Professional Documents
Culture Documents
LM2 (N Software)
LM2 (N Software)
Kulturstrasse 55 - 73
D-47055 Duisburg
P.O.Box 350138
D-47032 Duisburg
(: 0203/9984-0
FAX: 0203/9984-155
Service:
(: 0203/9984-139
FAX: 0203/9984-166
Web: http://www.brabender-technologie.com
Date: 98-05-12 E-mail: email@brabender-technologie.com
Revision: 1.0
After the end of batch feeding the digital output batch end
will be set. After that the refilling of the hopper can be
! started.
A start of a new batch is only possible after the refilling and
after run-down of the subsequent product stabilisation time.
LM N V1.1
The software version LM N V1.1 permits to select the new mode batch 3
(B3). With this mode the batch will be fed out gravimetrically.
This mode functions with a given feeding setpoint in kg/h, that is con-
trolled by a PID-controller after the start of the feeding operation.
During the feeding operation the batch parameters batch setpoint and
derivative action point will be processed. On reaching the switch-off
value (= batch setpoint * derivative action point) feeding will stop.
Gravimetric feeding is protected against external vibrations by the pa-
rameter anti-vibration. The protection against vibrations has to be ad-
justed to the environment so that it permits sufficient protection
against external vibrations, but does not disturb the feeding operation.
If the protection against vibrations is activated during gravimetric
feeding, the Congrav will switch over to volumetric feeding for the du-
ration of the vibration. The constant manipulated variable for this
volumetric feeding operation is calculated from the average value of the
last 64 manipulated variable values.
Further parameters for the gravimetric feeding operation: alarm cut-out
time, control difference and actual value adaptation. The parameter con-
trol difference as a function of the gravimetric setpoint in kg/h defines
the maximum allowed difference between setpoint and actual value
during gravimetric feeding. A violation of the control difference or of the
protection against vibrations will start the alarm cut-out time. If the du-
ration of the alarm exceeds the value that has been entered for the
alarm cut-out time, there will be an alarm cut-out with a message indi-
cating the type of alarm.
The actual value adaptation permits to adjust the formation of the gra-
vimetric actual value to the feeding conditions. The standard value of 3
is sufficient for most of the applications and should only be changed if
necessary.
©Brabender Technologie, Juli 1999 Appendix: Operating Instructions LM N V1._ Page 2/6
New parameters
1. Setpoint in kg/h Input = menu page F300
2. P-term controller Calibration point 34 [0.01 ... 100]
3. I-term controller Calibration point 35 [0.01 ... 100]
4. D-term controller Calibration point 36 [0 ... 10]
5. Anti-vibration Calibration point 37 [0 ... 100]
6. Alarm cut-out time Calibration point 38 [1 ... 600s]
7. Control difference Calibration point 39 [0 ... 100% ]
8. Act. value adaptation Calibration point 40 [0 ... 5]
LM N V1.2
Further modifications
On the host computer interface the software prevents the processing of
a negative zero. Before, the transmission of a negative zero caused a
MM-error and the corresponding alarm cut-out.
©Brabender Technologie, Juli 1999 Appendix: Operating Instructions LM N V1._ Page 3/6
LM N V1.3
The modifications to version V1.2 are very extensive. With version V1.3
the feeding functions have been optimised and errors that occurred in
version V1.2 have been eliminated.
Further modifications
©Brabender Technologie, Juli 1999 Appendix: Operating Instructions LM N V1._ Page 4/6
LM N V1.4
Partial batch operation
Further modifications
- Calibration point 32: refill mode [0 ... 1]
With an input = 0 the non-average weight value will be processed
during refilling, with an input = 1 the average weight value will be
processed (see V1.3). The selection of this function via the parame-
ter speed min is no longer part of the software.
- Calibration point 11: setpoint factor [0 ... 1]
With mode B2 the manipulated variable of the start (coarse feeding)
is automatically recalculated for each batch feeding. In case of a
setpoint modification, the setpoint factor is an adaptation factor for
this new calculation. With an input = 0 there won’t be any new cal-
culation.
setpoint _ new
Increasing the setpoint: Coarse feeding = coarse feeding × × setpoint factor
setpoint _ old
setpoint _ old
Decreasing the setpoint: Coarse feeding = coarse feeding × × setpoint factor
setpoint _ new
LM N V1.6
The product stabilisation period after refilling is calculated from the
input for calibration point product stabilisation period plus 4s. This
permits a stabilisation of the weight value for the further course of the
batch feeding operation. If the product stabilisation period after refill-
ing is to short, this would lead to unstable weight values and thus a
measuring error for the weight measuring and finally deteriorates the
accuracy of batch feeding to a considerable degree.
LM N V1.7
Modification of the function of the digital output DO1:
! The function batch end is to be found on the digital output
DO1.
The old function operation on the digital output DO1 is no longer avail-
able.
©Brabender Technologie, Juli 1999 Appendix: Operating Instructions LM N V1._ Page 6/6
Operating instructions
CONGRAV LM
Program version: N V1.3
Revision: 1.1
Date: 15.01.1997
BRABENDER Technologie KG
Postfach 35 01 38
Kulturstraße 55-73
D-47055 Duisburg
Telephone: 0203/9984-0
Telefax: 0203/9984-155
Table of contents
Description Page
1. INTRODUCTION 3
1.1. General 3
1.2. Manipulation of Congrav LM 4
1.2.1. Manipulation via a host computer 4
1.2.2. Manipulation via digital inputs 4
1.2.3. On-site operation via keyboard 4
1.3. Turning on mains 5
2. THE KEYBOARD OF CONGRAV LM 6
2.1. Division into four groups 6
2.1.2 Operating keys 7
2.1.3 Cursor keys 7
2.1.4 Numerical keys 7
2.2. Functions of the integrated LEDs 8
2.2.1. LED in the start-key 8
2.2.2. LEDs in the component-keys 8
3. THE DISPLAY OF CONGRAV LM 9
3.1. General structure of the pages 9
3.2. Status line 9
3.2.1. Status indications of a started component 10
3.2.2. Status indications of a stopped component 10
3.2.3. Status indications of a faulty component 11
3.3. Interlocking of the menu pages 12
3.3.1. Interlocking via software 12
3.3.2. Interlocking by the operator 12
4. THE MENU PAGES OF CONGRAV LM 13
4.1. Page overview 13
4.2. Parameter inputs 14
4.2.1.The menu-supported parameter input 14
4.2.2. The numerical parameter input 15
4.2.3. The parameter activation 15
4.3. The menu page F100: operation page 16
4.3.1. The sub-menu page F110: installation modes 17
4.3.2.The sub-menu page F120: Host computer configuration 18
4.4. The menu page F140: Test of I/O-periphery 19
4.5. The menu page F150: Memory Card and setpoint parameters 20
4.5.1 Memory Card (Option) 21
4.6. The menu page F200: Printer page 23
4.7. The menu page F210: Reset functions of Congrav LM 24
4.8. The menu pages F300, F301: Setpoint pages 25
4.9. Menu page F310, F311: Delay times 28
4.10. Menu page F400: Total survey page 1 29
4.11. Menu pages F410, F411: Total survey page 2 30
4.12. Menu pages F420, F421: Total survey page 3 31
4.13. Menu page F430: Reset all totals 32
4.14. Menu page F500: Alarm report page 33
4.15. Menu pages F600: Calibration program 35
5. CALIBRATION PROGRAM 37
5.1. Description of the calibration points 38
6. COMPONENT LEVEL 47
6.1. Structure of the component level 47
6.2. Component page K100: Component control 48
6.3. Component page K110: Operating parameters 49
6.3.1. Sub-menu page K111: Modes 50
6.4. Component page K120: Feeder parameters 51
6.5. Component page K130: I/O -control 52
6.6. Component page K140: Test page 54
6.7. Component page K150: Alarm configuration 55
7. COMPONENT MODES OF CONGRAV LM 57
7.1 Batch 1 (B1) 57
7.2 Batch 2 (B2) 58
7.3 Discharge (DI) 59
8. COMMISSIONING OF A LOSS-IN-WEIGHT FEEDER 60
8.1. Preliminary checks 60
8.1.1. Electrical checks 60
8.1.2. Mechanical checks 60
8.2. Static inspection 61
8.2.1.Checking the weighing system 61
8.2.2. Checking of the drives 63
8.3. Commissioning with product 64
9. APPENDIX A 66
INDEX
1. Introduction
1.1. General
The Congrav LM is a microcomputer for the control and evaluation of continuous feeding
processes. In its most powerful execution it is capable to monitor simultaneously the feeding
operation of a maximum of 8 loss-in-weight feeders, called components after this. The weigh-
feeders are loss-in-weight feeders (called N-type after this).
Please find below a description of the 2 possibilities to run the Congrav LM:
Centronics
Printer interface
Fig.1.1: Rear panel of Congrav LM; modes 1 and 2 (with mode 2 there is no I/O controller for component 5-8)
In order to ensure an optimum feeding operation the Congrav LM has to be adapted to the
components. This adaptation is realised via the software of the Congrav LM. Moreover, during
commissioning a fine adjustment will be carried through, during this operation the parameters
are determined under consideration of the process ambience.
Any modification of the values determined can alter the operating conditions essentially
and therefore should be made by skilled personnel only!
The chapter "The operating page F100" contains detailed instructions for configuration.
Information about composition and structure of the interface is supplied by the "Interface
instructions", which is enclosed in the operation manual.
After switching on the main switch the first function to run is the display test for app. 2
seconds. Then the configuration data stored in the two E²proms are entered into the working
memory. If there are no configuration data in the E²proms, e.g. after erasing of the E²proms,
the standard values from the Eprom are entered into the working memory. After the display
test has been completed the turn-on menu appears (fig.1.3), this will remain activated until
another menu page is called up by pressing a key and the operation level is thus selected.
BRABENDER TECHNOLOGIE KG
DUISBURG
Congrav LM
The operation level consists of a structured menu surface which permits a division of the
operating parameters oriented towards the functions.
♦ Function keys
♦ Operating keys
♦ Cursor keys
♦ Numerical keys
Cursor keys
TECHNOLOGIE KG DUISBURG
Congrav L/M
7 8 9 Numerical keys
4 5 6
1 2 3
0 C
F1 F2 F3 F4 F5 F6 ? HC CR
Operating keys
K1 K2 K3 K4 K5 K6 K7 K8 I 0
Function keys
Fig.2.1: Structure of the Congrav LM keyboard
The function pages contain the parameters required for the adaptation between the component
and the Congrav LM while the component pages contain the parameters necessary for
controlling the individual components.
As the input possibilities for parameters are very comprehensive, the function pages contain
additional sub-pages (sub menus), which can be scrolled by means of the scroll keys and
.
Key Function
calls up the help menu. The individual
?
menu pages can be called up by using the
scroll-keys.
prints out the menu page selected on a
HC connected printer which is ready for
operation. (Hard copy)
this key (RETURN) permits to complete
CR inputs or to select operating parameters
directly.
this key (START) permits to start all
components preselected on menu page
I F300. If all preselected components are
started, the LED will light up.
this key (STOP) permits to stop all
0 components preselected on menu page
F300.
this key (RESET) permits to acknowledge
faults of all components preselected on
menu page F300, so that the installation
can be started anew.
The cursor is used to select the desired menu point or parameter value so that these may be
changed.
Lightning Function
LED off at least one or all of the preselected components
have not started.
LED constantly all preselected components have started.
green
LED flashing red at least one or all of the preselected components
have a fault.
Lightning Function
LED off component is stopped.
LED constantly component is started.
green
LED flashing red component has a fault. The type of fault can be
seen on page F500 by pushing F5 -key.
LED constantly red at least one start condition of the component is
not fulfilled. The type of start condition can be
seen on page F500 by pushing F5 -key.
LED flashing orange component started and interlocked via the digital
input "interlocking" .
Field Meaning
F100 indicates the actual menu page number.
K1 to K8 indicates the operating status of components 1-8 :
field normal : component stopped.
field inverse : component started.
field flashing : component has a fault.
field empty : component blocked or not available.
The operating status of the 1. component appears in status field k1, operating status of the 2nd
component in k2, etc. ... Depending on the actual operating status (component started, stopped
or fault), fields K1 to K8 will also display information on the general feeding operation.
Display Meaning
B1, B2, DI The selected mode is displayed. B1 = batch 1, B2 = batch 2, DI = discharge
OL This indicates that the overload mark defined in CP05 is exceeded by the actual
hopper weight.
RF Filling of the hopper is displayed herewith. This is valid for hand refill as well as for
automatic refill.
MS This shows the material stabilisation phase which is started after conclusion of
filling. The material stabilisation phase can be changed in CP23 .
== The component is interlocked via the digital input "interlocking" and the feeding
cycle is started only after the interlock is cancelled.
EE Access to E²-prom could not be effected as planned.
T+ The positive tolerance limit has been exceeded.
FT The maximum feeding time has been exceeded.
Display Meaning
B1, B2, DI The selected mode is displayed.
RF The refill of the hopper is displayed.
ST One start condition has not been met so that the component cannot be started.
MM Access to a memory module could not be effected as planned.
EE Access to E²-prom could not be effected as planned.
-- The component is interlocked.
In case of an empty field no feeder type was selected for the component. Therefore
this component will not be considered.
BE The batch is ended.
Display Meaning
S+ or. S- The minimum speed value CP09 has not been reached, or the maximum speed value
CP10 has been exceeded.
OL This indicates that the overload mark determined in CP05 is exceeded by the actual
hopper weight. This alarm message is only displayed if an alarm cut-out has been
defined for overload.
UL The hopper filling level is lower than the underload value limit determined in CP04.
RF Refilling of the hopper could not be effected within the time determined in CP21.
WS The serial/digital weighing data are missing (only HS-Type, HM-Type and HD-
Type).
MM Access to memory module could not be effected as planned.
T+ The positive tolerance limit has been exceeded.
FT The maximum feeding time has been exceeded.
RAM reset
EEprom1 reset
EEprom2 reset
The calibration data may be released if the corresponding number code is given in directly
after the page has been called up (i.e. do not call up a cursor). The code inputs are shown as
"*"-sign in the display.
The calibration data are interlocked directly after call up of the page by input of a random
number (0-9). The message line will then display the report "input interlocked".
With an active interlock, in case of an input the report "no input possible" will appear .
With an activated interlocking the report "no inputs possible" is displayed in the message line
after an input.
Function pages
F 150 Memory card and setpoint parameters
F 140 Test of I/O-periphery
F 130 Text switch
F 120 Host computer parameters F210 RAM and EEprom reset
F110
F 110 Installation modes F200 Printer parameters
F100 Installation parameters
direct selection:
direct selection: F1
F2
Component pages
K150 Alarm configuration component 1 K250 Alarm configuration component 2
K140 Test program component 1 K240 Test program component 2
K130 Control page for I/O component 1 K230 Control page for I/O component 2
K120 Feeding parameters component 1 K220 Feeding parameters component 2
K111 Modes component 1 K211 Modes component 2
K110 Feeding parameters component 1 K210 Feeding parameters component 2
K100 Individual control of component 1 K200 Individual control of component 2
To leave the sub-menu without parameter input set the cursor to "back" and press CR -key or
another function page (keys F1 to F6 ) or component page (keys K1 to K8 ) is called up.
Example:
The installation mode "recipe kg" is to be switched over to "recipe %".
For this, an "installation parameter" is called up on page F100 and selected by means of F1 -
key and the cursor is positioned on menu point "mode" by means of the cursor keys (fig.4.2).
Mode Recipe kg
Host comp oper. Siemens (3964R)
Text switch English
Recipe kg
Recipe %
Return
Fig.4.3: Example; menu-supported parameter input
CR
Now the requested mode has to be marked with the cursor and confirmed by means of the -
key. After that the menu page F100 with the modified parameter will automatically be
displayed.
C
Input can be erased step by step within the input line, always the last number, using the -key.
Input is concluded by pressing CR -key, the new parameter value is then taken over.
Example:
The parameter "bulk density" of component 1 is to be set to 0,75 kg/l. For this, you call up
the component page K100 with key K1 and go to page K110 by means of the key (scroll
forward).
Now the old value of the parameter value "bulk density" has to be marked with the cursor and
the number code 0 7 5
is entered via the numerical keyboard, this number code will also
be displayed on the lower left side in the input line (fig.4.4). In the case of false inputs they can
be erased step by step by means of the C -key.
CR
The input is completed by pushing the -key and the new parameter value will be taken over
(fig.4.5).
Fig.4.6: Menu page F100; the values printed in bold type can be selected
Fig.4.9: Menu page F140; the values printed in bold type can be selected.
4.5. The menu page F150: Memory Card and setpoint parameters
When employing a memory card it is possible to store or to read out a maximum of 14 recipes.
Each recipe contains the data of the EEproms of Congrav LM and thus all installation and
calibration data (complete configuration).
After the first use of the memory card the actual configuration has to be absolutely
memorised!
With Congrav LM-2C only the installation back-up is available. The manipulation is only
possible via a PT03!
Enter recipe number 0 and memorise the recipe on memory card. Then input the actual recipe
number (e.g.: 1) and memorise this recipe as well on the memory card.
Recipe nr. 0 is no normal recipe. After the actual configuration has been memorised it receives
continuously the actual system data. Following inputs will now be automatically memorised
with recipe nr. 0 and the actual recipe remains unchanged.
recipe on memory card". There is no warning before writing over a recipe already
existing!
Load the recipe you need from the memory card. All data that have not been
memorised get lost. Carry through first the recipe parameter modifications (e.g. setpoint
modifications) and then the function "store recipe on memory card".
Enter the requested recipe number in the point "recipe number" then carry through "load recipe
from memory card". All data that have not been memorised get lost.
In its standard execution the Congrav LM is not equipped with a memory card (option), it can
be installed later in a Congrav LM with memory board. The present status can be seen in the
"memory card status" display.
As for mounting and important instructions for using the memory card please see "technical
documentation".
As each recipe contains all calibration data, modifications of the calibration data
that you have carried through at a later point of time (e.g. lever arm, max. output) have
to be changed in all recipes.
Fig.4.11: Menu page F200; The values printed in bold type may be selected
Fig.4.12: Menu page F210; the values printed in bold type can be selected
Important instruction:
The functions of this page are interlocked against unauthorised inputs if they are called up -
this interlocking is independent of the key switch. They can only be released by inputting the
numerical code "0884". Input of the code is only possible directly after call-up of the page, i.e.
before any cursor function.
During RAM or EEprom reset the message "reset RAM" or "reset EEprom" is displayed. After
the reset, the turn-on menu (fig.1.3) is displayed.
On a reset of the RAM all old operation parameters in the RAM are erased and the operation
parameters memorised in the EEprom are read in anew, so that the specific data of the feeder
remain the same.
On a reset of the EEprom all feeder specific data memorised in the EEprom are
definitely reset and the standard values from the Eprom are read in, so that all feeder
specific data must be entered anew or loaded from the memory card in the form
of a recipe.
Fig.4.13: Menu page F300; the values printed in bold type can be selected.
To simplify the parameter input the cursor keys left and right are additionally activated on this
page. You can place the cursor on any setpoint field. By pressing -key there is switch-over
to page F301, where the corresponding inputs for components 5-8 can be effected (not
applicable for operation with only one internal I/O-controller).
♦ The preselected component can be addressed by means of the operating keys stop 0 , start
I
and reset . If a component has not been selected these functions can only be carried
out by means of the component control pages K100, K200, ..., or K800.
♦ Calculation of total values (total setpoint, total actual value and all totals) on page F400 is
made from the individual values of the selected components. Components not selected will
not be taken into consideration.
♦ Beside the common start or stop of all selected components all selected components will be
stopped if one selected component is switched off due to any fault occurring and the
message "alarm stop" was activated on page F310.
Setpoint input:
In order to modify a setpoint you place the cursor on the corresponding field and enter the
desired value via the numerical keyboard. If an input is not possible due to the installation or
component mode the message "no setpoint input" appears in the status line. After change of
component mode no setpoints are reset. All setpoints can be changed with the installation or
component started.
Due to varying installation modes of the Congrav LM (single, group, and master/slave
operation) and of the modes of the individual components (gravimetric feeding, volumetric
feeding, etc.) it is also necessary to enter varying setpoints.
For setpoint inputs with varying modes please refer to the examples below. In the following
figures the permitted parameter inputs (%-column or kg/h-column) are written in bold type.
a) Recipe kg - operation:
♦ Installation mode single operation is characterised by the fact that the total setpoint is
displayed in the second line. The total setpoint is not entered but is calculated from the
individual setpoints of the selected components. Here the 1. component (setpoint = 100
kg/h) and the 3. component (setpoint = 30 kg/h) are preselected so that a total setpoint of
130 kg/h results.
♦ With single operation the setpoints are entered in the column kg/h. After conclusion of the
input there is a check whether or not the setpoint limitation was violated. The setpoint
limitation is:
If this setpoint limitation is violated the message "setpoint error Co.X" is displayed in
inverse representation in the status line and the value is not accepted so that the old
setpoint is still valid.
♦ With recipe % - operation first enter the group setpoint as total setpoint in kg/h.
Component setpoints of selected components (1 and 2) are related in % to the group
setpoint and entered in %-column. From the two inputs, setpoint in % and group setpoint,
the setpoint in kg/h is automatically calculated and appears in column kg/h. When entering
the setpoint in % it is checked whether the setpoint in kg/h resulting from this does not
violate the setpoint limitation (see above). If this is the case the status line will display the
message "setpoint error Co.X" (X indicates the component number) and the old setpoint
will not be changed.
♦ If the group setpoint is changed there is a check whether on new calculation of the
component setpoints the setpoint limitation will not be violated. If the setpoint limitation is
violated for at least one component setpoint, the message "setpoint error Co.X" will be
displayed and the setpoint entered will not be accepted.
♦ If first the setpoint input is made and after that the component is selected the setpoint is
calculated anew as a function of the group setpoint. If the new setpoint violates the
setpoint limitation, start condition "setpoint > max.“ appears and the feeders cannot be
started.
Fig.4.16: Menu page F310; the values printed in bold type can be selected
By pushing the -key, you get on page F311 which is structured totally alike, it is valid for
components 5-8 (not for operation with only one internal I/O-controller).
Required batches:
The option „required batches“ determines the number of batches that are automatically carried
through. In case of single batches, the required batches have to be set = 1.
Alarm stop:
The option "alarm stop" permits the shutoff of a selected component due to an alarm of
another selected component. In the above menu example an alarm shutoff of component nr. 1
would also shut off the other components provided all components have been selected.
The menu pages F400, F410, F411, F420, F421 and F430 permit the control of the feeding
process. They display the feeding parameters as setpoints, actual values and throughputs. By
pressing F4 -key the total survey page F400 is called up.
By pressing the -key the next total survey page, page F410, is called up (not for operation
with only one internal I/O-controller).
Fig.4.18: Menu page F410, the survey page for setpoints, actual values and totals for components 1-4
Actual batches none none The third column shows the number of batches that have been
carried through so far.
Further pressing of the -key will call up the next total survey page F411, (not for operation
with only one internal I/O-controller). This page is corresponding to page F410, it is valid for
components 5-8.
F411 B1 B1 B1 B1 B1 B1 B1 B1 PLC
Fig.4.19: Menu page F411, the total survey page setpoint / actual value / total values for component 5-8
Further pressing of the -key will call up the next total survey page F420.
Fig.4.20: Menu page F421, total survey page weight- / control deviation.- / speed values for component 1-4
Further pressing of the -key calls up the next total survey page F421, This page is
corresponding to page F420, it is valid for components 5-8.
F421 B1 B1 B1 B1 B1 B1 B1 B1 PLC
Fig.4.21: Menu page F422, total survey page weight- / deviation / speed values for component 5-8
Further pressing of -key calls up menu page F430 auf. This menu page is used to reset all
throughputs.
Fig.4.22: Menu page F430; the values printed in bold type can be selected
To erase the throughputs place cursor on the respective "L"-field and press CR -key. The total
throughput decreases each time by the erased single throughput, but it cannot become
negative. If a single throughput is reset which is greater than the total throughput the total
throughput is reset to zero. Therefore it is not necessary to stick to a special order (first single
throughputs, then total throughput).
An activation of the "L"-field (menu point "select") resets all single throughputs of the
selected components at a time.
The erased throughputs, also the total throughput, cannot be called back so that erasing the
throughputs corresponds to a reset of the throughput totalizer.
Fig.4.23: Menu page F500 containing examples of alarm messages and start conditions
Menu page F500 is called up by pressing F5 -key. It displays to the operator any missing start
condition or fault that has occurred during operation. Here, the following alarm reports can be
displayed:
The alarms listed in the table may cause two errors on Congrav LM according to what has
been laid down on page K150-K850.
On the one hand a fault might cause an alarm cut-out with alarm report. The alarm cut-out is
displayed on Congrav LM by a flashing mode display and a flashing red LED in the
corresponding K-key. Furthermore the digital output "alarm" (DO "alarm" of corresponding
component) is activated.
After acknowledgement of the alarm ( -key, K100-K800 or activation of DI "alarm reset")
feeding can be restarted.
On the other hand a fault might cause a simple alarm report without alarm cut-out. This alarm
report is displayed by an inverse mode display of the alarm - feeding is continued. Furthermore
the digital output (DO) "alarm" is activated.
After acknowledgement of the alarm ("alarm reset" ( -key) or activation of DI "alarm
reset") the mode display is refreshed and the digital output "alarm report" is reset. With the
alarm "underload" the digital output "underload" is set beside the digital outputs "alarm
report" or "alarm with cut-out“.
Start conditions
Before starting an installation the various start conditions must be fulfilled. An unfulfilled start
condition is displayed in the mode display of the component by "ST", by a red LED in the
K-key and by a corresponding report on page F500. Furthermore with selected components
the digital output "start condition of a selected component not fulfilled" will be activated.
If several start conditions are not fulfilled these will be displayed according to a definite
priority order. If the displayed start condition has been fulfilled the next missing start condition
will be reported as per the priority order. If the indicated start condition is fulfilled the next
start condition that is not fulfilled will be indicated according to the priority order. The
following table lists and explains the reports of missing start conditions:
A further start condition is characterised by the report "Feeder blocked". This means the
component has not yet been assigned to a feeder type. CP01. The start condition "Feeder
blocked" has the following effects:
the respective component will not be considered during the feeding cycle and cannot be
started.
If the Congrav LM is operated with less than 8 components, the components not existing must
be blocked. This will avoid any malfunctions due to a non-existing component.
Furthermore the start condition "setpoint < max." can occur due to wrong setpoint inputs on
setpoint page F300 in the installation mode recipe %.
Fig.4.24: Menu page F600; the values printed in bold type can be selected
You call up the calibration program by pressing F6 -key. The calibration program permits a
further adaptation between Congrav LM and the weighing module. The calibration program
consists of 40 calibration points (CP). Selection of calibration points is made by the cursor key
step by step. If the cursor reaches the last or the first line of the calibration points visible in the
display the calibration list is scrolled by one calibration point up or down corresponding to the
cursor key pressed.
To achieve a quicker selection the cursor can be shifted by 5 calibration points by means of the
scroll keys and . By pressing the F6 -key again it is always possible to return to the begin
of the calibration program.
Selection of the calibration programs of the individual components is made by briefly pressing
the respective K-key. When changing between the individual component calibration programs
the actual position of the cursor and thus the block of the displayed five calibration points will
be kept which permits a simplification of the operation and of the parameter comparison.
Input of a new parameter value is made in the input line and is taken over by pressing CR -key
(numerical input). The input procedure was already described in chapter 4.2.2. The parameter
values can only be changed within fixed value ranges. If a parameter input violates the value
range the input will not be taken over, i.e. the old parameter value remains unchanged, and the
status line will display the message "wrong input".
A parameter value can consist of a maximum of 7 digits. Input of larger parameter values is not
possible as with the input of the eighth digit the complete input in the input line will be erased.
Some parameter values require the input of an integer value (whole figure). If these parameters
are entered in real numbers (fraction), only the value in front of the point is considered as
parameter value .
The calibration program is interlocked after each reset of RAM- or E²prom or after each
switching on/off of the power supply by a number code . Changes in the calibration program
are only possible if the calibration program has been released before. The release is done as
follows:
The calibration program can be interlocked again by entering a random figure (0 - 9) after call-
up of the calibration program (do not call up a cursor) . After entering the figure the message
"Input interlocked" will be displayed. Attempts to make changes in an interlocked calibration
program are rejected with the report "no input possibility." .
The calibration program is left by calling up another menu page with the F-keys F1 - F5 .
Furthermore the calibration program may be left by calling up the component control pages.
This is done by a long pressure on the corresponding K-key.
5. Calibration program
CP Designation Type
01 Feeder type HS/HA/HM N parameter
Depending on the load cell type employed there are six feeder types which are defined by
means of different inputs.
Input 0: no feeder type selected. Component cannot be started because the start condition
"feeder blocked" is displayed. This input is necessary if the Congrav LM is
operated with less than eight components. Components that are not existing will be
designated by input of CP01 = 0. This will prevent faulty functions during
operation of Congrav LM which might occur due to a non-existing component.
Input 1: This is used to select the serial load cell, i.e. that of feeder type DDW-H/S. Weight
acquisition is made with the load cell IDL, the serial weight signal of which is
measured via the corresponding adaptation board BT 0291. (Terminal connections
see appendix A)
Input 2: This input serves to select the analogue load cell, i.e. the feeder type DDW-H/A. The
weight is measured by means of a strain gauge load cell. The analogue weight
signal of this strain gauge load cell is measured via the adaptation board BT 0982.
(Terminal connections see appendix A)
Input 5: This input serves to select the analogue load cell, the weight signal of which is serially
transmitted. The weight is measured by means of a strain gauge load cell, the analogue
weight signal of which is measured by means of the adaptation board AD 101 (with
basic device AED 9001). (Terminal connections see appendix A).
CP Designation Type
02 Weighing range N parameter
The weighing range of the loss-in-weight feeder results from multiplication of the lever value
CP15 and the weighing range value of the load cell used:
Example:
CP15 = 2 and weighing range of load cell = 30 kg
2 * 30 kg = 60 kg (weighing range of feeder)
Deviations from this idealised example may be the result of mechanical manufacturing
tolerances.
Weights which are beyond the weighing range of the feeder will not be acquired by the
system and may even damage the load cell if the mechanical limits have not been correctly
adjusted.
CP Designation Type
03 Maximum batch size N parameter
Feeder-specific output value which is used to limit the setpoint input. The setpoint range is
calculated from:
setpoint < 1.1 × maximum batch size
CP Designation Type
04 Underload N parameter
With this filling level min. hopper content is fixed which is required for start and operation. If
this value is undercut the feeder cannot be started (start condition) or there will be an alarm
cut-out or an alarm report. The filling level entered in % to the max. filling level value which
either results from the product (hopper contents CP16 × bulk density) or from the weighing
range CP02 if the product (hopper contents × bulk density exceeds the weighing range).
CP Designation Type
05 Overload N parameter
Defines for an H-type feeder the maximum filling level value for the feeding operation. If it is
exceeded there is either the choice (K150 - K850) of an alarm cut-out after 6 seconds or a
volumetric operation period until the filling level is smaller than the overload value.
The filling level value entered in % relates to the maximum filling level value which results
either from the product (hopper contents CP16 × bulk density) or from the weighing range
CP02, if the product (hopper contents × bulk density) exceeds the weighing range.
CP Designation Type
06 Coarse tare N parameter
The value entered in % is related to the weighing range CP02. The tared part WRtare is
subtracted from the weighing range so that the remaining weighing range which is usable for
the feeding operation WRuse is calculated as follows:
WR use = WR − WR tare
usable
weighing range
weighing range WRuse
WR
coarse tare
WRtare
CP Designation Type
07 Average value N parameter
CP Designation Type
08 Throughput divisor N parameter
Determines the valency for the throughput counter (totalizer). Input should be selected in such
a way that the internal counter has at least 0.1% of the rated output. Input of the valency is
made in kg or lb. I.e. an input of 0.125 corresponds to a valency of 125g. The smallest valency
is 1 g (input = 0.001) the largest is 1 t (input = 1000).
CP Designation Type
09 Speed minimum N parameter
Here the minimum speed is determined. If this speed value is undercut during operation an
alarm cut-out or an alarm report follows after 6 seconds.
CP Designation Type
10 Speed maximum N parameter
Here the maximum speed is determined. If this speed value is exceeded during operation an
alarm cut-out of an alarm report follows after 6 seconds.
CP Designation Type
11 Reserve N parameter
CP Designation Type
12 Reserve N parameter
CP Designation Type
13 Type of interlocking N parameter
With this calibration point it is possible to determine the logic of the digital input
"interlocking", the digital input "stop" and the digital output "alarm". The following table lists
the input possibilities. The logic "inverted" means that the alarm output is set if no disturbance
is present and is not set if a disturbance is present.
CP Designation Type
14 Indication of actual value N parameter
Determination and updating time for actual value and time base for short-term actual value.
CP Designation Type
15 Lever factor N parameter
This point for the statical weight adjustment of the loss-in-weight feeder (by the factor "1").
CP Designation Type
16 Hopper contents N parameter
The value input in litres contains the screw trough and the hopper.
CP Designation Type
17 Filling level minimum N parameter
Defines the filling level value at which automatic switch over from feeding operation to refill
mode occurs.
The filling level value entered in % relates to the max. filling level value which results either
from the product (hopper contents CP16 × bulk density) or from the weighing range CP02, if
the product (hopper contents × bulk density) exceeds the weighing range.
CP Designation Type
18 Filling level maximum N parameter
Defines the maximum filling level for refilling. If this max. filling level is reached a switch over
from filling mode to feeding operation follows after elapse of the material stabilisation time.
The filling level value entered in % relates to the max. filling level value which results either
from the product (hopper contents CP16 × bulk density) or from the weighing range CP02, if
the product (hopper contents × bulk density) exceeds the weighing range.
CP Designation Type
19 Window/Filter N parameter
From software version HG V1.5 on the IDL load cell is provided with an internal filter (IDL-
F). For the filter adjustment of the load cell please see the following table:
The filter setting 6 should be sufficient for most of the applications and is a good compromise
between interference suppression and signal response time and should be entered in standard.
If it is necessary to increase filtering, this should be done stepwise, as the signal response time
is simultaneously increased. This might cause problems, e.g. refill problems so that the feeder
will be continuously overfilled.
Due to the signal filtering in the IDL-F cell the average value setting for the filter values 6 - 9
can be decreased from 8 to 4.
Inputs > 9 are interpreted as pure window values so that the IDL load cell is still provided for.
Window (HS-type):
The window value entered, multiplied by 20 ms determines the time interval in which the serial
load cell finds a new weight value and sends it to the Congrav LM .
Filter (HM-type):
The filter value that has been input determines the intensity of weight value filtering (1: no
filtering - 8: extreme filtering). The stop function transmits the filter value to the serial load
cell. Therefore the stop function must be activated after a change. This can be done with
selected components by pressing the stop key, otherwise by means of the component control
page K100 - K800 or the digital input "stop" .
CP Designation Type
20 Actual value output N parameter
Act . value
Act .val. output = ⋅ max. act . val. output + offset
Max.batchsize(CP03)
The signal type of the actual value output can be determined by the following inputs in CP20:
When using a Congrav LM with I/O-controller with actual value outputs, one actual value
output each is available:
CP Designation Type
21 Maximum refill time N parameter
This calibration point permits to determine the maximum time for refilling. After elapse of the
maximum refilling time and after elapse of the material stabilisation time CP23 the component
switches back to the selected component mode if the filling level minimum CP17 was
exceeded. If this is not the case an alarm cut-out or an alarm message "filling error" will
occur according to what has been laid down on page K150 - K450.
Refilling is finished after the maximum filling level CP18 has been reached or before the
maximum filling time is over.
CP Designation Type
22 Refill timing N parameter
CP Designation Type
23 Stabilisation time N parameter
After the refill period the material stabilisation time starts. After elapse of the material
stabilisation time follows the switch over to the selected component mode.
CP Designation Type
24 Weight mode N parameter
Defines whether switch-over of the points „coarse/fine“ and „derivative action point“ is done
by means of average weight values or non-average weight values.
CP Designation Type
25 Setpoint mode N parameter
Input = 0 : a setpoint modification will not be taken over after batch feeding, it will only be
taken over after the start of a new batch.
Input = 1 : a setpoint modification will also be taken over during batch feeding. However,
this function is not activated if partial batch feeding has been activated.
CP Designation Type
26 Feeding tolerance N parameter
The input is in % as a function of the weighing range or as a function of the setpoint (please
see CP33), thus the maximum positive and negative tolerance are determined. If the positive
tolerance range is exceeded, there will be an alarm message „tolerance fault“ („T+“ mode
display). Falling short of the negative tolerance range starts fine feeding until the product
quantity that has been fed is within the tolerance range.
CP Designation Type
27 Batch stabilization time N parameter
The batch stabilization time runs down after the end of a batch or a partial batch. On the start
of a batch stabilization time at the end of a batch, the digital output „batch end“ (DO7 of the
corresponding component) is set.
CP Designation Type
28 Coarse delay N parameter
The coarse delay time runs down after the start of a batch. It determines the lapse of time
between setting of the digital output „operation“ and „coarse feeding“.
CP Designation Type
29 Coarse/fine switchover time N parameter
CP Designation Type
30 Derivative action correction N parameter
CP Designation Type
31 Switch-over kg/% N parameter
For the following parameters it is possible to switch over the units from kg to %:
• underload
• filling level min.
• filling level max.
• overload
Input = 0 : kg
Input = 1 : %
CP Designation Type
32 Partial batch automatic N parameter
The activation of the partial batch automatic is only allowed in „B1“ mode.
CP Designation Type
33 Tolerance mode N parameter
6. Component level
Each component can be operated and tested independently from the other components. For
this, the component level of the corresponding component has to be selected. This is made by
pressing the respective K-key (component 1 ⇒ K1 -key).
The component level consists of several component pages, the so-called K-pages (e.g.: K100,
K110, K120, K130, K140 and K150), which contain the required parameters. As all five
component levels have an identical structure, we only describe the K-pages of the first
component below.
Component pages
K150 Alarm configuration component 1 K250 Alarm configuration component 2
K140 Test program component 1 K240 Tes tprogram component 2
K130 Control page for I/O component 1 K230 Control page for I/O component 2
K120 Feeding parameters component 1 K220 Feeding parameters component 2
K111 Modes component 1 K211 Modes component 2
K110 Feeding parameters component 1 K210 Feeding parameters component 2
K100 Individual control component 1 K200 Individual control component 2
You call up the menu page K100 and thus the component level by pressing K1 -key. Selection
of the other menu pages is made after selection of the component level by using the scroll keys
( and ). Sub-menu page K111 is called up by selecting the menu point "mode" on menu
page K110.
The component pages K500 to K850 (components 5 to 8) are not available if only one
internal I/O controller is employed.
Fig.6.2: Component page K100; the values printed in bold type can be selected
You call up page K100 by long pressing of K1 -key. The page is divided into two columns. In
the left column the control functions that are selectable are listed. The individual control
functions are selected with the aid of the cursor and activated by pressing the CR -key.
Fig.6.3: Component page K110; the values printed in bold type can be selected
The menu point I/O configuration permits to configurate the function of the digital output
DO4 and digital input DI1 as per the table below.
Input Function Notes
I: 0 DI1= interlocking standard setting
I: 1 DI1= refill (H-type)
I: 2 DI1= batch cut-out (BA)
O: 0 DO4= batch end
O: 1 DO4= coarse or fine
O: 2 DO4= free
O: 3 DO4= tolerance +
O: 4 DO4= alarm report
Fig.6.4: Sub-menu page K111; the values printed in bold type can be selected
This sub-menu page lists all possible component modes . Selection of the desired mode is done
by means of the cursor. You place the cursor on the desired component mode and push the
CR
-key. Please find a detailed description of the individual component modes in chapter 7.
Fig.6.5: Component page K120; the values printed in bold type can be selected
This component page permits to adapt the feeding parameters to the feeding process. Σ (xdi) =
Coarse feeding
This point permits to determine the speed for coarse feeding. Simultaneously, this is
corresponding to the speed of discharge mode. In „B2“ mode this point is automatically
adjusted and can adopt a value up to 500%.
Fine feeding
This point permits to determine a speed percentage for fine feeding.
Coarse/fine switchover
The input in % as a function of a batch setpoint determines the batch value for switchover from
coarse feeding to fine feeding. On reaching this batch value the coarse feeding stops and after
expiry of the switchover setting time, fine feeding will start.
This component page is used for a control of the states of the analogue and digital inputs and
outputs. The analogue voltages are displayed as percentage in relation to 10 V DC (e.g.: 10 V
DC = 100%).
Description of the menu points:
Menu point Input type of Input Notes
parameters possibilities
Ana.inputs none none Displays the states of the analogue inputs of the component.
Indication in % of 10V DC.
Ana.outputs none none Displays the states of the analogue outputs of the component.
Indication in % of 10V DC or of 20 mA.
Dig.inputs none none Displays the states of the digital inputs of the component.
The digital inputs DI1 to DI8 are listed from the left side to the
right side. A "1" means - the input is set and a "0" means - the
input is not set.
Dig.outputs none none Displays the states of the digital outputs of the component.
The digital outputs DO1 to DO8 are listed from the left side to the
right side. A "1" means the output is set and a "0" means the
output is not set.
Load cell none none This menu point permits a control of the weighing signal if a serial
or a digital load cell are connected.
a) Serial load cell
Monitoring of the serial interface traffic between the serial load
cell and Congrav LM. In the menu field the last six digits of the
ppm-display of the load cell are displayed. The serial load cell has
a resolution of 1 mio. ppm, i.e. for a serial load cell with a
weighing range of 60 kg the following equation is valid: 1 ppm
= 6 mg
Furthermore the status report of the serial load cell (digit 1-3) is
displayed.
0E : Usable weighing range not reached because preload was to
low
0X : weight value unstable
0Y : weight value stable
b) Digital load cell
The digital load cell has two frequencies; indication of the last 16
bits of the counter reading. The display is decimal, i.e. in a value
range of 0 - 65535. With load cells it is normal that the indicated
values are constantly changing.
Analogue input 1: (AI1) To be used for the analogue weighing signal.
1I/O=input / output
Analogue input 2: (AI2) To be used for the analogue tachometer signal of the setting device
of the feeder drive.
Analogue input 3: (AI3) Is only available with external I/O-controllers Congrav T, to be
used for the analogue control signal.
Analogue output : (AO1) To be used for the analogue manipulated variable.
Analogue output 2: (AO2) Is only available with external I/O-controllers Congrav T, to be
used for the analogue actual value output.
Digital inputs : The digital inputs 1 to 5 have the following functions for all components:
Digital input Function Note
DI 1 Interlocking with internal I/O-controller it is
also possible to select refill, auto
tare or gravimetric discharge →
K110
DI 2 Start component a possible start delay will be taken
into consideration.
DI 3 Stop component a possible stop delay will be taken
into consideration.
DI 4 Reset
DI 5 Refill only with external I/O-controller
Congrav T; it is also possible to
select gravimetric discharge .
→K110
The digital outputs are open collector outputs with a common GND on GND
The terminal functions of the inputs/outputs can be seen in the "Technical Documentation".
Fig.6.7: Component page K140; the values printed in bold type can be selected
The component page K140 fulfils in principle the following two functions:
Fig.6.8: Component page K150; the values printed in bold type can be selected
The Congrav LM surveys the feeding operation and gives standard reports of faults during
operation either by an alarm report or by an alarm cut-out. In the mode display the alarms are
displayed as outlined below:
T+ : Positive tolerance, alarm cut-out as per the max. feeding time determined in CP26.
FT : Feeding time, alarm cut-out after expiry of the max. feeding time that has been
determined.
RF : Refill fault, alarm cut-out immediately after expiry of refill time as per CP16.
The digital output "alarm" (DO "alarm" of corresponding component) is activated parallely to
an alarm cut-out. This component page permits to select either an alarm cut-out or only an
alarm report for the listed alarm types. After expiry of the corresponding alarm time (see
above) only an alarm with the option "report only" is announced by the Congrav LM, yet
feeding is not stopped by the Congrav LM . An operation fault with the option "report only" is
indicated as follows:
- The mode display is no more refreshed, i.e. the mode display shows the alarm type in inverse
representation (not blinking).
- Digital output "alarm report" (DO "alarm report") of corresponding component is activated.
- If the option "alarm printout" has been activated on printer page F200, an alarm protocol
will be printed.
The alarm report will be reset by pushing the reset key. In order to select the desired option,
"cut-out" or "report only", the cursor has to be placed on the parameter and the CR -key has to
be pressed.
If the actual batch value that has been fed out is located within the permissible tolerance, batch
feeding will be stopped and the digital output „batch end“ will (DO4) will be set. After expiry
of the batch stabilization time the operating contact will be reset.
If the tolerance range is exceeded, the message „T+“ will appear and the operator has to
decidewhether overfeeding is permissible or not. If the operator accepts overfeeding, the
feeding operation can be continued by activating the reset key. If he does not accept
overfeeding, the feeding operation has to be stopped by activating the stop key, then the fault
indication „tolerance fault“ has to be reset by means of the reset key.
In order to feed out the batch setpoint, the min. filling level has to be = (fill. level min. + batch
setpoint). The setup permits to determine the time for refilling after the start/stop of the
feeding operation. After the start of feeding, there is in general a check whether there is
enough product in the hopper for feeding until the batch setpoint. Should this not be the case,
there is refilling until „filling level max.“
With partial batch feeding the necessary partial batch parameters can be calculated at the start
of the feeding operation. For this reason, no modification of the batch setpoint can be accepted
during batch feeding. For this, the setpoint mode has to be „off“.
BRABENDER TECHNOLOGIE KG, 1996 Copyright as per DIN 34 Page 57
Operating Instructions Congrav LM
If the batch setpoint exceeds the weight value (fill. level max. - underload) and if partial batch
automatic has been activated, the installation cannot feed out the batch setpoint and stops on
reaching the underload mark with the alarm message „underload“. If manual refill is activated
during batch feeding, the batch has to be broken off.
FT = setpoint • 3600 + 30 s
check. max. output
Example: setpoint = 10 kg
check. max. output = 400 kg/h
FT = 10 kg • 3600 + 30 s = 120 s
400 kg/h
This time depends very much on the product and has to be determined for each application.
DDW-H2x-M-x DDW-H3x-FWx
• All transport catches (painted red) have to be removed from the loss-in-weight feeder
(fig.8.2).
only DDW-H2x-M-x
♦ If no weight value will be displayed (fig.8.4) after you have called up page K100 (page
K200 for feeder 2, etc.) you have to start "auto-tare" function (fig.8.5). Thus, the "auto-
tare" value will be reset to zero and a positive weight value will be displayed. As negative
weight values cannot be displayed, a positive weight value (G0) is required for a perfect
control of the weighing device.
♦ By a brief loading and unloading of the feeder (add/take off weight) check whether the
display is free from changes. This means that the weight display must always show the
initial value if the control weight has been taken off or the total value if the control weight
BRABENDER TECHNOLOGIE KG, 1996 Copyright as per DIN 34 Page 61
Operating Instructions Congrav LM
has been added. If a change occurs you have to check the complete mechanical structure of
the feeder.
♦ Place a defined test weight (normally app. 30 % of the weighing range) on the hopper of
the loss-in-weight feeder. The exact weight value should be displayed now. If this should
not be the case correct the lever arm CP15 according to the formula:
GT
H corr = ⋅ H act
GD − G0
After a correction of the lever arm the new lever arm has to be checked accordingly.
♦ The weight value that is possibly still displayed after a correction of the lever arm and with
the test weight taken off is written in the tare memory after call-up of the "auto-tare"
function. After that the weight value displayed will be 0.000 kg.
With a weight value that is higher than 5 % of the total weighing range the "coarse tare"-
range CP06 has to be increased, as the "auto-tare" function permits to tare max. 5 % of
the weighing range. Therefore, the total weighing range is divided as illustrated in fig.8.6.
useable
weighing range
The static inspection of the first feeder is now concluded. This check has to be effected
separately for all feeders. If this has been done you can go on with the commissioning of the
individual feeders.
♦ Select page K100 (page K200 for feeder 2, etc.) and start the installation (fig.8.8).
K100 DI B1 B1 B1 B1 B1 B1 B1 PLC I=off
HS-Type Feeder 1
Start Setpoint 100.000 kg/h
Stop Actual value 0.000 kg/h
Alarm reset Speed 0.000 %
Refill Weight 23.543 kg
BA cut-out Tare weight 0.000 kg
♦ Check the sense of rotation of the drive motors of the loss-in-weight feeder . For easier
checking flashes indicating the senses of rotation are attached to each drive (fig.8.9).
♦ A tachometer permits to check the adjustment of the speed controller of the feed drive. If
the drive has a nominal speed of 3000 min-1, the speed has to be 300 min-1 if the setpoint is
10 % and 2700 min-1 if the speed is 90 % (setpoint modifications: please see page F300).
Should there be deviations despite the preadjustment in our works, they have to be
adjusted by means of our "adjustment instructions for speed controllers".
♦ After completion of the a.m. checks the installation can be stopped again (page K100).
♦ You start manual filling by putting the cursor on page K100 (page K200 for feeder 2 etc.),
menu point "refill" and pressing CR -key (fig.8.10). The feeder will be filled up to "filling
level max.". Filling is finished, if the indication on the mode display changes from "RF" to
"DI".
♦ Select mode "DI" (discharge) and enter setpoint 7,5 % on page F300 (fig.8.11).
♦ Select page K100 (page K200 for feeder 2 etc.) and start the installation. If the feeding
device is filled with product, the installation can be stopped again (fig.8.12).
♦ Select mode "CM" (checking max. output) on page K110 (page K210 for feeder 2 etc.)
(fig.8.13), then start the installation on page K100 (page K200 for feeder 2 etc.). Thus, the
sequence "checking max. output" has also been started. During this mode feeder specific
parameters are determined and stored. Page K110 (page K210 for feeder 2 etc.) displays
the addition of the product quantity fed in kg under menu point "checking of max. output".
After conclusion of mode "checking of max. output" the feeder switches off automatically
Fig. 8.13: Component page K110, selection of function "checking max. output", component 1
Now the feeder is ready for operation. In case of feeders with a tray an adjusting nozzle at the
inlet of the tray permits to set the filling level of the tray so that a further adaptation of output
is possible (fig.8.15).
After having changed the position of the adjusting nozzle you have to carry through "checking
max. output", as described above.
9. Appendix A
Fault UNDERLOAD
Cause : a) During refilling no material flow.
b) During "CM"-mode the underload value was undercut.
Remedy : a) Check material store and flow.
b) Check material slide valve or refill device on function.
c) Activate manual refill, because with "CM"-mode no automatic refill
will be activated.
Fault OVERLOAD
Cause : a) To much material in hopper.
Remedy : a) Check material slide valve or refill device on function.
b) Check max. filling level CP18 and overload CP05.
c) Switch on mode "DI" (discharge) until reaching of filling level max.
Fault AV FAULT
Cause : a) Controller beyond filter range.
Remedy : a) With extremely fluctuating speed check controller 1 - parameter on
pages K120 - K820, also check the control automatic CP27.
b) Check environment for external disturbances (e.g. vibrations caused
by starting machines etc.), correct if necessary.
c) Run "CM" mode.
d) Increase filter limit values CP28 .
e) Increase AV-cut-out time CP25.
Note: d) and e):
With increasing values the feeding accuracy of the installation will
decrease.
Fault CM FAULT
Cause : a.) No loss of weight.
b.) Wrong CM values due to external disturbances (e.g. CM-value range
2 > CM-value range 3
Remedy : a) Checking of feeding system.
b) Checking whether there are external disturbances in the environment
of the feeder.
Fault MM FAULT
Cause : Access to a memory module in Congrav LM could not be made
correctly.
Remedy : If this fault occurs we recommend you to contact the service division of
Brabender Technologie KG.
Fault EE FAULT
Cause : Access to the EEprom in Congrav LM could not be made correctly.
Remedy : If this fault occurs we recommend to contact the service division of
Brabender Technologie KG.
Note: Terminal connections of Congrav LM, Ia, Ib please see "Technical Documentation".
Index —D—
Data setting 16
Delay times 28
Derivative action corection 48
Derivative action correction 39
—A— DI 10
Actual batches 30 Dialogue language 16
Actual value kg/h 30 Digital inputs 57
Actual value output 38; 45 Digital outputs 57
Adjusting nozzle 71 digital inputs 4; 19
Alarm configuration 60 digital inputs (configuration) 53
Alarm cut-out 60 Digital outputs 19
Alarm cutout 33 Digital outputs (Test) 59
Alarm messages 33 Discharge (DI) 64
Alarm printout 23 Display 9
Alarm report 60 Display lightning 7
Alarm report page 33 Drives (checking) 67
Alarm reports 33
alarm reset(component) 52 —E—
alarm stop 25; 28
Alarms 33 EE 10
all totals 25; 29 EE-Fault 74
Analogue inputs 57 EEprom-error 33
Analogue output (Test) 59 EE-xxxx 33
Analogue outputs 57
Auto-tare 53 —F—
AV fault 73
average value (weight acq.) 42 Faults 72
Average weight acq. 38 Feeder blocked 35
Feeder parameters 56
Feeder type 39
—B— Feeder type 38
B1 10 Feeding tolerance 38; 47
B2 10 Fill fault 33
BA cut-out 52 Fill. level maximum 38
Batch 1 (B1) 62 Fill. level minimum 38
Batch 2 (B2) 63 Fill. Max. < Min 34
Batch report 23 Filling level maximum 44
Batch stabilization time 38; 47 Filling level minimum 43
Baud rate 18 Filter 38; 45
Bulk density 53 Fine feeding 56
Bulk density (Indication) 34 Function keys 6
—C— —G—
calibration data 12 group setpoint 27
Calibration program 36
change 66 —H—
Checking max. output 53
CM fault 74 Hard copy 7
Coarse delay 38; 48 Hopper contents 43
Coarse feeding 56 Hopper volume 38
Coarse tare 38; 41 host computer 4; 18
Coarse/fine switchover 38; 48 Host computer configuration 18
Commissioning (DDW-H) 65 Host computer operation 16
Commissioning with product 70
Communication fault 74 —I—
Component control 52
Component level 51 I/O control 57
Component modes 55 I/O-configuration 53
Control deviation +/- 72 Identnumber 18
Cursor 7 Indic. of actual value 38
Cursor keys 7 Indication of actual value 43
Input line 9; 15
key switch 12
keyboard 4; 6
—R—
Recipe % 17
—L— Recipe % - operation 26
Recipe faulty 20
LC 11 Recipe kg 17
LED (K-keys) 8 Recipe kg - operation 26
LED (start-key) 8 Recipe number 20
LED functions 8 Refill 52
Lever factor 38; 43 Refill fault 72
Load cell 57 Refill timing 38; 46
Load cell (alarm message) 73 Release 36
Load recipe 20 Reset all totals 32
Reset EEprom1 24
—M— Reset EEprom2 24
Reset functions 24
Maximal refill time 38 Reset RAM 24
Maximum batch size 38; 40 Reset totalizer 32
Maximum refill time 46 RF 10
Memory Board 22
Memory Card 20
Memory Card missing 20
—S—
Memory Card Status 20 S- 11
menu pages 9 S+ 11
menu pages (overview) 13 SB-Fault 74
menu-supported parameter input 14 scroll keys 6
Message line 9 Select 25
Min < Underload 34 Selection 25
MM 10 sense of rotation 69
MM-xxxx 33 Serial load cell (Test) 59
Mode 16; 53 Setpoint % 25
Modes 55 setpoint error 26
MS 10 setpoint input 26
Setpoint kg/h 25; 30
—N— setpoint limitation 26; 27
Setpoint mode 38; 47
number code 12; 36 Setpoint pages 25
numerical code 24 Setpoint parameters 20
Numerical keys 7 SIM 9
numerical parameter input 15 Simulation 59
Speed indication 31
—O— Speed maximum 38; 42; 73
Speed Min/Max 33
OL 10 Speed minimum 38; 42; 73
operating faults 8 ST 10
Operating keys 7 Stabilisation time 38; 46
operating status 8; 9 Start (component) 52
operation page 16 Start conditions 33; 34
Overload 33; 38; 40; 72 Static inspection 66
Overload < Max. 34 status line 9
Stop (component) 52
—P— Store recipe 20
sub-menu 14
parameter activation 15 switch function 15
parameter inputs 14 Switch-over kg/% 39; 48
Parameter value 36
Partial batch automatic 39; 48
PLC 9
—T—
Preliminary checks 65 Test 59