GS38300143 - Safety Relay Output
GS38300143 - Safety Relay Output
Input Specifications
Manual restart 1 NO Contact 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
Open loop voltage 5 V 115V 115V
Short-circuit current 100 µA P N P N
SUPPLY
Contact resistance < 1 kΩ
Cable length max. 2 m
Dielectric voltage
Inputs – Dupline® None
Mode of Operation
The Safety Output module be open, thus keeping the Any type of Dupline® Chan- note that all Dupline® chan-
GS38300143 monitors up system in a safe state. Find nel Generator can be used, nel addresses used for Safe-
to 63 Safety Input modules, below a principle diagram of as this component is not ty Input modules must be
type number GS751021xx. a DuplineSafe system. part of the safety function. monostable. Split I/O mode
Each Safety Input module The Channel Generator However, it is important to and intelligent channel func-
is monitoring the status of tions are not allowed. If this
one potential-free contact rule is not obeyed, the relay
in a safety device, e.g. an Safety contacts of the Safety Out-
emergency stop palm but- Output put module will remain in the
module
ton or pull cord switch. The open position in any situa-
Safety Input modules are tion.
Safety
continuously transmitting on Input
the Dupline® bus the status module Contactor 1
of the safety contacts using Combined Systems
a dynamic signaling princi- It is allowed to use stan-
ple on two Dupline® channel Tx 0 VDC dard Dupline® modules on
addresses (please refer to 24 VDC the channel addresses not
GS751021xx datasheet for used for safety signals, thus
more details). allowing combined systems.
Tx
During configuration of the
Safety Output module, the Contactor 2
Monitoring from a PLC, PC
user must define on which or Text Display
Tx
Dupline® channel address- 0 VDC There are two products
es Safety Input modules 24 VDC available for interfacing
shall be monitored. If all the a DuplineSafe system to a
configured Safety Input Tx
PLC, PC, Text Display or
modules are sending a Touchscreen. One possi-
RS 232 /
valid “safe-state” signal,
then the relay contacts of Channel RS 485 PLC / bility is the Profibus-DP
Generator Controller gateway (GS38910125),
the Safety Output module the other possibility is
will be closed. In any other the small Modbus inter-
situation (non-safe signal face GSTI50 for Text dis-
received from one or more plays and Touchscreens.
Safety Input modules or bus DuplineSafe Principle Diagram
Using these products, it
fault), the relay contacts will is possible to monitor the