AGENDA
01 Fire Triangle
05 Summary
• Flash-point temperature – The minimum temperature at which the liquid gives off sufficient vapor to
form an ignitable mixture with air near the surface of the liquid or within the test vessel used.
• Highest temperature which is attained in service under the most adverse conditions (but within the
specified tolerances) by any part or surface of Ex Equipment.
• For Equipment in Explosive atmosphere-this could occur internal to equipment or external to the equipment
• The maximum surface temperature marked on the equipment includes safety margins depending on the EPL of the
equipment
Area
Classification T Suitable equipment for Area Classification T Code
Code
T1 (450°C) T1 (450°C), T2 (300°C), T3(200°C), T4(135°C), T5(100°C), T6(85°C)
T2 (300°C) T2 (300°C), T3(200°C), T4(135°C), T5(100°C), T6(85°C)
T3 (200°C) T3(200°C), T4(135°C), T5(100°C), T6(85°C)
T4 (135°C) T4(135°C), T5(100°C), T6(85°C)
T5 (100°C) T5(100°C), T6(85°C)
T6 (85°C) T6(85°C)