SA 07.2 – SA 16.

2
Electrical data multi-turn actuators for open-close duty with 3-phase AC motors
Short-time duty S2 - 30 min, 440 V/60 Hz

Multi-turn actuator Motor

Output Max. Nominal Nominal Max. Starting Overcurr. AUMA power class
speed torque power1) Speed current2) current3) current prot. device for switchgear
Type [rpm] [Nm] Motor type PN [kW] [rpm] IN (A) Imax [A] IA [A] cos ϕ setting [A] Contactor Thyristor
4.8 0.4 0.4 1.1 0.40 0.4 A1 B1
VD0L063-4-0,01 0.01 1,680
6.7 0.4 0.4 1.1 0.40 0.4 A1 B1
9.6 0.4 0.4 1.0 0.50 0.4 A1 B1
VD0L063-4-0,03 0.03 1,680
13 0.4 0.4 1.0 0.50 0.4 A1 B1
19 0.5 0.7 1.9 0.43 0.7 A1 B1
VD0L063-2-0,04 0.04 3,360
26 0.5 0.7 1.9 0.43 0.7 A1 B1
SA 07.2 20
38 0.9 1.0 2.2 0.40 1.0 A1 B1
AD0L063-4-0,07 0.07 1,680
54 0.9 1.0 2.2 0.40 1.0 A1 B1
75 0.8 1.0 3.9 0.55 1.0 A1 B1
AD0L063-2-0,14 0.14 3,360
108 0.8 1.1 3.9 0.55 1.1 A1 B1
150 0.8 1.3 3.9 0.70 1.3 A1 B1
AD0L063-2-0,21 0.21 3,360
216 0.8 1.5 3.9 0.70 1.5 A1 B1
4.8 0.4 0.4 1.1 0.50 0.4 A1 B1
VD0L063-4-0,02 0.02 1,680
6.7 0.4 0.4 1.1 0.50 0.4 A1 B1
9.6 0.5 0.5 1.5 0.45 0.5 A1 B1
VD0L063-4-0,04 0.04 1,680
13 0.5 0.5 1.5 0.45 0.5 A1 B1
19 0.5 0.9 2.7 0.52 0.9 A1 B1
VD0L063-2-0,08 0.08 3,360
26 40 0.5 0.9 2.7 0.52 0.9 A1 B1
SA 07.6
38 1.3 1.6 3.8 0.40 1.6 A1 B1
AD0L063-4-0,14 0.14 1,680
54 1.3 1.6 3.8 0.40 1.6 A1 B1
75 1.2 1.7 6.2 0.53 1.7 A1 B1
AD0L063-2-0,28 0.28 3,360
108 1.2 1.9 6.2 0.53 1.9 A1 B1
150 1.3 2.2 6.2 0.60 2.2 A1 B1
AD0L063-2-0,35 0.35 3,360
216 30 1.3 2.2 6.2 0.60 2.2 A1 B1
4.8 0.4 0.5 1.6 0.40 0.5 A1 B1
VD0L071-4-0,04 0.04 1,680
6.7 0.4 0.5 1.6 0.40 0.5 A1 B1
9.6 0.9 1.0 2.8 0.40 1.0 A1 B1
VD0L071-4-0,08 0.08 1,680
13 0.9 1.1 2.8 0.40 1.1 A1 B1
19 1.1 1.2 4.4 0.52 1.2 A1 B1
VD0L071-2-0,17 0.17 3,360
26 90 1.1 1.4 4.4 0.52 1.4 A1 B1
SA 10.2
38 1.7 2.2 7.9 0.43 2.2 A1 B1
AD0L071-4-0,28 0.28 1,680
54 1.7 2.4 7.9 0.43 2.4 A1 B1
75 2.0 2.7 13 0.56 2.7 A1 B1
AD0L071-2-0,50 0.50 3,360
108 2.0 3.5 13 0.56 3.5 A1 B1
150 2.2 4.1 13 0.67 4.1 A1 B1
AD0L071-2-0,70 0.70 3,360
216 70 2.2 4.4 13 0.67 4.4 A1 B1
4.8 0.4 0.7 2.8 0.60 0.7 A1 B1
VD0L090-4-0,08 0.08 1,680
6.7 0.4 0.8 2.8 0.60 0.8 A1 B1
9.6 1.0 1.5 4.6 0.60 1.5 A1 B1
VD0L090-4-0,18 0.18 1,680
13 1.0 1.6 4.6 0.60 1.6 A1 B1
19 1.0 2.2 7.9 0.68 2.2 A1 B1
VD0L090-2-0,30 0.30 3,360
26 180 1.0 2.5 7.9 0.68 2.5 A1 B1
SA 14.2
38 2.2 3.3 13 0.56 3.3 A1 B1
AD0L090-4-0,50 0.50 1,680
54 2.2 3.8 13 0.56 3.8 A1 B1
75 3.4 6.0 31 0.65 6.0 A2 B2
AD0L090-2-1,00 1.00 3,360
108 3.4 6.5 31 0.65 6.5 A2 B2
150 3.8 8.9 31 0.73 8.8 A2 B2
AD0L090-2-1,30 1.30 3,360
216 140 3.8 8.9 31 0.73 8.8 A2 B2
4.8 0.8 1.2 4.3 0.55 1.2 A1 B1
VD0L090-4-0,14 0.14 1,680
6.7 0.8 1.3 4.3 0.55 1.3 A1 B1
9.6 1.7 2.7 9.3 0.52 2.7 A1 B1
VD0L090-4-0,30 0.30 1,680
13 1.7 3.1 9.3 0.52 3.1 A1 B1
19 2.5 3.9 16 0.61 3.9 A1 B1
VD0L090-2-0,60 0.60 3,360
26 360 2.5 4.1 16 0.61 4.1 A1 B1
SA 14.6
38 3.9 6.5 33 0.60 6.5 A2 B2
AD0L090-4-1,00 1.00 1,680
54 3.9 7.1 33 0.60 7.1 A2 B2
75 6.2 10 60 0.69 10 A2 B3
AD0L090-2-2,00 2.00 3,360
108 6.2 12 60 0.69 12 A2 B3
150 6.5 15 60 0.72 15 A2 B3
AD0L090-2-2,30 2.30 3,360
216 290 6.5 16 60 0.72 16 A2 B3
4.8 1.3 2.5 8.7 0.60 2.5 A1 B1
VD0L112-4-0,30 0.30 1,680
6.7 1.3 2.7 8.7 0.60 2.7 A1 B1
9.6 2.5 4.4 19 0.53 4.4 A1 B2
VD0L112-4-0,60 0.60 1,680
13 2.5 4.9 19 0.53 4.9 A1 B2
19 3.5 6.7 36 0.68 6.7 A2 B2
710 VD0L112-2-1,00 1.00 3,360
26 3.5 7.4 36 0.68 7.4 A2 B2
SA 16.2
38 6.5 11 44 0.65 11 A2 B3
AD0L112-4-2,00 2.00 1,680
54 6.5 13 44 0.65 13 A2 B3
75 9.3 20 98 0.78 20 A2 –
AD0L112-2-3,50 3.50 3,360
108 9.3 23 98 0.78 21 A2 –
150 9.8 25 98 0.81 21 A2 –
570 AD0L112-2-4,00 4.00 3,360
216 9.8 34 98 0.81 21 A2 –
1) – 3) Refer to Notes on Electrical data SA .2/SAR .2 multi-turn actuators with 3-phase AC motors
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y005.450/003/en Issue 1.20 Page 1/2


SA 07.2 – SA 16.2
Electrical data multi-turn actuators for open-close duty with 3-phase AC motors
Short-time duty S2 - 30 min, 440 V/60 Hz

Installation and sizing


Motor data Motor data is approximate. Due to usual manufacturing tolerances, there may be deviations from the values
given.
Motor protection To protect against overheating, thermoswitches or PTC thermistors are embedded in the motor windings.

Actuators without integral actuator controls (AUMA NORM):


Thermoswitches or PTC thermistors have to be considered within the external controls (refer to terminal plan).
Note: Failure to connect thermoswitches or PTC thermistors shall void the warranty for the motor.
Rating of the thermoswitches
AC current DC current
250 V, 50 – 60 Hz 60 V 1.0 A
cos j = 1 2.5 A 42 V 1.2 A
cos j = 0.6 1.6 A 24 V 1.5 A

Actuators with AM or AC integral actuator controls:


Thermal motor protection is already integrated.
Mains voltage, mains frequency Permissible variation of mains voltage: ±10 %
Permissible variation of mains frequency: ±5 %
Switchgear sizing For motor operation, reversing contactors (mechanically, electrically and electronically locked) or thyristors (elec-
tronically locked) can be used.

Actuators without integral actuator controls (AUMA NORM):


Switchgear are supplied by the customer. We recommend specification of switchgear suitable for their rated
operating power/motor power in compliance with the assigned AUMA power class.
Switchgear assignment to AUMA power classes:
AUMA Reversing contactor Reversing contactor
power class Rated operating power acc. to EN Motor power
60947-4-1 according to UL/CSA at
Utilization category AC-3
400 V AC 480 V AC 600 V AC
A1 4.0 kW 5.0 hp 5.0 hp
A2 7.5 kW 10 hp 10 hp
A3 15 kW 20 hp 25 hp
A4 30 kW 60 hp 60 hp
A5 55 kW 75 hp 100 hp
A6 75 kW 100 hp 125 hp

AUMA Thyristor
power class Rated operating current acc. to
EN 60947-4-2
Utilization category AC-53a
400 V AC
B1 6A
B2 8.5 A
B3 16 A

Actuators with AM or AC integral actuator controls:


Required switchgear in power classes A1 – A3 or B1 – B3 are already integrated in AM or AC actuator controls.
For switchgear of power classes A4 – A6, a control box is additionally required.
For actuators with AM integral actuator controls and installed switchgear in AUMA power class A3, an optional
thermal overcurrent protection device cannot be directly integrated within the AM. A control box is additionally
required. However, AC actuator controls can be used instead of AM actuator controls. When opting for AC
actuator controls, the additional control box can be omitted.

Notes on Electrical data SA .2/SAR .2 multi-turn actuators with 3-phase AC motors


1) Nominal power PN Mechanical power output at motor shaft at run torque of multi-turn actuator (corresponds to approx. 35 % of
maximum torque).
The consumed electrical power can be calculated using the following formula:
P = U x I x cos ϕ x √3
2) Nominal current IN Current at run torque at approx. 35 % of maximum torque
3) Max. current Imax Current at maximum torque

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.