1 1
9 TRIP - 21-2 LINE DISTANCE PROTECTION ZONE 2 2 1 1
10 TRIP - 21-3 LINE DISTANCE PROTECTION ZONE 3 2 1 1
11 TRIP - 21-4 LINE DISTANCE PROTECTION ZONE 4 2 1 1
12 TRIP - 21-5 LINE DISTANCE PROTECTION ZONE 5 2 1 1
13 TRIP - 21-6 LINE DISTANCE PROTECTION HIGH ZONE 2 1 1
14 TRIP - 51 LINE OVER CURRENT INSTANTANEOUS 2 1 1
15 TRIP - 50 LINE OVER CURRENT TIME-DELAYED 2 1 1
16 TRIP - 50BF BREAKER FAILURE INSTANTANEOUS OVERCURRENT 4 1 1 1 1
17 TRIP - 67 LINE DIRECTIONAL OVERCURRENT 2 1 1
18 TRIP - 67N LINE DIRECTIONAL OVERCURRENT EARTH FAULT 2 1 1
19 TRIP - 87L LINE DIFFERENTIAL 0
TSS-1B 20 TRIP - 87T TRANSFO. DIFFERENTIAL 2 1 1
21 TRIP - 87N TRANSFO. RESTRICTED EARTH FAULT 2 1 1
22 TRIP - 51 TRANSFO. OVERCURRENT INSTANTANEOUS 2 1 1
23 TRIP - 50 TRANSFO. OVERCURRENT TIME-DELAYED 2 1 1
24 TRIP - 51 GN TRANSFO. EARTH FAULT 2 1 1
25 ALARM - 49 TRANSFO. OVERLOAD 2 1 1
26 TRIP - 49 TRANSFO. OVERLOAD 2 1 1
27 ALARM - 96 TRANSFO. BUCHHOLZ 2 1 1
28 TRIP - 96 TRANSFO. BUCHHOLZ 2 1 1
29 TRIP - 63 TRANSFO. PRESSURE 2 1 1
30 TRIP - 26 TRANSFO. OIL TEMPERATURE 2 1 1
31 TRIP - 26 TRANSFO. WINDING TEMPERATURE 2 1 1
32 FAULT TAP CHANGER 2 1 1
33 TRIP TAP CHANGER OIL PRESSURE 2 1 1
34 TRIP - 87B1 BUSBAR PROTECTION - MAIN 1 1
35 TRIP - 87B2 BUSBAR PROTECTION BACK-UP 1 1
36 ALARM RTU FAULT 1 1
37 DISABLE RTU REMOTE CONTROL 1 1
TOTAL PER BAY : 84 6 14 4 3 3 14 14 4 3 3 14 2
TSS - TOTAL : 84
1 OPEN / CLOSE LINE EART. SWTCH (-76)/TRANSFOR EART. SWITCH(-38) 8 1 1 1 1 1 1 1 1
2 OPEN / CLOSE LINE DISCONNECTOR (-7)/TRANSFOR DISCONNECT(-3) 4 1 1 1 1
3 OPEN / CLOSE CB EARTHING SWTCH LINE SIDE (-75)/CB EARTHING SWITCH TRANSFOR SIDE (-35) 4 1 1 1 1
4 OPEN / CLOSE CIRCUIT BREAKER 9 1 1 1 1 1 1 1 1 1
TSD-2B 5 OPEN / CLOSE CB EARTHING SWTCH BUSBAR SIDE (-15/25) 5 1 1 1 1 1
6 OPEN / CLOSE BUS BAR DISCONNECTOR-1/2 1 1
7 OPEN / CLOSE BUS BAR EARTHING SWTCH(-14/-24/-74) 2 2
TOTAL PER BAY : 33 0 5 5 2 2 0 5 5 2 2 0 5
TSD - TOTAL : 33
1 OPEN / CLOSE LINE DISCONNECTOR (-7)/TRANSFOR DISCONNECT(-3) 4 1 1 1 1
2 OPEN / CLOSE CIRCUIT BREAKER 9 1 1 1 1 1 1 1 1 1
3 OPEN / CLOSE BUS BAR DISCONNECTOR-1/2 1 0 0 0 0 1
RCD-2B 4 RAISE / LOWER TAP CHANGER 2 1 1
TOTAL PER BAY : 16 0 2 2 1 1 1 2 2 1 1 1 2
RCD - TOTAL : 16