CSC-2000 (V2)

Substation Automation System


Product Guide
Version:V1.00
Doc. Code: 0SF.492.071(E)
Issued Date:2011.10
Copyright owner: Beijing Sifang Automation Co., Ltd

Note: the company keeps the right to perfect the instruction. If equipments do not agree with
the instruction at anywhere, please contact our company in time. We will provide you with
corresponding service.

®
is registered trademark of Beijing Sifang Automation Co., Ltd.

We reserve all rights to this document, even in the event that a patent is issued and a different
commercial proprietary right is registered. Improper use, in particular reproduction and
dissemination to third parties, is not permitted.

This document has been carefully checked. If the user nevertheless detects any errors, he is
asked to notify us as soon as possible.

The data contained in this manual is intended solely for the IED description and is not to be
deemed to be a statement of guaranteed properties. In the interests of our customers, we
constantly seek to ensure that our products are developed to the latest technological standards
as a result; it is possible that there may be some differences between the hardware/software
product and this information product.

Manufacturer:
Beijing Sifang Automation Co., Ltd.

Tel: +86-10-62961515
Fax: +86-10-62981900
Internet: http://www.sf-auto.com
Add: No.9, Shangdi 4th Street, Haidian District, Beijing, P.R.C.100085
Overview
and larger system, and solve the
CSC-2000 series automation system
problems of interoperability of operation
(CSC-2000 system) is a layered and
systems. To sum up, V2 system is the
distributed substation automation
comprehensive upgrade of CSC-2000
system, with the integrated functions of
system.
monitor, control, measurement, record,
relay protection, safe-automation V2 system passed the technology
equipments, communication and remote authentication of China Electric
control. The system has the ability to Machinery Engineering Institute and
operate in different voltage levels and acquired higher evaluation on Nov.12,
guarantee the power system running 2005. The local SCADA, telecontrol, bay
economically, safely, reliably, and stably. layer protection, and bay control
CSC-2000 system can be widely used in equipments meet the IEC61850 and can
different voltage level substations. be applied in various substations in
1000kV level and below. V2 system is
Basing on years of research and
also compatible with present protocols.
development in substation and
That solves the problem of transition
experience of engineering application,
from current protocols to IEC61850.
and referring to international standard,
Because of the excellent
CSC-2000 (V2) substation automation
open-endedness, it is convenient to
system (V2 system) is improved to adapt
apply the current substation automation
the development of higher voltage level
equipments and upgrade the system.

1
Features
General features of the system
‹ Full layered and distributed design, communicate mutually to realize
installed in distributed layers, operation interlock in different
economizing on space and cable; electric units;

‹ Bay layer equipments can stand ‹ Redundancy technique widely used


severe environment; in key links, including workstation
redundancy, network redundancy,
‹ Full bay unit oriented configuration
telecontrol channel redundancy, and
to operate and maintain
so on, which improves the system
conveniently and reliably;
reliability significantly;
‹ Workstations in substation level
‹ Complete AVQC functions;
operating equally and dependently,
and can be extend more reliably ‹ Flexible interface of interlock
and conveniently; system function in substation layer;

‹ Bay layers adopt flexibly networked ‹ Substation adopts general


and highly reliable hardware embedded communication
platform; hardware platform;

‹ Efficient, flexible and reliable ‹ Local SCADA is applicable to mixing


communication network; platform with multiple operation
system and multiple hardware
‹ 3 control modes realized: remote,
system;
local SCADA and on-site, and
correct rate up to 100%; ‹ Flexible and reliable sequence
operation scheme satisfies
‹ Operation monitoring of primary
requirements of programmed
equipments are independent of
operation in different conditions.
station layer workstations; bay
control equipments can

2
Support IEC61850
To specify the system and network of the ‹ Abstracted communication service
substation automation system, and interface ACSI separate functions
solve the problems of interoperation, and specific communication network,
IEC TC57 WG10, 11, 12 started to with excellent stability;
formulate the international standard for
‹ Special communication service
system and network of substation
mapping SCSM technique,
automation system. This standard refers
corresponds with particular bottom
to substation layer bus and processing
protocol one to one, with good
layer bus to provide a standard with
open-endedness;
interoperability for all the substation
automation system manufacturers. ‹ Excellent interoperability.
Since IEC 61850 has become the formal
IEC 61850 represents the direction of
international standard, China also
the substation automation technology,
adopts IEC 61850 as national standard
and influences other techniques of
and industry standard. The features
electrical power system automation
include:
profoundly. V2 system realizes the
‹ Modeling technique for complete support of IEC 61870, and the
object-oriented; compatibility of other products in Sifang
range, without any accessional
‹ Layered, distributed system is used
equipments or software.
to describe the substation
automation system;

3
Communication network and protocols
Station control layer network adopts Station control layer supports two
industry Ethernet network in V2 system. communication protocols: IEC 61850
Both station control equipments and bay and CSC 2000 protocol. Station control
layer equipments can support industry layer equipments (local SCADA,
Ethernet interface directly, and V2 telecontrol system), and bay layer
system can realize the redundancy equipments (measurement equipments,
configuration of network and interface high-voltage protection equipments,
for requirements. CAT 5 UTP can be low-voltage measurement and
used to electrical connection in main protection integrated equipments) can
control room or bay room, and fiber support these two protocols, and other
optical can be adopted for the protocols via communication
connection between main control room management equipment, like IEC
and bay room. Fiber optical can also be 60870-5-103(DL/T 667-1999), different
installed in bay rooms for special versions of Ethernet 103 protocol, IEC
requirements. 60870-5-104, Modbus/TCP,
Modbus/RTU and so on.

4
System functions
Local SCADA system functions
The Local SCADA system software can analysis and dynamic coloring help
run in both Windows operation system operators to grasp the operation
and UNIX operation system, and also conditions easily.
can be widely applied in windows/Unix
The system is a high integrated system.
multiple system platforms.
Interlock system and local SCADA
The system has significant technical system share the same database and
superiority compared with other graphics to prevent the false operations;
products. The real-time database adopts the local SCADA system, realizes
distributed structure; the graphics regulation of transformer voltage level in
system of the software is self-developed, substation by integrating VQC function;
and integrated with real-time database; protection management function
information processing, searching, and enables the system operating remote
filtrating and intelligent second alarming manage about protection equipments.
are improved in alarm system; topology

5
Supporting multiple system realize functions like fault push
platforms graph and alarm; graphics can also
be reflected in real-time database.
V2 SCADA system supports mixed
platform in both software and hardware: Intelligent alarm system
‹ Supports Windows/UNIX mixed Intelligent alarm system has following
operation system platform significations:

According to different requirements, ‹ Self-defined alarm types


all the operator workstation can
The system improves the fixed
apply UNIX operation system or
alarm modes from predefined by
Windows operation system. In
manufactures, to can be completely
addition, the operator station and
defined by users, which may satisfy
engineer station can adopt Windows
the different requirements for
operation system when the server
different geographical regions.
employs UNIX operation system.
The system also supports several
‹ Supports 64/32 bit mixed hardware
preinstalled alarm type templates for
platform
different requirements of regions.
According to different requirements, When the system is installed in first
all the operator workstation can time, on the basis of the region,
apply 64 bit hardware or 32 bit typical template can be selected
hardware. Additional, the operator and alarm types then can be
station and engineer station can generated automatically without
adopt 32 bit hardware when the manual definition.
server employs 64 bit hardware.
‹ Alarm filtration
Graphics library integrated in
Alarm filtration includes following
database
functions:
The integration of graphics and
It can be set in alarm types that only
database decreases the workload in
important alarms can pop up alarm
project design and maintenance, makes
window in screen, so less important
system operating more reliably.
alarm will not affect current
‹ Real-time database can be built operations.
automatically in the process of
In the alarm window, it can be
engineering graphic. Editing
selected that only to monitor
graphics can build relevance with
particular alarm information, and
corresponding graphics elements,
filter the rest.
which avoids false operation when
relating manually. The “alarm lights” (the alarm lights
are suspended in the information
‹ Real-time database has close
window of screen edge, including
relation with graphics. Real-time
corresponding icons of alarm types,
database can be changed to drive
and do not affect the normal local
the graphics conveniently, and

6
SCADA operations) will be flashing to guarantee the distributed
when some alarm information configuration of database. Redundant
received. Operators can determine database structure adopts one main and
to check or continue current one backup structure. Main database
operations. can update data simultaneously with
backup database, or independently.
‹ Graphic alarm light
When fault occurs in main database,
Each SCADA menu of the system backup database becomes new main
can apply the own push graph alarm database. Image database structure is
light, which can be configured to composed of a reference database
use or not. When a protection event (source database) and one or several
occurs and some switch trips, the image databases. Each database is
system considers the event a fault. proper copy of source database. The
The fault graph will be inferred and generation processing of image
pushed automatically in screen. database is the copy processing of
User can also regulate the source database, and all the changes of
quantities of push graph lights in source database will be reflected the
alarm system. When alarm happens, image database.
alarm light of relative graphic starts
To be specific, distributed real-time
to flash. Operators can click flashing
database has the following features:
light to enter into corresponding
SCADA menu, or ignore alarm and ‹ Supply flexible mechanism for
continue current operation. different data structure and data
model. Structure and capacity of
‹ Second alarm function
real-time database can be altered
Some alarm signal can be set according to modifying configuration
second alarm function. If the files.
occurrence time exceeds limit or
‹ Support redundant configuration.
occurrence times exceeds limit in
Main server and backup server
setting time, the system will report
standby mutually. Each client node
the alarm information again.
has complete backup copy of
‹ Intelligent retrieval real-time database.

The occurred alarm signals, not ‹ Supply distributed access


reset or confirmed, can be mechanism. Each node can access
organized in accordance to bay real-time database via interfaces.
level by system. The formed
‹ Support concurrent access to
retrieval can be viewed and
database and guarantee the
checked for operators.
security, consistency, and integrity
Distributed real-time database of data.

Real-time database management ‹ The function of database recovery


system supports redundant database and reset when system in fault.
structure and image database structure,
‹ Quick copy and backup function of

7
database. management, sampling values,
operation events record and
‹ Support multiple users and multiple
interrogation of equipments version.
computer nodes, and guarantee
real time. The main features:

‹ Supply interactive user and program ‹ Friendly interface and easy


with multiple flexible interfaces and operation;
services.
‹ Reasonable authority management;
‹ Real-time and online work mode. different authorities are needed
The modification and refresh of when interrogating setting value and
real-time database process online. modifying setting value;
The real-time database of all the
‹ Interrogated setting values can be
nodes can be refreshed
saved and printed; the saved setting
synchronously after the
values also can be downloaded to
modification.
equipments.
Protection management function
Topology analysis and dynamic
Protection management program coloring function
achieves the central management of all
Topology analysis and dynamic coloring
protection equipments, including all the
function can identify the electrical
Sifang protection equipments and the
situation in graphical interface according
protection equipments with protocol
to status of primary equipments, which
converter interfaces from other
helps operator grasp the entire working
manufacturers. Specific functions
circumstance in the substation.
contain: protection setting values

8
Advanced applications
With the improvement of intelligent frequently used advanced applications
requirements in substation, increasingly in SCADA system, including sequence
advanced applications are realized. The control, interlock system, VQC and so
following sections will introduce some on.

9
IED in bay unit but also the
Sequence control bus-couple bay control IED as well
as the protection IEDs.
Sequence control implements
‹ Operation in several bays: more
pre-defined operation sequences
than two bays involved sequence
according to programs automatically, to
control operation, like large-scale
realize “one-click” operation. The control
switching operations.
sequences in this process are saved in
operation sequences. Various statuses The implementation of sequence control
are defined into state, like operation process as follow:
state and maintenance state. The
‹ Acquire current state (source state)
operation sequences include multiple
from HMI (local SCADA system or
operation steps with sequence, and
control center), and input target
each step contains interlock logic,
state in human computer
operation content, confirmation logic,
interaction;
and so on.
‹ HMI obtain the operation
The function and process of
sequences;
sequence control
‹ The information of operation
The program control can realize the
sequence is displayed by HMI, and
states formation, saves,
sequence control operation is
implementations, and judgment of
initiated manually;
operations logic and states of operation
sequences besides of normal SCADA ‹ Implement all steps following the
functions. The difference of diversified operation sequence, and current
schemes reflects the realization of step and implementation state will
above functions. be updated according to
corresponding information in HMI;
The operation of sequence control can
be divided in three types: ‹ Operations like Emergency Stop,
Pause, and Continue can be
‹ IED operation: all the steps in the
executed in HMI in the process of
operation sequences are finished in
sequence control implementation.
a single IED in the bay, like 10kV
operation state shifted to Distributed sequence control
maintenance state. scheme
‹ Operation in several IEDs: the The key configuration of distributed
operations are for the single bay but sequence control scheme is CSI-200E
need to be realized by more than bay control equipment or CSC-200
two IEDs, like bus bar I operation protection and bay control integrated
shifted to bus bar II operation in equipment. The bay level equipments
220kV bay. The operation process save and implement the operation
not only refers to the bay control sequences and judge the states of bay

10
level operation (including IED operation In sequence control process,
and cross IEDs operation in bay), equipments upload step information
meanwhile local SCADA system or to workstation, and workstation
control center stores and carries out the displays the implementation step of
operation sequences. Most operations in the information. The judgment of
bay are achieved by bay control state is achieved in bay level
equipments, which decreases the equipments.
unnecessary information interaction and
‹ The bay level equipments need to
improve the execution efficiency; IEDs
achieve the control of relative bays,
are set in bays, so it is no effect for the
setting value switches and strip
bay even in bay extension; bay level
control of bay level protection and,
equipments can achieve information
and also the interlock information
interaction with local SCADA system
transmission and control operation.
and telecontrol machine synchronously,
Interlock information exchanges
so both local operation and remote
directly from equipments to
operation are supported.
equipments, and control operation is
The features of bay level operation: realized by station control devices.
The information does not specify
‹ Bay level operation sequences are
particular protocols, but supports all
stored in bay level equipments,
the communication protocols.
which are the only source of
operation sequences; the bay level ‹ It is necessary to expend or apply
operation sequences include the ASDU of telecontrol protocols
operations from the bay as well as flexibly for sequence control in
the relative bays. For example, dispatching end. Expansion and
220kV line bay control IED controls selection should follow the principle
soft strips of line protection in the below:
bay or 220kV bus-couple breakers.
1. Use existing ASDU in standard
‹ State formation tools: operation version at first and then
sequences and the state formation extended ASDU.
of states are downloaded to lay level
2. The extended ASDU should
equipments by off line tools in
follow the current frame
SCADA system.
structure and polling process.
‹ The process of implement of
3. The state of bay in sequence
sequence control in operator
control is expressed by
workstation or control center (via
telemetry.
telecontrol):
4. Sequence control commands
Workstation reading operation
adopt setting command, source
sequences → equipment uploading
states, object states, as well as
operation sequences → workstation
process of
sending sequence control
“Selection-Execution”.
commands → equipments
implementing 5. Implement steps and states are

11
expressed as binary integer by software parameters in control center
telemetry information. are need to be modified, like increasing
telecontrol timeout duration.
6. Operation sequences are
stored as files. Telecontrol The realization of cross bay combined
standard protocols are used for operation:
service transmission.
The combined operation for multiple
7. In the process of sequence bays is realized in local SCADA, but the
control, operations should be bay operation still need to be achieved
stopped when fault or alarm by bay level equipments. Because the
occurs. Manual PAUSE and actual operation of combined operation
STOP operation are supported, for multiple bays is completed on local,
and the operation can be the dedicated server for sequence
continued after pause. PAUSE control operation is not necessary to set
and STOP are implemented by in the system. That makes the system
the mode of direct control structure more clear and simple.
without selection, and
Centralized sequence control
CONTINUE is implemented by
scheme basing on local SCADA
“selection-operation”
and supporting remote operation
procedure.
In centralized scheme, storage and
8. Switching of protection stripe is
implementation of operation sequences
achieved by telecommand.
and judgment of operation logic and
9. Switching of setting values is state are achieved in station control level.
achieved by set command or The centralized achievement scheme is
telecommand. simple and less effect to alteration of
current equipments and operation
The information cannot be expressed by
management mode. The bay level
traditional telecontrol could expand
equipments only achieve normal
specific services in telecontrol protocols,
functions, like single point telecommand
like read of setting value, can use the
or single telesignalization. Here are the
expanded ASDU of IEC103 in
functions and features:
IEC101/104.
‹ Flexible sequence control state
In the initial development of sequence
configuration function;
control, in order to support
communication protocols of control ‹ Flexible operation sequences
center, sequence control and single configuration function;
point control adopt the same information
‹ Operation sequences preview
exchange process. The differences of
function;
the two control modes are shielded by
telecontrol machine, and station terminal ‹ Operation sequences simulation
software simulates the process of function;
sequence control to the same process of
‹ Operation sequences and interlock
single point control, so only some
logic on line validation function;

12
‹ Interlock logic before operation
coincides with single point
command interlock logic of bay
control equipments;

‹ Confirmation logic after operation


satisfies multiple conditions to
guarantee operation security;

‹ Tooltip can achieve small probability


complex situations.

The scheme also supports remote


Figure 1 relationship between sequence
operation sequence control. The relative
control operation module and programmed
functions of local SCADA sequence
service module 
control can be divided into two modules
to maintain the interface consistency of Overall, the sequence control schemes
local operation and remote operation. have following features:
The module of sequence control
‹ Station schemes support both
operation is in charge of the initiation of
distributed scheme and centralized
sequence control, and sequence control
scheme basing on local SCADA.
service module is responsible for
The centralized scheme can be
implementation of sequence control and
adopted when user requires to keep
judgment of state.
current operation mode but not to
Figure 1 shows the relationship between modify bay level equipment; and
sequence control operation module and also the distributed scheme can be
programmed service module in employed when users have high
distributed and centralized scheme. requirement of reliability and
efficiency.
With arrow 1 indicating local SCADA
operation in centralized scheme; ‹ Remote achievement scheme is
compatible with “black box scheme”
Arrow 2 indicating local SCADA
and extended scheme via protocols
operation in distributed scheme;
to satisfy the users’ requirement of
Arrow 3 indicating remote compatibility and reliability.
operation in centralized scheme;
‹ Station control layer protocols can
Arrow 4 indicating remote be both IEC61850 and CSC2000.
operation in distributed scheme;
Hence, the sequence control scheme of
V2 system is highly adaptable, and can
be applied in different voltage level
station for different requirements.

Interlock system

SCADA system and interlock system

13
adopt the same data and graphics to breakers or switches in the graphic
prevent false operation effectively. The system to change simulation state
interlock system integrated in the of operation sequences. The
SCADA system contains the following simulation state data of breakers
functions and features: and switches are stored in real-time
interlock database, so it does not
‹ Graphics and data are completely
affect other data in real-time
integrated. Interlock system and
database (like SCADA data).
graphic system shares the same
Additional, other progresses (alarm,
database and graphics, which avoid
write history) only deal with
reduplicate maintain.
real-time data, and all the functions
‹ On the basis of data of SCADA in other PC are not influenced.
system, the functions of operation
‹ Control interlock judgment function:
sequence can be completed by
left-click the equipment in the
modifying the data of operation
graphic system to enter telecontrol;
sequence database, like control with
firstly judge satisfaction of interlock
interlock judgment, generating
logic; if not, give the reason; if does,
operation sequences automatically,
enter the judgment of user authority
generating operation sequences
and continue the telecontrol.
manually, generating operation
sequences simulation, and ‹ Although SCADA system and
operation sequences interlock system mostly share the
implementation. same graphics, the latter has some
unique graphic elements, like
‹ Operation sequences database
ground wire. About this problem, the
includes templates of typical
concept of graphic layer is
operation sequences, equipment
introduced. In the normal SCADA
operation rules (can be generated
system, the unique graphic
via templates, and modified by
elements of interlock system are not
users), type information of
displayed, but only displayed in the
equipments and bays.
state of manual operation sequence
‹ The running interface of operation generation or simulation preview.
sequences is combined with graphic
‹ Complete electrical key and lock are
system of SCADA. Operator can
provided.
enter the state of manual operation
sequences generation from SCADA
graphic system: click the breakers
VQC subsystem
or switches in the graphic system to
VQC is the technique that regulating
join in current operation sequences,
transformer gears and switching reactive
and the sequences will be shown in
equipments to balance the control side
the table window of the screen.
bus voltage and high side power factor
Operators can also enter the state
(or reactive power) of main transformer
of simulation generation of
in the normal range. Capacitor bank can
operation sequence: click the
be applied to affect voltage and reactive

14
power. After enabling capacitor, reactive judgment of the operation mode can
power decreases, power factor be realized without complex setting.
increases, and the voltage rises. If
‹ Easy to set values. VQC setting
clearing capacitor, reactive power
values are composed by three types:
increases, power factor reduces, and
basic attributes of equipments,
voltage drops (In hypothesis of P and Q
which are set in graphic editor; VQC
flowed main transformer in same
basic parameters, which are set in
direction). The reactor has the reserve
setting interface; virtual points of
characteristic.
equipments are generated
The influence to power factor is automatically.
negligible by regulation of transformer
‹ Interlock function can be achieved
gears, so only effect of voltage is
flexibly. General interlock functions
considerable. Medium side voltage
exist in program, and other interlock
decreases when high side winding
functions user required can be
quantity increases, and rises when high
achieved by formula editing, without
side winding quantity reduces. (In the
modifying program.
following, it is default: medium side
voltage rises as gear tap getting higher) ‹ Simulation function. VQC can
simulate the whole control process
VQC subsystem has the following
after determination of the initial
features:
state.
‹ Single task, but share all source of
‹ Control mode: manual, automatic,
system.
and semi-automatic.
VQC subsystem is only in charge of
‹ Control strategy: standard
control of reactive power and
nine-zone, voltage prior
voltage. Functions of history
comprehensively control, double
statistics, graphics display and
nine-zone control with permission of
communication are dealt with by
high side voltage being restricted
other function modules of SCADA
condition.
system. The system sources are
utilized sufficiently. ‹ Nine-zone chart displays control
track. The displayed content can be
‹ No limited quantity for the controlled
configured as requirements.
equipments, only keep matched
with equipment database. ‹ Simulation equipment sending
message. The message can include
‹ Automatic topology. By means of
interlock state, action result, setting
shared topology database,
values, pre-action instruction.

15
Performance data
System performance index
Item Data
Integrated tolerance of analogue measurement ≤0.5%
Tolerance of grid frequency measurement ≤0.01 Hz
Maximal quantity of analogue input signal ≥50000, extendable
Maximal quantity of binary input ≥50000, extendable
Maximal quantity of binary output ≥1000, extendable
SOE ≤2ms
Operation accuracy rate 100%
Telecommand success rate ≥99.99%
Telemetry qualification rate ≥98%
Telesignalization accurate rate in fault ≥99%
System availability rate ≥99.8%
Workstation CPU average load rate
In normal condition (in any 30mins) ≤30%
In power system fault (in10s) ≤50%
Automation system network average load rate
In normal condition (in any 30mins) ≤30%
In power system fault (in 10s) ≤50%
Post disturbance review
Before the fault 5 minutes, extendable
After the fault 10 minutes, extendable

16
System response time
Item  Data 
Telemetry information response time (from BI ≤3s
terminals to substation layer)
Telemetry exceeding limit transmission time ≤3s
Telesignalization change response time ≤2s
Control command output time (from generation to ≤1s
output)
The response time of full size real-time data screen exported from HMI screen
85% of the screen ≤3s
The rest of the screen ≤5s
Update period of real-time data screen
Analogue ≤3s
Binary input ≤2s

 
 

17
System configuration scheme
Two typical configuration schemes can equipments and network communication
be mainly adopted in substation medium. The centralized system
automation system: centralized system scheme is usually employed in low
scheme and distributed system scheme. voltage level substations and the
The basic differences between the two distributed one is normally applied in
schemes are the placements of the high voltage level substations.

18
Centralized configuration substation automation
system scheme
The scheme of centralized configuration substation, single gateway can be
scheme is shown in Figure 2 below, adopted and switch of double dispatch
which is applicable for substation channels can be realized by software.
automation system in 110kV level and
Bay level equipments include bay
below or in 220kV level centralized
control equipments, protection
arranged substation. In this scheme, all
equipments, bay control and protection
the relative equipments are placed in
integration equipments. All of the
one room, and double Ethernet network
equipments can be connected to station
structure is used in station control layer.
control layer network via Ethernet.
Single network is also suitable for the
system in 110kV and below voltage The equipments from third parties can
levels. be connected to station control layer via
protocol gateways and the equipments
Station control layer contains two
protocols can also be converted into
operation workstations, protection
station control layer protocols. These
engineer station, VQC workstation,
protection equipments generally adopt
interlock system workstation. SCADA
IEC60870-5-103 protocols, and other
server can be integrated in the two
intelligent equipments use Modbus or
operation stations.
self-defined protocols to communicate
Gateway can be configured redundantly. via serial ports or Ethernet. The
The double dispatching channels can be quantities of protocol gateways can be
switched by channel switch equipment. configured by the connected equipments.
For 110kV voltage level and below

19
Figure 2 the scheme of centralized configuration substation automation system 

20
Distributed configuration substation automation
system scheme
The Figure 3 is the scheme of distribute operation station. Basically, different
configuration substation automation workstations are in charge of different
system. This network structure is functions.
applicable for the 330kV and above
Gateway is adopted redundant
voltage level substation system and
configuration. The double dispatching
distributed arranged 220kV substation
channels can be switched by channel
automation system. In the scheme,
switch equipment. Bay level equipments
station control layer equipments are
include bay control equipments,
placed in main control room; most bay
protection equipments, bay control and
level equipments are laid in secondary
protection integration equipments. All of
equipments bay room; only common
the equipments are connected to station
secondary equipments are set in main
control layer network via double
control room. Bay rooms are divided by
Ethernet. Because secondary
voltage levels, or bays, and bay-related
equipments, like protection and bay
secondary equipments are deposited in
control equipments are distributed in
bay rooms. Station control layer adopts
different bay rooms, the equipments
double Ethernet network. Bay rooms
could firstly connected to switches in bay
adopt fiber optical Ethernet for
room and then to switches of main
communication.
control room via optical fiber. The IEDs
Station control layer contains two from other manufacturers are converted
SCADA servers, two operation into station control layer protocol firstly
workstations, maintenance engineer and next connected to the bay room
workstation, protection engineer station, network.
VQC main station, interlock system

21
Figure 3 the scheme of distribute configuration substation automation system

22
Equipment

23
CSC-1320 Gateway
Product Guide

24
Overview

CSC-1320 gateways are communication equipment of substation automation


products based upon 32-bit micro- system, fitting for incoming and outgoing
processor chips. With advanced information in monitor system,
embedded operating system and flexible telecontrol system and sub-station
module design, CSC-1320 is mainly equipment of the fault information
used in the station layer communication system in different voltage levels.

25
Features
‹ CSC-1320 is equipped with rear required to be installed in the most
module plug-in structure. Single left slot and the most right slot
equipment supports 12 modules respectively in back sight), with
maximally. In other words, except enough support provided by the
the necessary CPU module and system.
power module, ten more modules
‹ The modules communicate through
can be configured freely. The widths
internal network, which is mainly
of the 10 modules are the same,
based upon 100M Ethernet, with
which actually realizes flexible
CAN-bus for assistance.
configuration. Every module can be
assembled in any slot (for ‹ The internal Ethernet can be
convenient maintenance, CPU connected by switch, and supports
module and power module are cascade to other equipments.

26
Functions
The equipment can be used as the ‹ Communicate with workstations via
communication station in substation CSC2000 protocol,
control layer. The function including: IEC60870-5-103 protocol, Modbus
protocol or expended IEC103
‹ Communicate with protection,
protocol;
measurement, control and record
equipments via different ‹ CSC-1320 is equipped with the high
communication protocols; capacity to save protection fault
information and record data;
‹ Communicate with control levels via
dispatching protocols; ‹ CSC-1320 can save 8×24 hour
telemeter data.

27
Software
The software supports application and ‹ Support partial fault information
hardware driver level separately, as sub-station protocol
programming as CPU module, Ethernet
‹ Support single and dual network
module, serial port module and field bus
system configuration
module.
‹ Support embedded sub-station with
The software supports leveled module
background mode
structure, for making a strong platform
with generality. Following functions are ‹ Support sequence control function
including: from dispatching terminal

‹ Support arbitrary protocol to access As station control layer equipment,


information CSC-1320 can be used as telecontrol
equipment, protection and fault
‹ Support arbitrary protocol to outgo
information management equipment
information
(sub-station), and substation
‹ Support tele-control telecontrol communication equipment (telecontrol+
protocol and incoming protocol sub-station).

28
Hardware
Human-machine Interface (HMI) register setting, also LEDs that is used
to indicating alarm and normal status.
Front panel of CSC-1320 is equipped
with user-friendly LCD and Front panel details are shown in Figure
navigation-keys which can help to 4.

 
Figure 4 Front panel of CSC-1320 gateway

1 Liquid crystal display (LCD) 5 Quit key

2 LEDs 6 Set key

3 Navigation keys 7 RS-232 communication serial port

4 Reset key

29
Serial communication module
CPU module
The serial communication module uses
The CPU module uses 32-bit CPU, with
32-bit CPU of PowerPC series, with
strong communication capability. The
strong communication capability. Six
module uses a FLASH of 8M or 16M to
standard RS232/RS485 serial ports are
save program and configuration. The
equipped on the module.
DOC electronic disk slot is configured on
the CPU module, so it is possible to Time synchronization module
select electronic disk of different
The time synchronization module
capacities to be storage medium for
supports 16-bit CPU.
different requirements. Module models
include CPU-D (DOC electrical disk), In the module, there are several modes
CPU-C (CF card), and CPU-N (CF can be selected by jumper:
card).
Serial port+ pulse time synchronization;
Ethernet module
IRIG-B time synchronization.
Ethernet module has the same
Cascading module
hardware configuration with the CPU
module, but configuration is more The cascading module enables the
flexible as expanded communication cascade of two equipments. There are
module. Generally, DOC electronic disk two electrical Ethernet terminals and two
is not applied on Ethernet module. Both optical Ethernet terminals on the module.
10Mb/s and 100Mb/s electrical Ethernet Equipment can be connected to four
and optical Ethernet are optional for others at most.
different requirements.
Power supply module
Up to 2 Electrical interfaces can be
There are three kinds of power module.
configured on the Ethernet-C or
One is 220V AC/DC, one is 110V/125V
Ethernet-D module.
DC, and another one is 48VDC, all being
Up to 4 Electrical interfaces can be provided with power loss signal and
configured on the Ethernet-N module. redundancy function.

Up to 2 Optical interfaces can be


configured on the Ethernet-F module.

30
Layout and Dimension
The equipment uses IEC60297-3 and lockable plugging functional module.
standard aluminum alloy case whose The dimensions of equipment and sizes
length is 4U, width is 19 inches (or 19/2 of the installation openings refer to
inches), and adopts integrated panel Figure 5 to Figure 6:

Figure 5 4U, 19” case with rear cover 

Table 1 dimension of the equipment

Case size A B C D E

4U,1/1x19’’ 177 482.6 265 320 437.2

Unit: mm

31
Figure 6 Cut-out on the control Panel

Table 2 dimension of the cutout of mounting

A B C D E

450 465 101.6 178 4-φ6.5

Unit: mm

32
Equipment Terminals

Terminals of CPU module


The serial ports are on the top of CPU-D Terminal definition refers to below:
module, and at the bottom are Ethernet
Table 3 CPU module serial port terminals
ports. The serial terminal is green 6-line
definition
phoenix terminal used for one serial port
RS232 and RS485 mode. Number 1 2 3
Mark TXD RXD GND
Number 4 5 6
Mark NC 485A 485B

Ethernet port consists of two electrical


Ethernet RJ45 terminals. The upper one
is Ethernet 1 and the lower is Ethernet 2.

NOTE 1: For CPU-C and CPU-N, the


serial port is DB9;

NOTE 2: For CPU-N, Ethernet terminal


is 4 RJ45 terminals. Ethernet 1 is on the
top, and then are Ethernet 2, 3, 4.
Figure 7 Terminals of CPU module

33
Terminals of Ethernet module
There are two kinds of Ethernet module: The external terminal of electrical
electrical Ethernet module and optical Ethernet module refers to the table
Ethernet module. below:

Table 4 Ethernet module serial port terminals


definition

Number 1 2 3
Mark TXD RXD GND
Number 4 5 6
Mark NC 485A 485B

In optical Ethernet module, SC 1310nm


multimode fiber interfaces are equipped.

Figure 8 Terminals of Ethernet module

34
Terminals of serial communication module
The serial communication module Terminal definition refers to below:
terminal is green 20-line phoenix
Table 5 serial terminals definition in serial
terminal used for six serial port RS232
communication module
and RS485 mode. Terminals of the
module are arranged as the following
Terminal Definition Terminal Definition
picture.
1 A1 11 B4
2 B1 12 GND
3 GND 13 A5
4 A2 14 B5
5 B2 15 GND
6 GND 16 A6
7 A3 17 B6
8 B3 18 GND
9 GND 19 Null
10 A4 20 Null

Meanwhile, there is a small table on the


block board at the top of the module
Figure 9 Terminals of serial communication
terminal, describing the corresponding
module
relationship of AX and BX in RS232 and
RS485 mode:

Table 6 Working mode definition of serial port


module

A B
RS232 RXD TXD
RS485 A B

35
Terminals of Time synchronization module
Time synchronization module terminal is and IN2 work as pulse inputs, and TXD,
green 6-line phoenix terminal, RXD, GND work as serial ports
supporting GPS pulse time connecting terminals. In RS232 mode:
synchronization and IRIG-B time TXD works as sending end, connecting
synchronization. to the receiving line of the counter
terminal; RXD works as receiving end,
connecting to the sending line of the
counter terminal; GND is ground. In
RS485 mode: TXD connects to 485+;
RXD connects to 485-.

In IRIG-B time synchronization, IN1 and


IN2 terminals work as inputs. No matter
IRIG-B pulse or IRIG-B (DC) time
synchronization, IN1 is the positive
terminal of input, IN2 is the negative
terminal of input, and GND terminal is
shielded grounding.

Figure 10 terminals of time synchronization


module

In GPS pulse time synchronization, IN1

Terminal definition refers to below:

Table 7 Time synchronization module terminals definition

Number 1 2 3 4 5 6
Mark IN1 IN2 TXD RXD GND NC
IRIG-B (DC) time synchronization DC + DC - GND
GPS time synchronization RS232 serial port GPS+ GPS- TXD RXD GND
GPS time synchronization RS485 serial port GPS+ GPS- 485+ 485- GND

36
Terminals of Cascading module
Cascade module includes of two Two cascading modules install in any
electrical Ethernet RJ45 terminals and slot of the two equipments respectively,
two optical Ethernet SC optic fiber and the two modules can be connected
terminals through cable for electrical Ethernet or
optic fiber for optical Ethernet.
Cascading modules are used in pairs.

37
Terminals of Power supply module
There are three kinds of power supply alert node output. It is a normally closed
modules. One supports 220V AC/DC, node, closing when power is losing.
one supports 110V/125V DC, and the Terminal definition refers to below:
third one supports 48V DC. The terminal
Table 8 power supply module terminals
is green 8-line phoenix terminal.
definition

Number Definition
220V 110V 48V
1 220V+ 110V+ 48+
2 Null Null Null
3 220V- 110V- 48V-
4 Null Null Null
5 GND GND GND
6 Null Null Null
7 Power Power Power
loss loss loss
8 Power Power Power
Figure 11 Terminals of power supply module
loss loss loss

When AC power source is used in 220V


power module, 220V+ and 220V- can be
connected to any of the two lines of AC
source. Terminal 7 and 8 are power loss

38
System architecture
CSC-1320 is a modular device, 12
modules can be plugging in 12 slots of
device, so CSC-1320 provides variety of
applications for user such as:

‹ Gateway
‹ Protocol converter
‹ Protocol converter and gateway

Gateway configuration
CSC-1320 supports IEC-60870-5-101,
IEC-60870-5-104 and DNP3 for
connecting to dispatching center and
IEC- 61850 and CSC-2000 for sending
and receiving IEDs information.
CSC-1320 is not dependent on the Figure 12 IEC-60780-5-101 communication
servers and all devices can be sent architecture
information to the gateway directly.
CSC-1320 is connected to modem with
CSC-1320 can be connected to the serial card which consist of six channels.
network through two Ethernet ports. CSC-1320 provides Baud-Rate
Architecture of CSC-1320 for 300-38400.
IEC-60870-5-101 is shown in Figure 12. The modules configuration is shown in
Figure 13.

39
Figure 13 IEC60870-50-101 Module
Configuration

CSC-1320 can be configured as a


gateway with IEC-60870-5-104 which is Figure 14 IEC-60780-5-104 communication

based on TCP/IP. architecture

IEDs can be defined in gateway with Ethernet module supports up to 50 IEDs


Ethernet module; each Ethernet module through two redundant Ethernet ports.
supports up to 50 IEDs through two The modules configuration is shown in
redundant Ethernet ports. Architecture Figure 15.
of CSC-1320 for IEC-60870-5-104 is
Switch
shown in Figure 14.
IEC-60870-5-104

1 2 3 4 9 12
Time
Master Ethernet Ethernet Power
Module Module
Synch.
Module
... Ethernet
... Module
Module Module

CSC-1320

Network 1

Network 2

IED-1 IED-300

Figure 15 IEC60870-50-104 Module


Configuration 

CSC-1320 can send and receive


information between several dispatching
center at the same time with different
protocols, so it can be configured as a

40
gateway with IEC-60870-5-101 and protocol converter by using serial
IEC60870-5-104 at the same time. communication module.

Architecture of CSC-1320 for CSC-1320 supports Baud-Rate


IEC-60870-5-101 and IEC-60870-5-104 300-38400.
is shown in Figure 16. It can be used for IEC 60870-5-103 and
MODBUS protocol. Max 9 modules can
be plugged in CSC-1320. Each serial
module consists of six channels.

Six or seven device with MODBUS and


IEC-60870-5-103 can be chained
together and connect to one channel.

It is not recommended to connect more


than 20 devices in one module. The
overall device quantity connected in one
CSC-1320 should be less than 120.

Architecture of CSC-1320 as gateway is


shown in Figure 18.

Figure 16 IEC-60780-5-101/104
communication architecture

The modules configuration is shown in


Figure 17.

Figure 18 Protocol converter communication 

Module configuration is shown in Figure


19.

Figure 17 IEC60870-50-101/104 Module


Configuration

Protocol converter configuration

CSC-1320 can be configured as a

41
Redundant configuration

CSC-1320 provides redundant


configuration for IEC 60870-5-101, IEC
60870-5-104 and DNP3.

There is same configuration on


redundant CSC-1320.
Remote-SCADA sends and receives
information through one gateway, if the
gateway fails remote SCADA switches
on the second gateway.
Architecture of gateway redundancy is
shown in Figure 21.

Figure 19 Protocol converter Module


Configuration

Protocol converter and Gateway


configuration

CSC-1320 can be configured as a


protocol converter and Gateway at the
same time.

Figure 21 Redundancy communication

Time synchronization

CSC-1320 provides IRIG-B protocol


which is connected to the GPS through
twisted pair cable.
Figure 20 Protocol converter and Gateway
Architecture of time synchronization is
communication
shown in Figure 22.
All channels include serial and Ethernet
can be monitor and CSC-1320 can send
a software alarm to Local SCADA if each
channel fails.

42
Figure 22 Time synchronization

CSC-1320 can receive the time from


Remote-SCADA if the IRIG-B link fails.

The clock time which is received from


remote SCADA, can be received by
computers and IEDs through SNTP
(simple Network Time Protocol). If the
GPS fails, all equipments can be
synchronized.

Only one Remote-SCADA can be


defined as a main clock time.

43
Technical data
Basic data

Frequency

Item Data
System rated frequency 50 Hz or 60Hz

Rated auxiliary voltage

Item Data
DC voltage 220V
110V
48V
AC voltage 220V/50Hz
Permissible tolerance ±20%
Power consumption
In normal condition <50W.

Response time

Item Data
Telesignalization response time ≤ 1s
Telemeter response time ≤ 3s

Binary input

Item Data
Input voltage range 24 V DC
Response time/dropout time Software provides de-bounce time
Power consumption, energized ≤ 2mA
Independent of operating voltage

44
Binary output

Item Data
Max. system voltage 250V DC/AC
Current carrying capacity 3 A continuous
Breaking capacity 30W, for DC at I<500 mA, L/R < (5+/-0.75) ms

45
Type tests

Insulation test

Item Data
Standards IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Voltage test (100 % test)
All circuits besides auxiliary voltage and 2KV,50Hz,1min
RS485/RS232 and time synchronization IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Auxiliary voltage 3.5 kV DC
IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Communication ports and time synchronization 500V,50Hz,1min
terminals IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Impulse voltage test
all circuits, except communication ports and time 5kV (Ui≥63V) /1kV (Ui<63V)
synchronization IEC 60255-5:2000 class III
GB/T 15145-2001
DL/T 478-2001
Insulation resistance
Insulation resistance >100 MΩ at 500 VDC
IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001

Electromagnetic compatibility tests

Item Data
Standards GB/T 14598.9-2002
identify IEC 60255-22-3:2000, for radiated
electromagnetic field disturbance test
GB/T 14598.10-2007
identify IEC 60255-22-4:2002, for electrical fast

46
transient/burst immunity test
GB/T 14598.13-2008
Modify from IEC 60255-22-1:2007, for 1MHz
burst immunity test
GB/T 14598.14-1998
identify IEC 60255-22-2:1996, for electrostatic
discharge test
GB/T 14598.17-2005
Identify with IEC 60255-22-6:2002, for
Conducted electromagnetic field disturbance
tests
GB/T 14598.18-2007
Identify with IEC 60255-22-5:2002, for surge
immunity test
GB/T 14598.19-2007
Identify with IEC 60255-22-7:2003, for power
frequency immunity test
GB/T 14598.20-2007
Identify with IEC 60255-26:2004, for
electromagnetic compatibility requirements
High-frequency burst disturbance test 2.5 kV (peak value); 1 MHz
test duration 2 s
IEC 60255-22-1, class III
and VDE 0435 Part 303, class III
Electrostatic discharge 8 kV contact discharge
15 kV air gap discharge
both polarities; 150 pF; Ri = 330 Ω
IEC 60255-22-2; class IV
and EN 61000-4-2; class IV
Radio-frequency electromagnetic field disturbance 10V/m, 80 to 1000 MHz
non-modulated IEC 60255-22-3, class III
Radio-frequency electromagnetic field disturbance 10 V/m, 80MHz to 2.7GHz
amplitude-modulated 80%AM; 1 kHz
IEC 61000-4-3, class III
Radio-frequency electromagnetic field disturbance 10 V/m, 900 MHz; repetition rate 200 Hz, on
pulse-modulated duration 50 %
IEC 61000-4-3/ENV 50204, class III
Fast transient disturbance 4KV
IEC 60255-22-4 and IEC 61000-4-4, class IV
High-energy surge voltages (Surge) 2KV
Auxiliary voltage IEC 61000-4-5, class III
radio-frequency line-conducted disturbance, 10 V; 150 kHz to 80 MHz
amplitude-modulated AM 80 %; 1 kHz
IEC 61000-4-6, class III

47
Power frequency magnetic field test 30 A/m; 50 Hz, continuous
300 A/m; 50 Hz, 3 s
0.5 mT, 50 Hz
IEC 61000-4-8, class IV
IEC 60255-6
Oscillatory surge withstand capability test 2.5kV, 1 MHz
ANSI/IEEE C37.90.1
Fast transient surge withstand capability test 4KV
5kHz
ANSI/IEEE C37.90.1
Radiated electromagnetic field disturbance 10 V/m; 25 to 1000 MHz
amplitude and pulse-modulated
ANSI/IEEE C37.90.2
Damped wave 2.5 kV (peak value, polarity alternating)
100 kHz, 1 MHz, 10 and 50 MHz, Ri = 200 Ω
IEC 60694 / IEC 61000-4-12
Radiated emission 30MHz to 1GHz ( IT device may up to 5 GHz)
CISPR11, class A
EN61000-6-4:2005
Conducted emission 0.15MHz to 80MHz
CISPR11, class A
EN61000-6-4:2005

Mechanical tests

Item Data
During operation
Standards IEC 60255-21-1:1988
IEC 60255-21-2
Vibration Sinusoidal
10 to 50 Hz; +/- 0.035 mm amplitude
50 to 150 Hz
IEC 60255-21-1, class 2
IEC 60068-2-6
Shock Semi-sinusoidal
Acceleration 5 g, duration 11 ms; 6 shocks in both
directions of 3 axes
IEC 60255-21-2, class 1
IEC 60068-2-27
During transportation
Standards IEC 60255-21-2
Vibration Sinusoidal

48
5 to 8 Hz: ± 7.5 mm amplitude
8 to 150 Hz; 2 g acceleration
frequency sweep 1 octave/min
20 cycles in 3 perpendicular axes
IEC 60255-21-1, class 2
IEC 60068-2-6
Shock Semi-sinusoidal
Acceleration 15 g, duration 11 ms
6 shocks in both directions of 3 axes
IEC 60255-21-2, Class 1
IEC 60068-2-27
Continuous shock Semi-sinusoidal
Acceleration 10 g, duration 16 ms
2000 shocks in both directions
of 3 axes
IEC 60255-21-2, class 1
IEC 60068-2-29

Environmental tests

Item Data
Temperatures
Type-tested , test Bd, for 16 h -25 °C to +70 °C
IEC 60068-2-1
IEC 60068-2-2
Recommended permanent operating temperature -10 °C to +55°C
IEC 60255-6
(Legibility of display may be impaired above
+55 °C /+131 °F)
Storage and transport temperature limit -25°C~+70°C
Humidity
Permissible humidity 95 % of relative humidity

Equipment design

Item Data
Case size 4U×19inch
4U×19/2inch
Dimensions See dimension section
Weight ≤ 10kg
Protection level IP20 class I

49
EN 60529
IEC 60529

CE certificate

Item Data
EN 61000-6-2 and EN61000-6-4 (EMC Council
EMC Directive
Directive 2004/108/EC)
Low voltage directive EN 60255-27 (Low-voltage directive 2006/95 EC)

50
Station communication ports

Front communication port

Item Data
Number 1
Connection Isolated, RS232; front panel
9-pin subminiature connector
Communication speed 9600 baud
Max. length of communication cable 15 m

RS232/RS485 communication port (for each module)

Item Data
Number 6
Connection 2-wire connector
Rear port in communication module
Max. length of communication cable 1.0 km
IEC 60870-5-103 protocol
Communication speed Factory setting 9600 baud
Min. 1200 baud, Max. 19200 baud

Ethernet communication port (for each module)

Item Data
Electrical Ethernet communication port
Number 0~2
(0 ~ 4)
Connection RJ45 connector
Rear port in Ethernet-C or Ethernet-D module
(Rear port in Ethernet-N module)
Max. length of communication cable 100m
IEC 61850 protocol
Communication speed 100 Mbit/s
IEC 60870-5-103 protocol
Communication speed 100 Mbit/s
Optical Ethernet communication port
Number 0~2

51
Connection SC connector
Rear port in Ethernet-F module
Optical cable type Multi-mode
Max. length of communication cable 2.0km
IEC 61850 protocol
Communication speed 100 Mbit/s
IEC 60870-5-103 protocol
Communication speed 100 Mbit/s

Time synchronization

Item Data
Mode IRIG-B mode
Connection Rear port in synchronization module
Voltage levels differential input

52
CF)
Gateway
Gateway

110V DC
CSC-132

19 inches
Bay Level

CF-1 Type
(128M CF)
Station Level

220V DC/AC
CF-2 Type (2G
CF-4 Type (2G)
CF-3 Type (8G)
*

2
1
Application Type
/
Ordering
M

CPU Module
*

Quantity
*

8
4
Model
E

Ethernet-T Module
*

Quantity
*

5
Model
F

Ethernet-FX Module
*

Quantity

53
3
Model
S

Serial Communication
module
*

Quantity
G

Time Synchronization
Module
*

Quantity
C

Cascading Module
*

Quantity
P

Power Module
*

2
1

Voltage
X

Case
*

Code
R

Function Version
*

code
Station Level 1
Gateway
Bay Level 2
Gateway
Station Level 4
Gate way + Bay
Level Gateway

 
 

54
CSI-200E Bay Control IED
Product Guide

55
Overview

CSI-200E series bay control IEDs are and above. The bay units includes main
usually applied in the substation transformer bay (high, medium, and low
automation system, and also may be voltage), 110kV outgoing line bay,
used as simple measurement and 220kV outgoing line bay, 500kV
control equipments. outgoing line bay, bus connector bay,
transfer bus bay, kiosk bay, the whole
The equipment is bay-oriented designed
substation bay (the common part in one
and mainly used in the system of 110kV
substation) and so on.

56
Features
‹ Flexible configuration: emergency.

Flexible configuration is a special ‹ Bay management:


feature of the equipment to fit
In the station Ethernet network,
different requirements of users. All
CSI-200E can connect other Sifang
the modules in equipment are
IEDs in the bay, to receive the
modular designed, connecting
telecontrol command from and
through internal bus, and can be
upload information to workstation.
plugged-out and installed simply
according to the requirements in ‹ Complete event record:
practical.
Large flash-ROM chip is equipped
The software function can also be to record relative operation, fault,
configured flexibly. User can SOE and alarm, and data cannot be
operate “CSI-200E Manager” on PC lost even power off. That is
and download the PLC logic convenience for fault analysis.
diagram basing on ladder diagram
‹ Automatic detection:
to the equipment. Bay interlock,
synchronization function, on-load All the modules are detected by
voltage regulation and other special machines automatically in
self-defined logic function can also factory test, without any artificial
be achieved. intervention for high reliability.

‹ Powerful communication function: ‹ Self-diagnose:

The equipment provides The equipment provides full


electrical/optical Ethernet and self-diagnose function. Once any
LonWorks. The master module can module running abnormally, the
complete communication according equipment informs operators and
to selection of network module. also indicates the fault position.
(See details in Hardware section) CSI-200E has the capability to
monitor actions of all the binary
CSI-200E also provides standard
outputs.
RS485 ports and can be connected
to substation automation system of ‹ Non-adjustment in locale:
other manufactures.
CSI-200E does not contain any
‹ Local operation function: adjustable potentiometer. For
reliability, all the modules have been
Emergency operation buttons are
checked in delivery test, so no more
designed on the control panel.
adjustment is needed to avoid
Authorized user can handle the
influence from human factors.
breakers and switches in single line
diagram on the LCD directly in ‹ Structure character:

57
Internal modules are designed to panel directly through 32-pin
install in rear board, which brings terminal of the rear without beam
convenience for running test and terminals. The middle links are
fault maintenance decreased to improve the reliability.

High and low voltage terminals are ‹ Easy to expand and upgrade in the
located separately. The equipment general hardware platform.
can be connected to the operation

58
Functions
‹ Display of single line diagram of the ‹ Sampling of the AC variables:
bay:
The equipment has the capability to
Big LCD with Chinese/English HMI sample and submit three-phase
is adopted to display the single line voltage RMS, three-phase current
diagram of the bay in CSI-200E. RMS, 3U0, 3I0, active power,
User can run “CSI-200E Manager” reactive power, frequency as well as
software on PC and select second to thirteen harmonic in the
necessary components in bay according to different voltage
component library (breakers, levels.
switches, reactors, capacitors, line)
‹ Sampling of the DC variables and
to draw the electrical connection
temperature:
diagram. The software can convert
the diagram to configuration code, Sorts of DC variables can be
and transfer the code to the sampled, like DC220V, DC110V,
equipment via RS-232 serial port on DC24V, DC0V ~ 5V, DC4mA ~
the panel. Then the single line 20mA. The equipment can also
diagram can be displayed in the sample and submit the temperature
LCD. value of primary transformer.

‹ Telesignalization: ‹ Acquisition of the power energy:

Each BI terminal can be defined as The IED can also achieve the
many types of input, like state input acquisition of pulse power energy
(important signal can be set as and Integral power energy.
double point input), alarm input,
‹ On-load voltage regulation
SOE, pulse counter input,
transformer tap input (BCD or HEX) The tap gear (BCD code or HEX
and so on. code) of primary transform can be
collected and submitted. The
‹ Telecommand:
equipment can also respond the
The equipment accepts remote telecommand (rise, drop, or stop)
control commands from workstation from the workstation to adjust the
to operate breakers and the position of transformer tap;
switches, reset transceivers and the
‹ Synchronization function
operating instruments. A row of
emergency buttons also are built on Synchro-close can be achieved in
the front panel, which can be used different modes for various needs:
to operate the breakers and Synchro-check, Energizing check or
switches on the single line diagram quasi-synchronization.
directly for the jurisdiction users in
‹ Fault line detection for ungrounded
special conditions.

59
system transmit interrogation command
from fault line detection station,
The equipment may send 3U0
which has the ability to judge the
exceeding limit alarm message to
fault phase.
fault line detection station, and

60
Software
CSI200EManage is a user-friendly ‹ The single line diagram can be
software tools for operator to draw the drawn in the software and
single line diagram, set the parameters, downloaded to the CSI-200E in
and establish interlock PLC ladder LCD.
diagrams.
‹ Following different equipments of
‹ Three function modules, single line bay units, all the terminals of
diagram drawing, PLC editor and hardware modules can be
equipment configuration, are configured.
included in the software. Each of
‹ Graphical visualization substitutes
the function modules has a window
program compiling. In PLC editor,
view on the main interface of
ladder diagram can be achieved to
software.
reflect the interlock logic system,
which can also be downloaded to
equipment to implement the
corresponding logic functions.

‹ In the main interface, information


bar displays the information of
downloading, and message window
can show the messages serial port
received and sent.

61
Hardware
Human-machine interface (HMI) the panel, 5 LED lights indicate the
states of the equipment currently, and 6
HMI is the human-machine interface of
shortcut function buttons are convenient
the equipment. Current measured
for user to operate locally. The front
values, enabled straps and single line
figure is shown in Figure 23 below:
diagram can be display on the LCD. On
1
5
4

CSI-200E

6 7
3 8  
Figure 23 Front panel of the IED

1 Liquid crystal display (LCD) 5 Reset key

2 LEDs 6 Quit key

3 Shortcut function key 7 Set key

4 Navigation keys 8 RS232 communication port

62
Master module (COM module) in 4 groups with separated common
terminals
This module is an essential one for the
equipment. It connects HMI module via Extended BI module: 24 channels of
serial port, submits the data to HMI for BI in 4 groups with separated
displaying, and receives equipment common terminals
configuration information and PLC logic
Functions of BI module consist of: digital
from PC.
input (signal point information or double
AC input module (AI module) point information), BCD code or binary
input, impulse input and so on. BI
Hardware configuration: according to the
module can be divided into two kinds:
different configuration and functions,
one module with CPU named basic BI
CSI-200E can be divided into A, B, C,
module; the other one without CPU is
and E four types:
extended BI module.
A: 8 channels voltage: U1a, U1b, U1c,
Binary output module (BO
U2a, U2b, U2c, U3, U4; 4 channels
module)
current: I1, I2, I3, I4;
Hardware configuration:
B: 6 channels voltage: U1a, U1b, U1c,
U2a, U2b, U2c, U3, U4; 6 channels Internal bus
current: I1, I2, I3, I4, I5, I6;
14 pairs of idle contacts
C: 4 channels voltage: U1a, U1b, U1c,
The BO module can control the switches,
U4; 3 channels current: I1, I2, I3;
breakers, on-load voltage regulation
E: 8 channels voltage: U1a, U1b, U1c, (rise, drop and stop) devices. The width
U2a, U2b, U2c, U3, U4; of the output impulse of each channel
can be configured through PLC (only for
A, B, C can measure the power P, Q,
pulse output).
cosΦ, and f; E can measure: f.
Binary output module (BOB
AI module can be configured in different
module)
measuring methods. The AC module
with 8U4I can measure 1 channel power Hardware configuration:
in “three meters mode” connection and 2
Internal bus
channels power in “two meters mode”
connection. The AC module with 6U6I 10 pairs of double coil double
can measure 2 channels power. position relay contacts

Three AI modules can be configured The double coil double position relay is
maximally. applied in BOB module. Collection
circuit is designed to monitor the state of
Binary input module (BI module)
relay contacts, so BOB module is
Hardware configuration: suitable for normally-closed condition,
for instance the earth switch interlock.
Internal bus
10 pairs of contacts can be used in
Basic BI module: 24 channels of BI telecontrol and synchronization like BO

63
module, if not used in long term input. equipments. Two DT modules can be
placed in one CSI-200E maximally.
Binary output module (BOC
Attributes of collection data from
module)
sampling channels of each module can
Hardware configuration: be set in management software.

Internal bus Power supply module


14 pairs of idle contacts This module is a DC inversion power
module. After filtering from the
BOC module has the same hardware
anti-interference filer circuit, DC 220V or
structure of the BO module. Except the
110V can be converted to DC voltage 5V,
all the functions of BO module, BOC
±12V, 24V(1), and 24V(2), according to
module also has the SOE submission
the inversion principle. All the four
function of BO contact status and
voltages required for equipment, do not
contact changes.
have common ground end, but floating
DC and temperature module (DT earthing without connecting the
module) equipment chassis.

Hardware configuration: The usage of 4 output voltage:

Internal bus; 5V is used for the power supply of


CPUs;
5 channels sampling circuit for
temperature or DC variables. ±12V is used for analog system
power supply;
The measured DC variables or
temperature resistor are connected to 24V is applied to drive BO relay.
the converter, (output values are 0~5V
c16, a16 in the power module are
voltage or 4~20mA current), then to the
idle contacts.
5 channel DC inputs, which have the
common cathode in CSI-200E series

64
Layout and Dimension
The equipment adopts the structure of each other and the functions of
front plug-in. The modules are equipment can be configured easily. The
connected by back-bus block and structure of function module is shown in
communicate through internal bus. Thus Figure 24:
these modules can change location with

Figure 24 structure diagram of the module in CSI-200E

CSI-200E has two sizes: 19 inches shown in the figures are not fixed.
width/4U height and 19/2 inches Modules with same width can be
width/4U height. Width of the power interchanged theoretically.
module is 30.64mm. Master module
The dimensions of the two
width is 40.64mm. Width of AC
CSI-200E cases are shown in
module is 60.96mm. All of other
Figure 25 to Figure 28, and the
modules width is 20.32mm. Thus
diagram of installation cutout on the
these modules can change the slot
panel is also illustrated below:
location flexibly. Module positions

65
Figure 25 4U, 19” case with rear cover

Table 9 Dimension of the IED case

Case size A B C D E

4U,1/1x19’’ 177 482.6 265 320 437.2

Unit: mm

Figure 26 Cut-out on the Panel

Table 10 Dimension of the cutout on the panel

A B C D E

450 465 101.6 178 4-φ6.5

Unit: mm

66
Figure 27 19/2’’ case with rear cover

Table 11 Dimension of the IED

Case size A B C D E F

4U,1/2x19’ 177 231 193.8 220.8 149 193.5

Unit: mm

Figure 28 Cutout on the panel

Table 12 Dimension of the cutout on the panel

A B C D E

199.5 213.5 101.6 156 6-φ6.5

Unit: mm

67
Equipment Terminals
Terminals of Master module
Master module employs 32-bit CPU with
high speed and powerful functions. The
hardware includes:

1. Data record large memory size


RAM and FLASH

2. External interface: 10/100M double


electrical Ethernet (RJ45 terminal);
100M double optical Ethernet (SC
terminal, with wavelength 1300nm,
multimode fiber); double LonWorks

3. Timing mode: differential IRIG-B and


pulse time synchronization interface.

Figure 29 Terminals arrangement of


communication module

68
Terminals of AC Input module
Two kinds of AC input module, 8U4I and Table 13 Description of terminals of AI
6U6I are shown in following diagram. modules
The description of the terminals refers to
Terminal Analogue input Remark
the Table 13.
8U4I 6U6I
a01 I1 I1 Star point
b01 I1’ I1 ’
a02 I2 I2 Star point
b02 I2’ I2 ’
a03 I3 I3 Star point
b03 I3’ I3 ’
a04 I4 I4 Star point
b04 I4’ I4 ’
a05 U4 I5 Star point
b05 U4n I5 ’
a06 U3 I6 Star point
b06 U3n I6 ’
a07 U2b U2b
b07 U2c U2c
a08 U2a U2a
b08 U2n U2n
a09 U1b U1b
b09 U1c U1c
a10 U1a U1a
b10 U1n U1n
a11 Ground Ground
b11 Ground Ground

Figure 30 Terminals arrangement of AI


modules

69
Terminals of BI modules
BI modules include BI basic module and Table 14 Description of terminals of BI basic
BI extended module. Each module module
includes 24 channel inputs in 4 groups.
Terminal Definition remark
c02 BI1 BI group 1
c04 BI2 BI group 1
c06 BI3 BI group 1
c08 BI4 BI group 1
c10 BI5 BI group 1
c12 BI6 BI group 1
c14 BI7 BI group 1
c16 BI8 BI group 1
c18 COM1 Common terminal of
group 1
c20 BI9 BI group 2
c22 BI10 BI group 2
c24 BI11 BI group 2
c26 BI12 BI group 2
c28 COM2 Common terminal of
group 2
c30 GPS1
c32 GPS2
Figure 31 Terminal arrangement of BI basic
a02 BI13 BI group 3
module
a04 BI14 BI group 3
a06 BI15 BI group 3
a08 BI16 BI group 3
a10 BI17 BI group 3
a12 BI18 BI group 3
a14 BI19 BI group 3
a16 BI20 BI group 3
a18 COM3 Common terminal of
group 3
a20 BI21 BI group 4
a22 BI22 BI group 4
a24 BI23 BI group 4
a26 BI24 BI group 4
a28 COM4 Common terminal of
group 4
a30 Null
a32 Null

70
Table 15 Description of terminals of BI
extended module

Terminal Definition remark


c02 BI25 BI group 1
c04 BI26 BI group 1
c06 BI27 BI group 1
c08 BI28 BI group 1
c10 BI29 BI group 1
c12 BI30 BI group 1
c14 BI31 BI group 1
c16 BI32 BI group 1
c18 COM1 Common terminal of
group 1
c20 BI33 BI group 2
c22 BI34 BI group 2
c24 BI35 BI group 2

Figure 32 Terminals of the BI extended c26 BI36 BI group 2

module c28 COM2 Common terminal of


group 2
c30 Null
c32 Null
a02 BI37 BI group 3
a04 BI38 BI group 3
a06 BI39 BI group 3
a08 BI40 BI group 3
a10 BI41 BI group 3
a12 BI42 BI group 3
a14 BI43 BI group 3
a16 BI44 BI group 3
a18 COM3 Common terminal of
group 3
a20 BI45 BI group 4
a22 BI46 BI group 4
a24 BI47 BI group 4
a26 BI48 BI group 4
a28 COM4 Common terminal of
group 4
a30 Null
a32 Null

71
Terminals of BO module and BOB module
Table 16 Definition of the BO module
Terminal Definition Remark
2 c02 Contract 1-0 BO group 1
4 c04 Contract 1-1 BO group 1
6
a02 Contract 2-0 BO group 2
8
a04 Contract 2-1 BO group 2
10
12 c06 Contract 3-0 BO group 3
14 c08 Contract 3-1 BO group 3
16 a06 Contract 4-0 BO group 4
18 a08 Contract 4-1 BO group 4
20 c10 Contract 5-0 BO group 5
22
c12 Contract 5-1 BO group 5
24
a10 Contract 6-0 BO group 6
26
28 a12 Contract 6-1 BO group 6
30 c14 Contract 7-0 BO group 7
32 c16 Contract 7-1 BO group 7

Figure 33 Terminal arrangement of DO module a14 Contract 8-0 BO group 8


a16 Contract 8-1 BO group 8
c18 Contract 9-0 BO group 9
c20 Contract 9-1 BO group 9
a18 Contract 10-0 BO group 10
a20 Contract 10-1 BO group 10
c22 Contract 11-0 BO group 11
c24 Contract 11-1 BO group 11
a22 Contract 12-0 BO group 12
a24 Contract 12-1 BO group 12
c26 Contract 13-0 BO group 13
c28 Contract 13-1 BO group 13
a26 Contract 14-0 BO group 14
a28 Contract 14-1 BO group 14
c30 Null
c32 Null
a30 Null
a32 Null

72
Table 17 Definition of the BOB module
Terminal Definition Remark
2 c02 Contract 1-0 BO group 1
4
c04 Contract 1-1 BO group 1
6
8 a02 Contract 2-0 BO group 2

10 a04 Contract 2-1 BO group 2


12 c06 Contract 3-0 BO group 3
14
c08 Contract 3-1 BO group 3
16
18 a06 Contract 4-0 BO group 4
20 a08 Contract 4-1 BO group 4
22 c10 Contract 5-0 BO group 5
24
c12 Contract 5-1 BO group 5
26
28 a10 Contract 6-0 BO group 6
30 a12 Contract 6-1 BO group 6
32 c14 Contract 7-0 BO group 7
Figure 34 Terminals arrangement of BOB c16 Contract 7-1 BO group 7
module a14 Contract 8-0 BO group 8
a16 Contract 8-1 BO group 8
c18 Contract 9-0 BO group 9
c20 Contract 9-1 BO group 9
a18 Contract 10-0 BO group 10
a20 Contract 10-1 BO group 10
c22 Null
c24 Null
a22 Null
a24 Null
c26 Null
c28 Null
a26 Null
a28 Null
c30 Null
c32 Null
a30 Null
a32 Null

73
Terminals of DT module
Table 18 Description of terminals of DT
module

Terminal Analogue Input Remark


c2 DT1+ Channel 1
c4 DT1- Channel 1
c6 DT2+ Channel 2
c8 DT2- Channel 2
c10 DT3+ Channel 3
c12 DT3- Channel 3
c14 DT4+ Channel 4
c16 DT4- Channel 4
c18 DT5+ Channel 5
c20 DT5- Channel 5
c22-c32 Null
a2-a32 Null
Figure 35Terminals arrangement of DT
module

74
Terminals of Power supply module
c08 AUX.DC 24V- output 2

a10 AUX.DC 24V- output 3

c10 AUX.DC 24V- output 4

a12 AUX.DC 24V- output 5

c12 AUX.DC 24V- output 6

a14 Alarm contact A1, for AUX.DC


power input failure

c14 Alarm contact A0, for AUX.DC


power input failure

a16 Alarm contact B1, for AUX.DC


power input failure

c16 Alarm contact B0, for AUX.DC


power input failure

a18 Isolated terminal, not wired

c18 Isolated terminal, not wired

a20 AUX. power input 1, DC +

c20 AUX. power input 2, DC +

a22 AUX. power input 3, DC +

c22 AUX. power input 4, DC +

Figure 36Terminals arrangement of power a24 Isolated terminal, not wired

supply module c24 Isolated terminal, not wired

a26 AUX. power input 1, DC -


Table 19 Definition of terminals of power supply
module c26 AUX. power input 2, DC -

a28 AUX. power input 3, DC -


Terminal Definition
c28 AUX. power input 4, DC -
a02 AUX.DC 24V+ output 1
a30 Isolated terminal, not wired
c02 AUX.DC 24V+ output 2
c30 Isolated terminal, not wired
a04 AUX.DC 24V+ output 3
a32 Ground
c04 AUX.DC 24V+ output 4
c32 Ground
a06 Isolated terminal, not wired

c06 Isolated terminal, not wired

a08 AUX.DC 24V- output 1

75
Technical data
Basic data

Frequency

Item Data
System rated frequency 50Hz or 60Hz

Internal current transformer

Item Data
Rated current Ir 1 or 5A
Nominal current range (0-1.2)×Ir
Accuracy 0.2 level
Power consumption (per phase)
At Ir =1A <0.2VA
At Ir =5A ≤0.8VA

Internal voltage transformer

Item Data
Rated current voltage Vr(ph-ph) 100V
Nominal range 0V to 120V
Accuracy 0.2 level
Power consumption
At Vr =100V ≤0.2VA per phase

Rated Auxiliary voltage

Item Data
Rated auxiliary voltage Vaux 220V DC
110V DC

76
Permission tolerance ±%20 Uaux
Power consumption
Normal operation 19/2’’ case: <25W
19” case: <50W

Binary inputs

Item Data
Input voltage range 110/125 V DC
220/250 V DC
Response time/dropout time Software provides de-bounce time
Power consumption, energized ≤2mA
Independent of operating voltage

Binary outputs

Item Data
Max. system voltage 250V DC/AC
Relay output contacts
Current carrying capacity 5 A continuous
30 A for 0.5s making current
Making capacity 150 W(DC)
1250 VA(AC)
Breaking capacity 250V AC, 30V DC at I=5A

Other output contacts

Current carrying capacity 3 A continuous

Making capacity 30 W(DC)


62.5 VA(AC)
Breaking capacity 250V AC, 30V DC at I=3A

77
Type tests

Insulation test

Item Data
Standards IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Voltage test (100 % test)
All circuits besides auxiliary voltage, 2KV,50Hz,1min
RS485/RS232 and time synchronization IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Auxiliary voltage 3.5 kV DC
IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Communication ports and time synchronization 500V,50Hz,1min
terminals IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Impulse voltage test
all circuits, except communication ports and time 5kV (Ui≥63V) /1kV (Ui<63V)
synchronization IEC 60255-5:2000 class III
GB/T 15145-2001
DL/T 478-2001
Insulation resistance
Insulation resistance >100 MΩ at 500 VDC
IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001

Electromagnetic compatibility tests

Item Data
Standards GB/T 14598.9-2002
identify IEC 60255-22-3:2000, for radiated
electromagnetic field disturbance test
GB/T 14598.10-2007
identify IEC 60255-22-4:2002, for electrical fast

78
transient/burst immunity test
GB/T 14598.13-2008
Modify from IEC 60255-22-1:2007, for 1MHz
burst immunity test
GB/T 14598.14-1998
identify IEC 60255-22-2:1996, for electrostatic
discharge test
GB/T 14598.17-2005
Identify with IEC 60255-22-6:2002, for
Conducted electromagnetic field disturbance
tests
GB/T 14598.18-2007
Identify with IEC 60255-22-5:2002, for surge
immunity test
GB/T 14598.19-2007
Identify with IEC 60255-22-7:2003, for power
frequency immunity test
GB/T 14598.20-2007
Identify with IEC 60255-26:2004, for
electromagnetic compatibility requirements
High-frequency burst disturbance test 2.5 kV (peak value); 1 MHz
test duration 2 s
IEC 60255-22-1, class III
and VDE 0435 Part 303, class III
Electrostatic discharge 8 kV contact discharge
15 kV air gap discharge
both polarities; 150 pF; Ri = 330 Ω
IEC 60255-22-2; class IV
and EN 61000-4-2; class IV
Radio-frequency electromagnetic field disturbance 10V/m, 80 to 1000 MHz
non-modulated IEC 60255-22-3, class III
Radio-frequency electromagnetic field disturbance 10 V/m, 80MHz to 2.7GHz
amplitude-modulated 80%AM; 1 kHz
IEC 61000-4-3, class III
Radio-frequency electromagnetic field disturbance 10 V/m, 900 MHz; repetition rate 200 Hz, on
pulse-modulated duration 50 %
IEC 61000-4-3/ENV 50204, class III
Fast transient disturbance 4KV
IEC 60255-22-4 and IEC 61000-4-4, class IV
High-energy surge voltages (Surge) 2KV
Auxiliary voltage IEC 61000-4-5, class III
radio-frequency line-conducted disturbance, 10 V; 150 kHz to 80 MHz
amplitude-modulated AM 80 %; 1 kHz
IEC 61000-4-6, class III

79
Power frequency magnetic field test 30 A/m; 50 Hz, continuous
300 A/m; 50 Hz, 3 s
0.5 mT, 50 Hz
IEC 61000-4-8, class IV
IEC 60255-6
Oscillatory surge withstand capability test 2.5kV, 1 MHz
ANSI/IEEE C37.90.1
Fast transient surge withstand capability test 4KV
5kHz
ANSI/IEEE C37.90.1
Radiated electromagnetic field disturbance 10 V/m; 25 to 1000 MHz
amplitude and pulse-modulated
ANSI/IEEE C37.90.2
Damped wave 2.5 kV (peak value, polarity alternating)
100 kHz, 1 MHz, 10 and 50 MHz, Ri = 200 Ω
IEC 60694 / IEC 61000-4-12
Radiated emission 30MHz to 1GHz ( IT device may up to 5 GHz)
CISPR11, class A
EN61000-6-4:2005
Conducted emission 0.15MHz to 80MHz
CISPR11, class A
EN61000-6-4:2005

Mechanical tests

Item Data
During operation
Standards IEC 60255-21-1:1988
IEC 60255-21-2
Vibration Sinusoidal
10 to 50 Hz; +/- 0.035 mm amplitude
50 to 150 Hz
IEC 60255-21-1, class 2
IEC 60068-2-6
Shock Semi-sinusoidal
Acceleration 5 g, duration 11 ms; 6 shocks in both
directions of 3 axes
IEC 60255-21-2, class 1
IEC 60068-2-27
During transportation
Standards IEC 60255-21-2
Vibration Sinusoidal

80
5 to 8 Hz: ± 7.5 mm amplitude
8 to 150 Hz; 2 g acceleration
frequency sweep 1 octave/min
20 cycles in 3 perpendicular axes
IEC 60255-21-1, class 2
IEC 60068-2-6
Shock Semi-sinusoidal
Acceleration 15 g, duration 11 ms
6 shocks in both directions of 3 axes
IEC 60255-21-2, Class 1
IEC 60068-2-27
Continuous shock Semi-sinusoidal
Acceleration 10 g, duration 16 ms
2000 shocks in both directions
of 3 axes
IEC 60255-21-2, class 1
IEC 60068-2-29

Environmental tests

Item Data
Temperatures
Type-tested , test Bd, for 16 h -25 °C to +70 °C
IEC 60068-2-1
IEC 60068-2-2
Recommended permanent operating temperature -10 °C to +55°C
IEC 60255-6
(Legibility of display may be impaired above
+55 °C /+131 °F)
Storage and transport temperature limit -25°C~+70°C
Humidity
Permissible humidity 95 % of relative humidity

IED design

Item Data
Case size 4U×19inch/4U×19/2inch
Dimensions See dimension section
Weight ≤ 10kg
Protection level IP20 class I
EN 60529

81
IEC 60529

CE certificate

Item Data
EN 61000-6-2 and EN61000-6-4 (EMC Council
EMC Directive
Directive 2004/108/EC)
Low voltage directive EN 60255-27 (Low-voltage directive 2006/95 EC)

82
Station communication ports

Front communication port

Item Data
Number 1
Connection Isolated, RS232; front panel
9-pin subminiature connector
Communication speed 9600 baud
Max. length of communication cable 15 m

RS485 communication port

Item Data
Number 2
Connection 2-wire connector
Rear port in master module
Max. length of communication cable 1.0 km
IEC 60870-5-103 protocol
Communication speed Factory setting 9600 baud
Min. 1200 baud, Max. 19200 baud

Ethernet communication port

Item Data
Electrical communication port
Number 0~2
Connection RJ45 connector
Rear port in master module
Max. length of communication cable 100m
IEC 61850 protocol
Communication speed 100 Mbit/s
IEC 60870-5-103 protocol
Communication speed 100 Mbit/s
Optical communication port ( optional )
Number 0~2
Connection SC connector
Rear port in master module

83
Optical cable type Multi-mode
Max. length of communication cable 2.0km
IEC 61850 protocol
Communication speed 100 Mbit/s
IEC 60870-5-103 protocol
Communication speed 100 Mbit/s

Time synchronization

Item Data
Mode IRIG-B
Connection 2-wire connector
Rear port in master module
Voltage levels differential input

84
Functions

Analogue measurement range

Item Data
AC voltage 0V~120V
AC current (0~1.2) In
(In—CT rated current)
Frequency 45Hz~55Hz
Temperature -50℃~150℃
DC voltage 0V~5V
DC current 4mA~20mA

Pulse variable level

Item Data
Input voltage DC220V/110V
Pulse width ≥10ms
GPS input 24V

Analogue measurement accuracy

Item Data
AC current/voltage 0.2 level
Power/ electric energy 0.5 level
Temperature error ≤±1℃
DC current/voltage 0.2 level

Sequence of events (SOE) resolution

Item Data
SOE resolution ≤2ms

Response time

Item Data

85
Telesignalization response time <1s
Telemeter response time <2s

86
Ordering
1 2 3 4 5 6 7

*
*
*

*
*
*
*
*
*
*

*
*

*
*
CSI-200EA * * * T P X

1. AC Module
AC Module(8U4I) A
AC Module(6U6I) B
AC Module(4U3I) C
AC Module(8U) E

Number of AC module n

CT:1A 1
CT:5A 5

2. Master Module
New Master W

0 2 0 0 1
2 0 2 0 2
2 0 0 2 2
0 0 2 0 1
0 0 0 2 1
LON LON Ethernet Ethernet
MASTER MMI Electircal Optical 485 Port

3. BI Module
BI with Extended moudule I
BI basic J

Number of BI module n

110V 1
220V 2

4. BO Module
BO O
BOC N
BOB R

Number of BO module n

5. DT Module
DT T

Number of DT module n

Voltage 1
Current 2
6. Power Module
Power P

110V 1
220V 2

7. Case
Code X

19'' 1
19/2'' 2

DC220V AC5A CSI 200EA-A25M20202I12J11O1R1T12P2X1


Starndard Configuration DC220V AC5A CSI 200EA-A25M20202I12J11O1R1T12P2X1
DC110V AC1A CSI 200EA-A21W20202I11J11O1R1T12P1X1
DC110V AC1A CSI 200EA-A21W20202I11J11O1R1T12P1X1

87
CSC-196 Time server
Product Guide

88
Overview

CSC-196 time server is a time can provide accurate time synchronous


synchronization device which is signals to dispatching ends and
developed and produced by Beijing equipments of substation system, such
Sifang Automation Co, Ltd. referring to as the PMU (Phasor Measurement Unit),
Specifications of time synchronization protection, bay control equipment.
system for power system. The device

89
Features
‹ It is strictly designed according to ‹ CSC-196 is modular equipment
Specifications of time which has 19’’ 2U standard
synchronization system for power rack-type case. Input signal
system. Multi-type time receiving modules and time signal
synchronization systems such as output modules can be configured
basic mode, master-slave mode, as required.
and run-standby mode can be
‹ CSC-196 is equipped with display
configured. The working logic and
panel which shows date, time,
technical parameters of the
received signal quality and internal
equipment comply with the
error; there are some LEDs which
specifications. Additional, the
perform time status. There is a
quantities of output signal can be
serial port that provides detailed
freely expended.
operating state information and
‹ The core time-transfer algorithm of failure diagnosis information for all
CSC-196 is based on the patent inputs and outputs for finding fault
200410009685.2 (“Beidou No.1” reasons quickly.
satellite navigation system and GPS
‹ Treatment of leap second
mutual standby time transfer
identification complies with
method and equipment). It can
Specifications of Time
identify and follow the best input
Synchronization System for Power
signal automatically to guarantee
System and IEEE C37.118-2005.
time accuracy of the output signal to
Information about leap second can
be better than 1us, which meets the
be obtained in advance, and
requirement of high precision
forenotice mark of leap second can
time-transfer signals for PMU and
be set to meet requirement of PMU.
other devices to accurate
time-transfer signals.

90
Functions
‹ Multi external time reference signals synchronization signal exporting
such as GPS, Beidou (BD) and automatically when external time
IRIG-B (DC) are provided for reference signal in abnormal. Time
CSC-196. Up to 4 timing reference accuracy under self time keeping
signals are available per equipment. state is better than 0.92us/min
(55us/h).
‹ Many time synchronization signals
such as the time synchronization ‹ It supports time compensation
pulse, IRIG-B code, serial port time function, and can set compensation
message (PPS) and network time parameters of all input and output
message (SNTP) can be exported. signals freely to offset time errors
caused by long distance signal
‹ Many time synchronization signal
transmission, thereby guaranteeing
interfaces such as optical fiber, idle
output signal accuracy of each
contact, TTL, RS-422/485, RS-232
master clock or slave clock to reach
and Ethernet port are available.
±1us.
‹ Both main signal module and
‹ It supports double power source hot
sub-signal module have built-in
standby, all output interfaces are
high-accurate crystal oscillators,
isolated outputs.
which may maintain time

91
Hardware
Module arrangement
Each CSC-196 can be assembled 10 ‹ The other modules are optional; one
modules maximally. Assembly of module sub-signal receiving module can be
should comply with following basic configured, and must be assembled
principles: at position 2; one standby power
supply module can be configured,
‹ The main signal receiving module is
and must be assembled at position
essential, which must be assembled
9; the other modules can be
at position 1 (the leftmost slot in
assembled freely at position
back sight).
2~position 9 with free quantity.
‹ The main power supply module is
The module installation diagram (the
essential, which must be assembled
rear view of the case) is shown below:
at position 10 (the rightmost slot in
back sight).

Figure 37 Rear view of CSC-196

92
Front panel
Refer to Figure 38 for arrangement of the CSC-196 front panel:

Figure 38 front panel of CSC-196

‹ PPS indicator: the pulse per second status of the second punctual time
output indicator. After initialization edge of input time reference signals.
the indicator maintains flashing The Input I corresponds to the
once per second, when importing highest priority input signal, and the
time signal. Input II corresponds to the
secondary high priority input signal
‹ SYNC indicator: shows the
(not the main signal module and the
synchronization status of input and
sub signal module).
output signals.
1) ON: The second punctual time
1) ON: The device is in tracking
edge of input time signal is
lock state, viz. using input time
stable, and keeps
reference signal synchronize
synchronization with output
output time signal;
signal.
2) OFF: The equipment is in
2) Flashing: The second punctual
initialization state or punctuality
time edge of input time signal is
keeping state. The operating
stable, but not keeps
state is abnormal.
synchronization with output
‹ Y, M, D, H, M, and S LEDs: display signal.
local time.
3) OFF: Unidentified second
‹ Alarm indicator: It turns on in case punctual time edge of input
of abnormity of the equipment, and time signal or the second
acts synchronously with the output punctual time edge of input
contact of the main signal receiving time signal is not stable.
module. The alarm indicator keeps
‹ I time quality, II time quality LEDs:
flashing once per 3 seconds in case
show state of time reference signal.
of communication fault between the
“I” corresponds to input signal with
display board and the main signal
the highest priority, while “II”
receiving module.
corresponds to input signal with
‹ Input I, Input II indicators: show secondary priority.

93
exported.
Power supply module
The message type, baud rate and
Power supply module is the power
exported bay of RPM and RPS can be
source of CSC-196. Two kinds of power
set by configuration serial port. In default,
supply modules, DC110V/125V,
RPS output is the second message in
DC220V can be applied. The main
Sifang format, and RPM output is the
power supply module and standby
minute message in Sifang format.
power supply module have same
hardware, but different assembled Idle contact pulse output module
positions.
The module code is K, and the mark on
Main signal receiving module the module is K. This module supports 8
channels of idle contact type time
Three modules are available to receive
synchronization pulse output. Each
time signals:
channel output signal can be configured
‹ GPS signal receiving module as PPS (default), PPM (PPH), IRIG-B
(DC), or programmable pulse.
‹ Multimode optical fiber signal
receiving module Multimode optical fiber output
module
‹ Monomode optical fiber signal
receiving module. Two types of multimode optical fiber
output modules are available, with code
Auxiliary signal receiving module
F on the module.
Except main signal receiving module,
F1 module supports 4 channel optical
one auxiliary signal receiving also can
output, and F2 for 2 channels (Output 3
be applied in CSC-196.
and 4 are not available). Each channel
‹ GPS signal receiving module can output one signal of PPS, PPM
(PPH), IRIG-B (DC) (default),
‹ Optical fiber signal receiving module
programmable pulse, as well as RPS
‹ BD signal receiving module and RPM message.

‹ Monomode optical fiber receiving Differential signal output module


module.
The code of differential signal output
Serial port output module module is C1, with mark C labeled on
the module shutter. C1 module can
Two types of serial port output module
export 8 channels signals in the
are available for the equipment, with the
interface of RS422/485. 8 channels
codes of T1 and T2. Each module
output signal can be set as PPS, PPM,
supplies 8 channels serial port time
IRIG-B (DC) (default), programmable
synchronization message output.
pulse, as well as RPS and RPM
Module T1 has 8 channels RS-232
message.
output and module T2 has 4 channels
RS-232 output and 4 channels RS-422. CODE B FORMAT: comply with
By setting the jumper, 8 channels RPS Specifications of time synchronization
(default) or RPM message can be system for power system; be compatible

94
with IEEE C37.118-2005. Accuracy of time synchronization: better
than 10ms.
Time accuracy of second punctual time
edge: better than 1us. IRIG-B (AC) output module
TTL output module Two types of IRIG-B (AC) output module
are available, with code A1 and A2,
The code of the TTL signal output
respectively.
module is L1, with mark L on the module
shutter. 8 channels output signal can be A1 produces and exports 3 channels
set as PPS, PPM, IRIG-B (DC) (default), signal. A2 is the extended module of A1,
programmable pulse, as well as RPS which can export 8 channels signal. The
and RPM message. IRIG-B (AC) output module supports
hot-plugging.
CODE B FORMAT: comply with
Specifications of time synchronization CODE B FORMAT: comply with
system for power system; be compatible Specifications of time synchronization
with IEEE C37.118-2005. system for power system; be compatible
with IEEE C37.118-2005.
Time accuracy of second punctual time
edge: better than 1us. Accuracy of time synchronization: better
than 20us.
Network time synchronization
module Monomode optical fiber output
module
The code of the network time
synchronization module is N, which The monomode optical fiber output
supports the SNTP protocol (RFC 2030). module supports 2 channels optical
output. Each channel can output one
The module supports two 10/100M
signal of PPS, PPM (PPH), IRIG-B (DC)
self-adaption Ethernet RJ45 interface,
(default), programmable pulse, as well
with physical isolation between Ethernet
as RPS and RPM message.
interfaces.

95
Layout and dimension

Figure 39 2U 19’’ case with rear cover

Table 20 Dimensions of the equipment

Case size A B C D

2U,1/1x19’’ 88 482.6 294 432

Unit: mm

Figure 40 Cut out on the panel

Table 21 Dimension of the cutout for equipment mounting

A B C D E

451 465 76.2 90.2 4-φ7

Unit: mm

96
Equipment terminals
Power supply module (Code D)

Terminal definition:

DC failure: Non-maintained normally


closed contact;

IN- and IN+: Power input. The anode


and cathode are not limited during
connection;

: connect the chassis, to the


shielding earth.

D2

1
DC
Failure
2

IN-
IN+

POWER DC 220V

Figure 41 Terminals arrangement of power


supply modules

97
Main signal receiving module (Code J)
In the figure below, J1 and J6 are GPS
signal receiving modules; J2 and J7 are J6

multimode optical fiber signal receiving


Config serial
modules; J5 and J8 are monomode
optical fiber signal receiving modules.
P+
P-
ANT
A1
A2

GPS Unit

Figure 42 Terminals arrangement of main


signal receiving modules

Note: Accurate crystal oscillators are


configured for J1, J2, and J5. High quality
constant temperature crystal oscillator

98
equipped for J6, J7, J8 to meet requirements only receives 1 channel time reference
of high accuracy. signals.

For module J1 and J6, ANT is connected P+ and P- terminals are testing pulse
to the GPS antenna, with interface of output, with TTL interfaces. By setting
BNC. Each module can receive one jumper on the signal receiving module,
channel reference time signal. signals of PPS input, IRIG-B input, PPS,
PPM, PPH output and IRIG-B output can
For module J2 and J7 with multimode
be transferred to the testing terminal
ST optical fiber interface, maximal 2
output.
channels time reference signal can be
imported to each module. The input A1 and A2 terminals are alarm output
signals include two types: contacts, non-maintained normally
closed, which close when the equipment
1) Time synchronization with IRIG-B
in trouble, and open automatically when
(DC) code: the first channel IRIG-B
trouble is removed. They can work to
synchronization codes can be
drive the external 110V/220V electrical
connected to Input 1; the second
contacts with the panel alarm indicators
channel IRIG-B code can access
NO or OFF synchronously.
Input 2. Hence, 2 channels of input
time reference signals are available Config Serial is the USB serial port for
for each receiving module. configuration information input and
return (Note it is a serial port actually,
2) PPS+ time message: PPS optical
never connect other USB devices),
fiber connects to Input 1, and time
which can connect a computer serial
message optical fiber connects to
port with a debugging cable. Config
Input 2. Since PPS and time
Serial can be used to configure
message combine one channel of
operating parameters of equipments,
time signals, each module only
and interrogate status of the input and
receives one channel of time
output signals of the equipment.
reference signals.
Indicators are equipped for J2 and J5
J5 and J8 module with 1310nm
modules, to show the status of input
monomode SC optical fiber interface
signal directly.

99
Auxiliary signal receiving module (Code JF)
In the following figures:

JF1 is the GPS signal receiving module.


The antenna connects to ANT, with the
interface BNC.

JF2 is the optical fiber signal receiving


module, which has the same input signal
interface with J2 module.

JF4 is BD signal receiving module, with


the antenna interface of TNC (with
thread).

JF5 is the monomode optical fiber


receiving module, which has the same
input signal interface with J5 module.

Figure 43 Terminals arrangement of auxillary


signal receiving modules

JF2

Input1

Input2

Fiber Input Unit

100
Serial port output module (Code T)
Table 22 Terminals definition of module T1

Terminal Definition Remark


1+ TXD1 RS-232
1- GND1 group1
2+ TXD2 RS-232
2- GND2 group2
3+ TXD3 RS-232
3- GND3 group3
4+ TXD4 RS-232
4- GND4 group4
5+ TXD5 RS-232
Figure 44 Terminals arrangement of serial 5- GND5 group5
port output module 6+ TXD6 RS-232
6- GND6 group6
Terminal definition:
7+ TXD7 RS-232
When the output interface is RS-232, the 7- GND7 group7
output terminal “+” is TXD, “-” is GND; 8+ TXD8 RS-232
definition of common PC 9-PIN serial 8- GND8 group8
port: 2-RXD, 5-GND, so connect the
Table 23 Terminals definition of module T2
output terminal “+” to the second pin of
the PC serial port, and “-” to the fifth pin. Terminal Definition Remark
1+ TXD1 RS-232
When the output interface is RS-422, the
1- GND1 group1
output terminals, “+” and “-”, correspond
to the anode and cathode of the 2+ TXD2 RS-232

differential signal respectively. 2- GND2 group2


3+ TXD3 RS-232
T module has two types with the same
3- GND3 group3
terminal numbers but different definition.
4+ TXD4 RS-232
4- GND4 group4
5+ Anode RS-422
5- Cathode group1
6+ Anode RS-422
6- Cathode group2
7+ Anode RS-422
7- Cathode group3
8+ Anode RS-422
8- Cathode group4

101
Idle contact pulse output module (Code K)
Output characteristic: 3) Isolation mode: photoelectric
isolation;
1) Corresponding relationship between
the static idle contact and TTL level 4) Output mode: collector open circuit,
signal is: contact closed and “+” terminal to the collector;
corresponding to high level of TTL,
5) Maximal Vce voltage: 250V DC:
contact open to low level of TTL;
contact jumping from open to closed 6) Allowable Ice operating current:
corresponding to punctual time 20mA.
edge;

2) Time accuracy of second punctual


time edge: better than 3us;

Table 24 Definition of module K 

Terminal Definition Remark


1+ Collector Output 1
1- Emitter
2+ Collector Output 2
2- Emitter
3+ Collector Output 3
3- Emitter
4+ Collector Output 4
4- Emitter
5+ Collector Output 5
Figure 45 Terminals arrangement of idle 5- Emitter
contact type signal output module
6+ Collector Output 6
6- Emitter
7+ Collector Output 7
7- Emitter
8+ Collector Output 8
8- Emitter

102
Multimode optical fiber output module (Code F)
F1 module supports 4 channel optical Output characteristic:
output, and F2 for 2 channels (Output 3
1) The optical port “ON” corresponds
and 4 are not available).
to high voltage level, and “OFF” to
low level.

2) Optical fiber port parameters:


multimode 820nm, optical
power >-17dB.

3) Time accuracy of second punctual


time edge: better than 1us.

Figure 46 Terminals arrangement of the


multimode optical fiber output module

103
Differential signal output module (Code C)
This module includes 8 groups Table 25 Terminal definition of module C
RS422/RS485 differential signal output.
Terminal Definition Remark
1+ Anode Output1
1- Cathode
2+ Anode Output2
2- Cathode
3+ Anode Output3
3- Cathode
4+ Anode Output4
4- Cathode
5+ Anode Output5
5- Cathode
6+ Anode Output6
Figure 47Terminals arrangement of
differential signal output module 6- Cathode
7+ Anode Output7
7- Cathode
8+ Anode Output8
8- Cathode

104
TTL output module (Code L)
8 channels TTL signal outputs are Table 26 Definition of module L
applied on TTL output module. The
Terminal Definition Remark
exported voltage signals can be chosen
by jumper 4 on the module. The diagram 1+ Collector Output 1

of interface is shown below. 1- Emitter


2+ Collector Output 2
2- Emitter
3+ Collector Output 3
3- Emitter
4+ Collector Output 4
4- Emitter
5+ Collector Output 5
5- Emitter
6+ Collector Output 6
Figure 48 interface output of TTL module
6- Emitter
7+ Collector Output 7
7- Emitter
8+ Collector Output 8
8- Emitter

Figure 49 Terminals arrangement of TTL


output module

105
Network time synchronization module (Code N)
Two RJ45 Electrical Ethernet interfaces Table 27 Definition of module N
are supplied by network time
Definition Remark
synchronization module.
1 RJ45 interface1 Physical isolation
2 RJ45 interface2 between
interfaces

Figure 50 Terminals arrangement of network


time synchronization module

106
IRIG-B (AC) output module (Code A)
Table 28 Definition of IRIG-B (AC) output
One A1 module can be configured for
module A1
CSC-196 maximally. A2 modules can be
equipped as an extended IRIG-B(AC) Terminal Definition Remark
output module for extending. B1+ Anode Output1
B1- Cathode
B2+ Anode Output2
B2- Cathode
B3+ Anode Output3
B3- Cathode

Table 29 Definition of IRIG-B (AC) output


module A2

Terminal Definition Remark


1+ Anode Output1
1- Cathode
2+ Anode Output2
2- Cathode
3+ Anode Output3
3- Cathode
4+ Anode Output4
4- Cathode
5+ Anode Output5
5- Cathode
6+ Anode Output6
6- Cathode
7+ Anode Output7
Figure 51 Terminals arrangement of IRIG-B
7- Cathode
(AC) output module
8+ Anode Output8
8- Cathode

107
Monomode optical fiber output module (Code H)
The monomode optical fiber output Table 30 Definition of module N
module supports 2 channels optical
Definition
output.
Output 1 Channel 1 optical output
Output 2 Channel 2 optical output

Figure 52 Terminals arrangement of


Monomode optical fiber output module

108
System architecture
There are many forms of time
synchronization systems, the typical
forms include the single, Master-Multi
Slave mode and Run-Standby mode.

Single configuration

‹ A single time synchronization Figure 53 Structure of single time

system consists of a Master clock synchronization

and signal transmitter for devices


‹ SNTP module is connected to the
and systems receiving time. It is
Ethernet Network through two
possible to equip the Master clock redundant RJ45 ports.
with the interface receive time ‹ Maximum 56 devices can be
reference signals from the upper connected to one Master in single
level of time synchronization configuration, refer to Figure 54.
system.
‹ Bay level equipments receive clock
time by IRIG-B code and if IRIG-B
fails then they can receive the clock
time by the SNTP (Simple Network
Time Protocol).

‹ Equipments in station level receive


the clock time by SNTP (Simple
Network Time Protocol).

‹ In single configurations, receiver


module is connected to the antenna
and sends the clock time to
equipments through the Fiber-Optic
Output module. Refer to Figure 53.

Figure 54 Single Configuration Architecture

Following modules are required for


single configuration:

‹ Master CSC-196
- Main signal receiver module

109
(code J) satellite clock time through antenna
- Signal output module (code C) which is connected to the Main
signal receiver module. Slave
Refer to Figure 55
CSC-196 is connected to Master
CSC-196 with Fiber-optic interface

C
to receive the clock time.
1+ 5+

‹ Maximum 28 Slaves can be


1- 5-
2+ 失电 6+
2- 6-
3+ 7+
3-
4+
IN-
7-
8+
connected to one Master.
4- 8-

RS422/485 Unit
‹ All relays can be connected to Slave
with shielded twisted pair; maximum
56 devices can be connected to one
Figure 55 Single Module Configuration Slave. Refer to Figure 57.

Master-Multi Slave configuration

‹ Master-Multi Slave mode time


synchronization system consists of
one Master clock and Multi Slave
clocks refer to Figure 56. It is
possible to equip the Master clock
with the interface to receive time
reference signals from the upper
level of time synchronization system.

Figure 57 Master-Multi Slave configuration


Architecture

Following modules are required for


Figure 56 Structure of Master-Multi Slave Master –Multi Slave configuration:
Time synchronization
‹ Master CSC-196
‹ It is recommended to apply - Main signal receiver module
Master-Slave configuration for (code J)
connecting relays to CSC-196 in - Multimode Fiber-Optic output
different control rooms. module (code F)
‹ Slave CSC-196
‹ Master CSC-196 receives the
- Main signal receiver module

110
(code J) are connected to both Masters through
- Signal output module (code C) output module (F) which is equipped
with Fiber-Optic receiver ports. Both
Refer to Figure 58. ports of output module in Slave receive,
the clock time from Master-1 and
Master-2 at the same time, but port-1 is
the high priority receiver therefore Slave
receives the clock time through port-1
when the time quality of both Mains is
same.

In healthy status Time Quality of


Master-1 and Master-2 is equal to zero.

Figure 58 Module configuration


If antenna connection fails Time quality
(Tq) changed to 3. In this case Salve
Run-Standby configuration receives the clock time from the Master
with Tq=0.
‹ Run-Standby mode time
synchronization system consists of If the main signal receiver module of
two Master clocks, multi Slave clocks Master-1 fails (J1), Master-1 receives
the clock time through standby signal
and signal transmitters. Refer to
receiver module (JF2) in other words
Figure 59. It is possible to equip the
Master-2 receives time from the
master clock with the interface to antenna, and sends the clock time to
receive time reference signals from Master-1 through Fiber-Optic output
the upper level of time module (F).
synchronization system. Each Slave includes one signal receiver
module (J2) which is equipped with two
fiber receiver ports. Both ports receive
time from Master-1 and Master-2 at the
same time. Port-1 is the high priority
receiver and Port-2 is the second
receiver port.

If Master-1 fails:

• Time quality of Master-1


changed to 3 (Tq=3).
• Slaves will receive time from
Figure 59 Structure of Run-Standby time Master-2 with Tq=0.
synchronization
If the antenna of Master-1 fails:
Master-1 and Master -2 are equipped • Time quality of Master-1
with two receiver modules (J1), which
changed to 3 (Tq=3).
are connected to the antenna, all Slave

111
• Master-1 will receive time clock (code J)
from Master-2 - Signal output module (code C)
• Slaves will receive time from Refer to Figure 61.
Master-2 with Tq=0.

Figure 61 Run-Standby Module


configuration

SNTP Configuration

SNTP is Server-Client based, The


CSC-196 is defined as SNTP (Simple
Figure 60 Run-Standby Configuration Network Time Protocol) server and
Architecture relays and computers are defined as
Client. Receiving the clock time by
Following modules are required for
the Bay level equipments is based on
Run-Standby configuration: two priorities; first priority is IRIG-B and
‹ Master-1 second is SNTP. Bay level equipments
- Main signal receiver module are connected to the Ethernet network;
they can receive the clock time by SNTP
(code J1)
if IRIG-B fails.
- Main signal receiver module
(code JF2) Two IPs can be defined in equipments
- Multimode Fiber-Optic output and computers. SNTP receives the clock
module (code F) time through Main receiver module (J1)
and send it to the network.
‹ Master-2
- Main signal receiver module Two IPs can be defined in computers
(code J1) and equipments for SNTP of Master-1
- Main signal receiver module and Master-2 and IP1 is high priority
(code JF2) over IP2.

- Multimode Fiber-Optic output In healthy status Time Quality of


module (code F) Master-1 and Master-2 is equal to zero
‹ Slave so Tq=0 for Bothe SNTP modules.
- Main signal receiver module If antenna connection fails Time quality

112
(Tq) changed to 3. In this case Port-1 is disconnected, and the
computers receives the clock time from equipment can receive the clock time by
the Master with Tq=0 through SNTP. Port-2.

If Master-1 fails:

‹ Time quality of Master-1 changed to


3 (Tq=3).
‹ Computers will receive time from
Master-2 with Tq=0.

If equipments IRIG-B connection fails:

Equipments can receives the clock time


through Network, the equipment is
connected through two Ethernet ports Figure 62 SNTP time synchronization
with two different IPs, port1 has higher
priority over Port2, if connection of

113
Technical data
Basic data

Frequency

Item Data
System frequency 50Hz or 60Hz

Rated auxiliary voltage

Item Data
Rated value 110V/125V DC
220V DC
Power consumption
In normal condition <35W

Receiver

Item Data
Channels 12 (to follow 12 satellites)
Receiving sensitivity Capture<160dBW
Tracing<163dBW
Capture time Warm start<50s
Cold start<50s
Time accuracy 500ns

Antenna

Item Data
Sensitivity <163dBW
Operating temperature range -40℃~70℃
Length of GPS antenna 150m (without repeater)
Length of Beidou antenna 100m

114
Alarm output

Item Data
Max. system voltage 250V DC/AC
Current carrying capacity 3A continuous
Making capacity at inductive load with L/R>10 ms 30 W(DC)
62.5 VA(AC)
Breaking capacity 250V/3A, for AC
30V/3A, for DC

115
Type tests

Insulation test

Item Data
Standards IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Voltage test (100 % test)
All circuits besides auxiliary voltage and 2KV,50Hz,1min
RS485/RS232 and time synchronization IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Communication ports and time synchronization 500V,50Hz,1min
terminals IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Impulse voltage test
all circuits, except communication ports and time 5kV (Ui≥63V) /1kV (Ui<63V)
synchronization IEC 60255-5:2000 class III
GB/T 15145-2001
DL/T 478-2001
Insulation resistance
Insulation resistance >100 MΩ at 500 VDC
IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001

Electromagnetic compatibility tests

Item Data
Standards GB/T 17626.2-1998
identify IEC 61000-4-2:1995, for electrostatic
discharge immunity test
GB/T 17626.3-1998
identify IEC 61000-4-3:1995, for Radiated,
radio-frequency, electromagnetic field immunity
test
GB/T 17626.4-1998
Identify IEC 61000-4-4:1995, for Electrical fast

116
transient/burst immunity test
GB/T 17626.5-1998
identify IEC 61000-4-5:1995, for surge
immunity test
GB/T 14626.10-1998
Identify with IEC 61000-4-10: 1995, for
Damped oscillatory magnetic field immunity
test
GB/T 17626.9-1998
Identify with IEC 61000-4-9, for pulse magnetic
field immunity test
GB/T 17626.8-1998
Identify with IEC 61000-4-8:1995, for power
frequency magnetic field immunity test
GB/T 17626.12-1998
Identify with IEC 61000-4-12:1995, for
Oscillatory waves immunity test
Electrostatic discharge 8 kV contact discharge
15 kV air gap discharge
both polarities; 150 pF; Ri = 330 Ω
IEC 61000-4-2; class IV
Radiated radio-frequency electromagnetic field 10V/m, 80 to 1000 MHz
disturbance IEC 61000-4-3, class III
Electrical fast transient/burst disturbance 4KV on power ports
2KV on I/O ports
IEC 60255-22-4 and IEC 61000-4-4, class IV
Surge disturbance 4.0kV open-circuit test
IEC 61000-4-5, class IV
Power frequency magnetic field 30 A/m; 50Hz, continuous field
300A/m; 50Hz 1s to 3s
IEC 61000-4-8, class IV
Pulse magnetic field 300A/m field strength
IEC 61000-4-9, class IV
Damped oscillatory magnetic field 30A/m (peak)
2s
IEC 61000-4-10, class IV
Oscillatory waves 2.5 kV (peak value, polarity alternating)
IEC 61000-4-12

Mechanical tests

Item Data

117
During operation
Standards IEC 60255-21-1:1988
IEC 60255-21-2
Vibration Sinusoidal
10 to 50 Hz; +/- 0.035 mm amplitude
50 to 150 Hz
IEC 60255-21-1, class 2
IEC 60068-2-6
Shock Semi-sinusoidal
Acceleration 5 g, duration 11 ms; 6 shocks in both
directions of 3 axes
IEC 60255-21-2, class 1
IEC 60068-2-27
During transportation
Standards IEC 60255-21-2
Vibration Sinusoidal
5 to 8 Hz: ± 7.5 mm amplitude
8 to 150 Hz; 2 g acceleration
frequency sweep 1 octave/min
20 cycles in 3 perpendicular axes
IEC 60255-21-1, class 2
IEC 60068-2-6
Shock Semi-sinusoidal
Acceleration 15 g, duration 11 ms
6 shocks in both directions of 3 axes
IEC 60255-21-2, Class 1
IEC 60068-2-27
Continuous shock Semi-sinusoidal
Acceleration 10 g, duration 16 ms
2000 shocks in both directions
of 3 axes
IEC 60255-21-2, class 1
IEC 60068-2-29

Environmental tests

Item Data
Temperatures
Type-tested , test Bd, for 16 h -25 °C to +70 °C
IEC 60068-2-1
IEC 60068-2-2
Recommended permanent operating temperature -10 °C to +55°C

118
IEC 60255-6
(Legibility of display may be impaired above
+55 °C /+131 °F)
Storage and transport temperature limit -25°C~+70°C
Humidity
Permissible humidity 95 % of relative humidity

Equipment design

Item Data
Case size 2U×19inch
Dimensions See outline and installation dimension
diagram
Protection level IP20 class I
EN 60529
IEC 60529

CE certificate

Item Data
EN 61000-6-2 and EN61000-6-4 (EMC Council
EMC Directive
Directive 2004/108/EC)
Low voltage directive EN 60255-27 (Low-voltage directive 2006/95 EC)

119
Functions

Time synchronization pulse

Item Data
Pulse width 105ms
Pulse types
PPS 1
PPM 0~1
PPH 0~1
Time accuracy of interface
Idle contacts better than 3us
820nm multimode ST optical fiber interface better than 1us
1310nm monomode SC optical fiber interface better than 1us
Differential interface better than 1us

Serial port time message output

Configuration
Message format support standard message format complying with
Specifications of time synchronization of power
system and Sifang message format
Message output time can be configured as output by second, by minute,
or by hour.
Output baud rate can be configured as 1200, 2400, 4800, 9600,
19200bit/s
Interface types RS232, RS422/485, 820nm multimode ST optical
fiber, 1310monomode SC optical fiber
Frame header Aligning with front edge of PPS deviation less than
1ms

IRIG-B output

IRIG-B (DC)
Reference standard Specifications of time synchronization of power
system, complying with IEEE C37.118-2005
Interface types RS422/485, 820nm multimode ST optical fiber,
1310monomode SC optical fiber

120
Time accuracy better than 1us
IRIG-B (AC)
Carrier frequency 1kHz
Frequency jitter ≤1% of carrier frequency
Signal amplitude (peak to peak) 3V~12V, high amplitude; 10V, typical
3:1~6:1, modulation ratio; 3:1, typical
Output impedance 600Ω
Time accuracy of second punctual time point better than 20us
Reference standard Specifications of time synchronization of power
system, complying with IEEE C37.118-2005

SNTP interface output

Item Data
Interface type 10/100M Ethernet RJ45, psychical isolation
Time synchronization accuracy better than 10ms

Output modules configuration

Channels of output signal Data


IRIG-B (AC) module 3, A1
8, A2
Multimode optical fiber output module 4
Monomode optical fiber output module 2
Network time synchronization module 2
Other output modules (idle contact type signal
output module, serial port message output module,
8
differential signal output module, TTL signal output
module, ect.)

Effective transmission distance of signals

Item Data
Multimode optical fiber <2km
RS232 <15m
RS422/485 <150m
Idle contact <150m
Electrical Ethernet interface RJ45 <100m
TTL <10m (not recommended for strong EMI
environment)

121
IRIG-B <1000m
Monomode optical fiber <20km

122
Ordering
Module Code Function Qty. Remark
Power supply module D1 DC 110V If double power supply is required, please
D2 DC 220V configure two power supply module
Main signal receiving module J1 Receive GPS signal 1. Main signal receiving card is necessary, and
J2 Receive multimode optical fiber signal only one can be configured.
J5 Receive monomode optical fiber signal 2. Sub-signal receiving card is optional, and only
J6 Receive GPS signal, with constant temperature crystal oscillator one can be configured.
equipped
J7 Receive multimode optical fiber signal, with constant temperature
crystal oscillator equipped
J8 Receive monomode optical fiber signal, with constant
temperature crystal oscillator equipped
Auxiliary signal receiving module JF1 GPS signal receiving module
JF2 Multimode optical fiber signal receiving module
JF4 BD signal receiving module
JF5 Monomode optical fiber signal receiving module
Idle contact pulse output module K 8 channels of idle contact pulse signal output;
1 PPS, 1PPM, 1PPH, IRIG-B (DC), and programmable pulse can
be set by jumper for each channel
Serial port output module T1 8 channels of RS-232 output;

123
RPS or RPM message can be set by jumper.
T2 4 channels of RS RS-232 output, 4 channels of RS-422;
RPS or RPM message can be set by jumper
Multimode optical fiber output module F1 4 channels of multimode optical fiber signal;
1 PPS, 1PPM, 1PPH, and IRIG-B (DC) can be set by jumper
F2 2 channels of multimode optical fiber signal;
1 PPS, 1PPM, 1PPH, and IRIG-B (DC) can be set by jumper
Network synchronization output module N Supports 2 channels of SNTP network time output Physical isolation between 2 Ethernet ports
IRIG-B(AC) output module A1 Generate and output 3 channels of IRIG-B (AC) signal Only 1 A1 module can be equipped for one
A2 Output 8 channels of IRIG-B (AC) signal equipment

Monomode optical fiber output module H1 Output 2 channels of monomode optical fiber signal;
1 PPS, 1 PPM, 1 PPH, RPS message, RPM message and
IRIG-B (DC) can be set by jumper.
Differential signal output module C1 Output 8 channels of RS422/485 interface signal; C1 module is recommended to replace the
1PPS, 1PPM, 1PPH, IRIG-B (DC), Programmable pulse, previous version of B1, and available since April
RPS message and RPM message can be set by jumper. 2009
TTL signal output module L1 Output 8 channels of TTL interface signals; L1 module is recommended to replace the
1PPS, 1PPM, 1PPH, IRIG-B (DC) and Programmable pulse can previous version of B2, and available since April
be set by jumper. 2009
GPS anent 30m/50m/100m/150m Equal to configuration quantity of J1 and JF1
Standard antenna/with lightning protection
BD anent 30m/50m/100m/ Equal to configuration quantity of JF4

124
CSM-320E Gateway
Product Guide

125
Overview

CSM-320E is a substation automation type network by configuring


information management gateway, corresponding network interface.
covering the following applications:
‹ Protocol gateway. CSM-320EW can
‹ Distributed RTU. CSM-320EW is a work as the communication
multi-channel and multi-protocol converter of RS-232/485 to
telecontrol unit, communicating with LonWorks, and also the converter
dispatching center. Up to 4 logical from LonWorks to Ethernet and
RTU can be configured within one RS-485.
physical channel. Data source
CSM-320EW can be applied in
interface of CSM-320EW can be
substation automation system with
LonWorks, Ethernet and RS-485
different voltage levels, different scales,
serial port.
and different function requirements. The
‹ Network RTU. CSM-320EW can powerful function and flexible
conveniently connect to the configuration makes the CSM-320EW
Ethernet and WAN by Ethernet the automation information management
interfaces, and also extend other equipment for substation.

126
Features
‹ The functions of CSM-320EW can Electrical Ethernet interfaces, and 4
be configured according to optional optical Ethernet interfaces.
requirements conveniently.
‹ CSM-320EW supports dual
CSM-320EW supports multiple
CSC2000 network, including
telecontrol protocol and multiple
LonWorks, serial ports and Ethernet.
independent communication
Two equipments also support dual
channels.
hot backup to improve the reliability.
‹ CSM-320EW is based on real-time
‹ Software of CSM-320EW is
operating system, and supports
designed in module and easy to
multiple-process. Process switching
expend because of its open APIs.
delay meets industrial standard
within mini-seconds. ‹ CSM-320EW provides telnet
console and debug client software.
‹ Abundant physical interfaces. The
Users can access the workstation
equipment can be configured with
via Ethernet.
10 serial ports, 3 USB port, 8

127
Functions
CSM-320EW achieves telecontrol SC1801 protocol;
function, protection incoming function,
8890 protocol;
and outgoing function of
IEC60870-5-103 protocol. CDC-TYPE II protocol;

‹ Categories of standard DL467-92 protocol;


communication interfaces of
Other common telecontrol
CSM-320EW are:
protocols.
Electrical Ethernet (10/100M
‹ Protection protocols supported are:
self-adaption);
IEC60870-5-103 protocol;
USB port;
LFP protocol;
RS232/485;
1994 protocol;
Optical Fiber interface.
MODBUS protocol;
‹ Telecontrol protocols supported are:
SPA protocol;
DL451-91 protocol;
MLINK+ protocol;
IEC 60870-5-101 protocol;
COURIER protocol;
IEC 60870-5-104 protocol;
SC1801 protocol;
DNP3.0 protocol;
Other equipment communication
N4F protocol;
protocols in station.

128
Layout and dimension

Figure 63 2U 19’’ case with rear cover

Table 31 Dimensions of the equipment

Case size A B C D

2U,1/1x19’’ 88 482.6 324.7 432

Unit: mm

Figure 64 Cut out on the panel

Table 32 Dimension of the cutout for equipment mounting

A B C D E

451 464.4 76.2 90.2 4-φ7

Unit: mm

129
Hardware and terminals
Front panel and terminal arrangement

Figure 65Front sight of the panel

Figure 66 Back sight of CSM-320EW

There are indicators, LCD display, characters. Driver of LCD is packed with
navigation keys and four function keys CSM-320EW series software package.
on the front panel. Lights indicate the
Sifang navigation keyboard and function
status of power, 10 serial ports, 8
keys can help to display and modify
Ethernet interfaces and 8 BI of the
some important system information
equipment. LCD of CSM-320EW has
through the LCD.
160×80 pixel, displaying 20×5 English

130
3 Transfer data TXD
CPU unit
4 Data terminal ready DTR
CPU unit adopts N270, with 1.6GHz
5 Ground GND
basic frequency, and 1G RAM. The
6 Data device ready DSR
module includes programmable
7 Request sending RTS
Watchdog, integrates all functions of
industrial control PC, and decreases 8 Clear sending CTS

development cost and period. 9 Bell BELL

Power supply unit 3 to 10 serial ports are in RS232/485


100V~265V DC/AC wide range power mode. Two typical configurations of
unit is supplied in the equipment. The Phoenix terminal definition are shown in
terminals of power supply unit are tables below:
standard Phoenix terminals. The figure Table 35 X1(COM3-COM6) Phoenix terminal
of terminals of power supply unit and the definition
definition are shown below.
Terminal RS232 RS485
1 COM3-GND
2 COM3-D+
3 COM3-D-
4 COM3-RXD
Figure 67 Figure of power supply unit
5 COM3-TXD
terminals
6 COM5-GND
Table 33 Definition of terminals of power
7 COM5-D+
supply unit
8 COM5-D-

Terminal Definition 9 COM5-RXD

1 Ground 10 COM5-TXD

2 Negative input 11 COM4-GND

3 Null 12 COM4-D+

4 Positive input 13 COM4-D-

5 Off power alarm 14 COM4-RXD

6 Off power alarm 15 COM4-TXD


16 COM6-GND
Serial communication unit 17 COM6-D+

Serial port1 and port2 are RS232 (using 18 COM6-D-


standard 9 pin interface). The definition 19 COM6-RXD
of each pin is shown in table below: 20 COM6-TXD

Table 34 Terminal definition of RS232 Table 36 X2(COM7-COM10) Phoenix terminal


definition
1 Data carrier detect DCD
2 Receive data RXD Terminal RS232 RS485

131
1 COM7-GND with a pair of idle contacts for each input
2 COM7-D+ channel. It supports input of common
ground or common 24V DC either.
3 COM7-D-
4 COM7-RXD Terminal of BI/BO unit is 20pin Phoenix
5 COM7-TXD terminal. The definition of the terminals
6 COM9-GND is defined in Table 37.

7 COM9-D+ Table 37 X3 BO/BO terminals Definition


8 COM9-D-
Terminal Definition
9 COM9-RXD
1 BI1
10 COM9-TXD
2 BI3
11 COM8-GND
3 BI_GND
12 COM8-D+
4 BI5
13 COM8-D-
5 BI7
14 COM8-RXD
6 /
15 COM8-TXD
7 BO1_COM
16 COM10-GND
8 BO2_COM
17 COM10-D+
9 BO3_COM
18 COM10-D-
10 BO4_COM
19 COM10-RXD
11 BI2
20 COM10-TXD
12 Bl4
Ethernet interface unit 13 BI_GND
14 BI6
Except the Electrical Ethernet interface
with RJ45 connector, the Optical 15 BI8

Ethernet interfaces can be configured in 16 /


the motherboard. Four optical Ethernet 17 BO1
interfaces with ST connector can be 18 BO2
provided maximally.
19 BO3

Binary input/Binary output unit 20 B04

The BI/BO unit is integrated on the


motherboard. This unit provides 5 output
relays. Each BO channel provides a
separated pair of contacts. The working
coil voltage of relay is 24V. The unit also
provides 8 channels opto-isolated BI,

132
Technical data
Basic data

Frequency

Item Data
System rated frequency 50 Hz or 60Hz

Rated auxiliary voltage

Item Data
Rated value 110V~265V DC/AC
Power consumption
Normal operation >30W

Binary outputs

Item Data
Output voltage ±24V DC
Current carrying capacity 1A continuous

133
Type tests

Insulation test

Item Data
Standards IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Voltage test (100 % test)
All circuits besides auxiliary voltage and 2KV,50Hz,1min
RS485/RS232 and time synchronization IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Auxiliary voltage 3.5 kV DC
IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Communication ports and time synchronization 500V,50Hz,1min
terminals IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001
Impulse voltage test
all circuits, except communication ports and time 5kV (Ui≥63V) /1kV (Ui<63V)
synchronization IEC 60255-5:2000 class III
GB/T 15145-2001
DL/T 478-2001
Insulation resistance
Insulation resistance >100 MΩ at 500 VDC
IEC 60255-5:2000
GB/T 15145-2001
DL/T 478-2001

Electromagnetic compatibility tests

Item Data
Standards GB/T 14598.9-2002
identify IEC 60255-22-3:2000, for radiated
electromagnetic field disturbance test
GB/T 14598.10-2007
identify IEC 60255-22-4:2002, for electrical fast

134
transient/burst immunity test
GB/T 14598.13-2008
Modify from IEC 60255-22-1:2007, for 1MHz
burst immunity test
GB/T 14598.14-1998
identify IEC 60255-22-2:1996, for electrostatic
discharge test
GB/T 14598.17-2005
Identify with IEC 60255-22-6:2002, for
Conducted electromagnetic field disturbance
tests
GB/T 14598.18-2007
Identify with IEC 60255-22-5:2002, for surge
immunity test
GB/T 14598.19-2007
Identify with IEC 60255-22-7:2003, for power
frequency immunity test
GB/T 14598.20-2007
Identify with IEC 60255-26:2004, for
electromagnetic compatibility requirements
High-frequency burst disturbance test 2.5 kV (peak value); 1 MHz
test duration 2 s
IEC 60255-22-1, class III
and VDE 0435 Part 303, class III
Electrostatic discharge 8 kV contact discharge
15 kV air gap discharge
both polarities; 150 pF; Ri = 330 Ω
IEC 60255-22-2; class IV
and EN 61000-4-2; class IV
Radio-frequency electromagnetic field disturbance 10V/m, 80 to 1000 MHz
non-modulated IEC 60255-22-3, class III
Radio-frequency electromagnetic field disturbance 10 V/m, 80MHz to 2.7GHz
amplitude-modulated 80%AM; 1 kHz
IEC 61000-4-3, class III
Radio-frequency electromagnetic field disturbance 10 V/m, 900 MHz; repetition rate 200 Hz, on
pulse-modulated duration 50 %
IEC 61000-4-3/ENV 50204, class III
Fast transient disturbance 4KV
IEC 60255-22-4 and IEC 61000-4-4, class IV
High-energy surge voltages (Surge) 2KV
Auxiliary voltage IEC 61000-4-5, class III
radio-frequency line-conducted disturbance, 10 V; 150 kHz to 80 MHz
amplitude-modulated AM 80 %; 1 kHz
IEC 61000-4-6, class III

135
Power frequency magnetic field test 30 A/m; 50 Hz, continuous
300 A/m; 50 Hz, 3 s
0.5 mT, 50 Hz
IEC 61000-4-8, class IV
IEC 60255-6
Oscillatory surge withstand capability test 2.5kV, 1 MHz
ANSI/IEEE C37.90.1
Fast transient surge withstand capability test 4KV
5kHz
ANSI/IEEE C37.90.1
Radiated electromagnetic field disturbance 10 V/m; 25 to 1000 MHz
amplitude and pulse-modulated
ANSI/IEEE C37.90.2
Damped wave 2.5 kV (peak value, polarity alternating)
100 kHz, 1 MHz, 10 and 50 MHz, Ri = 200 Ω
IEC 60694 / IEC 61000-4-12
Radiated emission 30MHz to 1GHz ( IT device may up to 5 GHz)
CISPR11, class A
EN61000-6-4:2005
Conducted emission 0.15MHz to 80MHz
CISPR11, class A
EN61000-6-4:2005

Mechanical tests

Item Data
During operation
Standards IEC 60255-21-1:1988
IEC 60255-21-2
Vibration Sinusoidal
10 to 50 Hz; +/- 0.035 mm amplitude
50 to 150 Hz
IEC 60255-21-1, class 2
IEC 60068-2-6
Shock Semi-sinusoidal
Acceleration 5 g, duration 11 ms; 6 shocks in both
directions of 3 axes
IEC 60255-21-2, class 1
IEC 60068-2-27
During transportation
Standards IEC 60255-21-2
Vibration Sinusoidal

136
5 to 8 Hz: ± 7.5 mm amplitude
8 to 150 Hz; 2 g acceleration
frequency sweep 1 octave/min
20 cycles in 3 perpendicular axes
IEC 60255-21-1, class 2
IEC 60068-2-6
Shock Semi-sinusoidal
Acceleration 15 g, duration 11 ms
6 shocks in both directions of 3 axes
IEC 60255-21-2, Class 1
IEC 60068-2-27
Continuous shock Semi-sinusoidal
Acceleration 10 g, duration 16 ms
2000 shocks in both directions
of 3 axes
IEC 60255-21-2, class 1
IEC 60068-2-29

Environmental tests

Item Data
Temperatures
Type-tested , test Bd, for 16 h -25 °C to +70 °C
IEC 60068-2-1
IEC 60068-2-2
Recommended permanent operating temperature -25 °C to +65°C
IEC 60255-6
(Legibility of display may be impaired above
+55 °C /+131 °F)
Storage and transport temperature limit -25°C~+70°C
Humidity
Permissible humidity 95 % of relative humidity

Equipment design

Item Data
Case size 2U×19inch
Dimensions See outline and installation dimension
diagram
Weight ≤ 8kg
Protection level IP20 class I

137
EN 60529
IEC 60529

CE certificate

Item Data
EN 61000-6-2 and EN61000-6-4 (EMC Council
EMC Directive
Directive 2004/108/EC)
Low voltage directive EN 60255-27 (Low-voltage directive 2006/95 EC)

138
Station communication ports

RS232 communication port

Item Data
Number 2-10
Connection 9 pin D-type for port1 to port4;
Phoenix terminal for port5 to port6;
Rear port in motherboard
Max. length of communication cable 15m
Communication speed 9600 baud

RS485 communication port

Item Data
Number 0~8
Connection Phoenix terminal
Max. length of communication cable 1.0 km
IEC 60870-5-103 protocol
Communication speed Factory setting 9600 baud
Min. 1200 baud, Max. 19200 baud

Ethernet communication port

Item Data
Electrical communication port
Number 8
Connection RJ45 connector
Max. length of communication cable 100m
IEC 61850 protocol
Communication speed 100 Mbit/s
IEC 60870-5-103 protocol
Communication speed 100 Mbit/s
Optical communication port ( optional )
Number 0~4
Connection Optical/ Electrical converter unit with ST connector
Max. length of communication cable 2.0km
IEC 61850 protocol

139
Communication speed 100 Mbit/s
IEC 60870-5-103 protocol
Communication speed 100 Mbit/s

140
Functions

Measurement capacity

Item Data
Telesignalization No limit
Telemetry No limit
Telecommand No limit
Pulse energy No limit
SOE No limit

Measurement accuracy

Item Data
Current 0.2%
Voltage 0.2%
Power 0.5%
Frequency 0.01Hz

Refresh time

Note: for CDT protocol, in 1200 baud


Item Data
State change ≤1s
Primary telesignalization ≤2s
Secondary telesignalization ≤5s
General telesignalization ≤10s
SOE resolution 1ms
GPS time synchronization accuracy 1ms

Mean Time Between Failures

Item Data
MTBF >20000h
System available factor >99.9%

141
Ordering
CSM-320EW_Fn / X [ Y ] [ /E ]

┃ ┃ ┃ ┃

┃ ┃ ┃ ┗━ Extended configuration number (Null or N)

┃ ┃ ┗━ Extended configuration number, reserved

┃ ┗━━ Typical configuration number, from 1 to 9

┗━━━━ Function, from F1 to F9

Note:The codes in [ ] are optional.

Instruction of Fn is shown in following.

Fn Instruction

F1 Telecontrol

F2 Income
F3 Outgo
F4 Gateway
F5 Income + Gateway
F6 Telecontrol + Outgo
F7 Telecontrol + Income + Outgo + Gateway
F9 Telecontrol + Income + Gateway (CSM-329E)

Definition of X and Y can be found below:

Definition of code X

X Configuration Instruction

6 B1 Typical configuration 1

Typical configuration 1 includes 8 Ethernet interface, 2 DB9 serial


Note
port, and 8 RS232/RS485 port

Definition of E can be shown below.

Definition of code E

E Configuration Instruction

142
E Configuration Instruction

Standard configuration
Can be applied for telecontrol or telecontrol
Null (CPU 1.6G Hz, Memory
+ income function configuration
1G, LCD)

Standard configuration Can be applied for income + outgo function


/N
without LCD configuration

143