1200H April 13, 2023

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Date: Roving Time Weather Condition

04-13-2023 1200H Cloudy

Cooling Tower and Chilled Water System

Chiller Unit No. ▲


% Input Full Load Ampere Total Running Hours Running Status
1 71.4 640 Normal
2 - - Standby

Equipment Name ▲
Running Status.
Chilled Water Pump 1 Normal
Chilled Water Pump 2 Standby
Condenser Pump 1 Standby
Condenser Pump 2 Normal
Cooling Tower 1 Standby
Cooling Tower 2 Normal

General Power Equipment

Number

General Power Equipment Status Running Status..

1 MVSG A Normal
2 MVSG B Normal
3 LVSG A Normal
4 ATS-LVSG A Normal
5 LVSG B Normal
6 ATS-LVSG B Normal
7 LVSG C1 Normal
8 ATS-LVSG C1 Normal
9 LVSG C2 Normal
10 ATS-LVSG C2 Normal
11 LVSG D1 Normal
12 ATS-LVSG D1 Normal
13 LVSG D2 Normal
14 ATS-LVSG D2 Normal
15 FSS A (Novec) Data Hall 1&2 Normal
16 FSS B(Novec) Data Hall 1&2 Normal
17 Transformer C Normal
18 Transformer D Normal
19 FSS A (Novec) Data Center 1 Normal
20 FSS B (Novec) Data Center 3 Normal
21 Transformer A Normal
22 Transformer B Normal

Second Floor Electrical Rooms

Temp Temp Temp Temp RH RH RH RH


Second Floor Electrical Temp Temp Cold Cold Hot Hot RH RH Cold Cold Hot Hot
Rooms ▲
Max Min Aisle Aisle Aisle Aisle Max Min Aisle Aisle Aisle Aisle
Max. Min. Min. Max. Max. Min. Max. Min.
2F Data Center 1 35 19 - - - - 67 30 - - - -
2F Data Center 2 - - 22 17 20 28 - - 72 58 63 47
2F Data Center 3 - - 26.4 24.7 28.7 31.6 - - 55 51 44.6 38.4
2F Rectifier 1 23 - - - - - 57 - - - - -
2F Rectifier 2 22 - - - - - 59 - - - - -
2F UPS 1 21 - - - - - 64 - - - - -
2F UPS 2 19 - - - - - 62 - - - - -
Transformer A 30 - - - - - 71 - - - - -
Transformer B 30 - - - - - 67 - - - - -

Number

Room Name Running Status...

1 Transformer A Ventilation Fan No.1 Standby


2 Transformer A Ventilation Fan No.2 Standby
3 Transformer B Ventilation Fan No.1 Standby
4 Transformer B Ventilation Fan No.2 Standby
5 Rectifier 1 FCU #1 Normal
6 Rectifier 1 FCU #2 Standby
7 Rectifier 1 FCU #3 Standby
8 Rectifier 2 FCU #1 Standby
9 Rectifier 2 FCU #2 Normal
10 Rectifier 2 FCU #3 Standby
11 2F DATA Center 1 PACU #1 Normal
12 2F DATA Center 1 PACU #2 Normal
13 2F DATA Center 1 PACU #3 Standby
14 2F DATA Center 1 PACU #4 Normal
15 2F DATA Center 1 PACU #5 Normal
16 2F DATA Center 1 PACU #6 Standby
17 2F DATA Center 1 PACU #7 Standby
18 2F DATA Center 1 PACU #8 Normal
19 2F DATA Center 2 PACU #1 Standby
20 2F DATA Center 2 PACU #2 Standby
21 2F DATA Center 2 PACU #3 Standby
22 2F DATA Center 2 PACU #4 Standby
23 2F DATA Center 2 PACU #5 Normal
24 2F DATA Center 2 PACU #6 Normal
25 2F DATA Center 2 PACU #7 Standby
26 2F DATA Center 2 PACU #8 Standby
27 2F UPS 1 FCU #1 Standby
28 2F UPS 1 FCU #2 Normal
29 2F UPS 2 FCU #1 Standby
30 2F UPS 2 FCU #2 Normal
31 2F Data Center 3 Fanwall #2 Normal
32 2F Data Center 3 Fanwall #3 Standby
Ground Floor Electrical Rooms

Ground Floor Electrical Rooms ▲


Temperature °C. Humidity %.
Battery Room 1 22.5 75
Battery Room 2 23 81
Battery Room 3 20.4 61
Battery Room 4 23.5 83

Number Room Name. Running Status....


1 Synchro 1 FCU #1 -
2 Synchro 1 FCU #2 Normal
3 Synchro 2 FCU #1 Normal
4 Synchro 2 FCU #2 Normal
5 Battery Room 1 FCU #1 Standby
6 Battery Room 1 FCU #2 Normal
7 Battery Room 1 FCU #3 Standby
8 Battery Room 2 FCU #1 Normal
9 Battery Room 2 FCU #2 Standby
10 Battery Room 2 FCU #3 Standby
11 Battery Room 3 FCU #1 Normal
12 Battery Room 3 FCU #2 Standby
13 Battery Room 3 FCU #3 Standby
14 Battery Room 4 FCU #1 Standby
15 Battery Room 4 FCU #2 Normal
16 Battery Room 4 FCU #3 Standby

Number

Emergency Backup Power Status..

1 Genset 1 Standby
2 Genset 2 Standby
3 Fuel Pump 1 Auto
4 Fuel Pump 2 Standby
5 Synchro 1 Panel Standby
6 Synchro 2 Panel Standby
7 Daytank 1&2 (Liters) 4957.2
8 Daytank 3 (Liters) 5672.5
9 Total Diesel Fuel Reserve (Liters) 10629.7

2F Parameter Reading LVSG A LVSG B UPS 1 ▼


UPS 2 DP Rectifier A DP Rectifier B
Voltage (LL) Line 3 405 396 404 397 406 397
Voltage (LL) Line 2 403 406 402 406 403 406
Voltage (LL) Line 1 396 402 395 403 396 403
Current (LL) Line 1 573 629 189 158 224 223
Current (LL) Line 3 566 617 171 155 217 212
Current (LL) Line 2 530 629 165 154 219 218
Power KW (Ave) 378.33 427.2 111.67 98.77 151.62 150.19
- - - - - - -

Number 2F UPS 1 and UPS 2



Rooms Load on Inverter Bypass Battery

1 2F UPS 1 unit Load on Inverter Normal - -


2 2F UPS Battery 1 - - - Normal
3 2F UPS 2 unit Load on Inverter Normal - -
4 2F UPS Battery 2 - - - Normal

Number

2F Parameter Reading. CPS1 (Rectifier Rm2) CPS2 (Rectifier Rm1) CPS3 (Rectifier Rm2) CPS4 (Rectifier Rm1)

1 Battery Voltage (Volts) 379.6 379.6 379.6 379.6


2 Battery Current (Amps) 7 3 21 1
3 Battery Temp °C 23 22 25 21
4 Rectifier Current (Amps) 375 374 194 188
5 Rectifier Capacity % 32 23 17 16
6 Battery Remaining Capa… 100 3360 3360 3360

2F DC1 (DC-DC
Converters) ▼
1-1 1-2 1-3 1-4 1-5 1-6 2-1 2-2 2-3 2-4 2-5 2-6 3-1 3-2 4-1 4-2

Current (Amps) 551 411 338 376 423 458 596 339 411 361 398 439 585 353 585 364
% Utilization 36 27 22 24 27 38 39 22 27 23 26 29 38 23 38 24

2F DC2 (DC-DC
Converters) ▼
3-3 3-4 4-3 4-4

Current (Amps) 61 2 64 2
% Utilization 4 0 4 0
Third Floor Electrical Rooms

Third Floor Electrical Rooms ▲


Temperature °C Humidity %
3F UPS 1 22 68
3F UPS 2 23 60
Transformer C 30 84
Transformer D 28 78

Number

Rooms Name... Running Status.....

1 3F UPS 1 FCU #1 Standby


2 3F UPS 1 FCU #2 Standby
3 3F UPS 1 FCU #3 Standby
4 3F UPS 1 FCU #4 Normal
5 3F UPS 2 FCU #1 Normal
6 3F UPS 2 FCU #2 Standby
7 3F UPS 2 FCU #3 Standby
8 3F UPS 2 FCU #4 Standby
9 3F Data Hall 1&2 FANWALL #1 Normal
10 3F Data Hall 1&2 FANWALL #2 Standby
11 3F Data Hall 1&2 FANWALL #3 Normal

Number ▲
3F Parameter Reading LVSG C LVSG D UPS 1. UPS 2.
1 Voltage (LL) Line 1 401 402 398 399
2 Voltage (LL) Line 2 404 405 397 398
3 Voltage (LL) Line 3 395 396 398 399
4 Current (LL) Line 1 74 79 7.8 3.6
5 Current (LL) Line 2 107 98 13.5 10.5
6 Current (LL) Line 3 103 13.5 11.6 7.2
7 Power KW (Ave) 63.79 65.35 111.67 98.77

Number ▲
3F UPS 1 and UPS 2 Rooms Load on. Inverter. Bypass. Battery.
1 3F UPS 1 unit Load on Inverter Normal - -
2 3F UPS Battery 1 - - - Normal
3 3F UPS 2 unit Load on Inverter Normal - -
4 3F UPS Battery 2 - - - Normal

Remarks

Normal Operation / Chiller 3 standby

Facility Management Team on Duty

Technician on Duty
Roger Noleda/ Rico Gonzales/ Paul Marking Mateo/ Juleus Bines/ Jeffrey Cabigao/ Jerzhkie Manuel
Engineer on Duty
Paul Cansino/ Sarah Jean Langitgan/ Jan Aubrey Batangoso