Alstom Micom p546 v80 Line PTT User Manual Enu
Alstom Micom p546 v80 Line PTT User Manual Enu
OMICRON PTL
User Manual
V1.000
Content
1. General ............................................................................................................................................ 3
2. Software and Hardware Requirements........................................................................................... 3
3. Hardware ......................................................................................................................................... 4
4. Functional Range ............................................................................................................................ 4
5. XRIO Converter ............................................................................................................................... 5
6. Specific Protection Tests ................................................................................................................ 6
6.1 Distance Protection ........................................................................................................................ 6
6.2 Overcurrent Protection ................................................................................................................... 6
6.3 Phase Current Differential Protection .............................................................................................. 6
6.3.1 Communication Check .............................................................................................................. 6
6.3.2 Line Diff Pick Up Current Test ................................................................................................... 7
6.3.3 Line Diff Trip Time Test............................................................................................................. 7
6.3.4 Line Diff External Fault ............................................................................................................. 7
6.3.5 Line Diff Operating Characteristic ............................................................................................. 7
1. General
This user manual describes details of testing P546 relays with the OMICRON Protection Test Template.
General information on the usage of OMICRON Protection Testing Library items can be found in the
OMICRON PTL user manual.
Control Center
Quick CMC
Ramping
Advanced Distance
State Sequencer
Overcurrent
Pause Module
Diff Operating Characteristic
Annunciation Checker
Any CMC test set with a NET1-B, NET1-C or NET2 interface can be used with this
Protection Test Template. In addition a CMGPS 588 is necessary.
3. Hardware
There are multiple possibilities of wiring a P546 relay to a CMC test set. The advised connections are
shown in Figure 1. These connections are the default settings in the Hardware Configuration of the PTT.
4. Functional Range
Supported functions:
Although the functions listed above are not supported by the Protection Test Template, the
Relay Parameter Section of the XRIO Converter includes all protection parameters of the relay.
5. XRIO Converter
The Test Object already contains the ALSTOM MiCOM P546 XRIO Converter, which includes setting
parameters of the modelled protection relay. The setting parameters are built as an image of the MiCOM
S1 Agile software.
The Standard Filter for XRIO Files can be used for importing settings into the Relay Parameter
Section.
The Additional Information block contains a block to enter several settings of the remote relay (“Relay
Parameter Section – REMOTE RELAY”). It is necessary to enter these settings here, because they are
used especially for Current Differential Protection tests.
Further information about the Additional Information block can be found in the OMICRON PTL user
manual.
For all distance protection tests the prefault time has to be set to a value greater than 1 s. Otherwise the
delta directional algorithm in the relay might not work and a fixed RCA (Relay Characteristic Angle) of 60 °
is used instead of the set Dir. Char Angle (31.E3). The test points could fail as this results in a different
directional line in the zone characteristic.
Test Model
The Mho characteristic modeled in the XRIO-converter is only valid for the Test Model selected as
"Constant test current" (ITest) or “Constant test voltage” (Vtest). If the Test Model is set to “Constant
source impedance” in the Advanced Distance module, the Mho characteristic used by the relay differs
from the drawn characteristic in the test module and the test points will fail. This happens due to the
dynamic mho expansion of the relay.
The test points have to be set according to the active Overcurrent Elements. Example:
Definite time elements with 2 test points at 0.9 and 1.1 x pickup
Inverse time elements with 3 test points on the inverse curve
For the different fault types the relay uses different polarizing voltages than the OC test module for the
directional phase OC elements. Therefore, the directional element angles for the tests are adapted in the
OC test module.
This adaption is working for three phase faults and single phase faults but not for two phase faults.
Consequently testing of two phase faults with a directional phase OC element is NOT supported. Only
non-directional phase OC elements can be tested with two phase faults.
Attention: The “Test steps” of the Annunciation Checker show the instructions for relay 1 and for relay 2. If
you run the test the module shows you the different instructions step by step. You have to ensure that
your order corresponds to the order shown above.
The Annunciation Checker Tests have to be assessed manually after successfully performing the tests.