Grounding Sets - Complete Assemblies
Grounding Sets - Complete Assemblies
Grounding Sets - Complete Assemblies
Ground Set
Storage Bag
Cat. No. HL5993
GROUNDING
HI-LINE UTILITY SUPPLY CO.
Phone: 800-323-6606 Fax: 847-488-1285 www.hilineco.com 123
Grounding
Cat. No. Application Wgt. *For 25kV or small 35kV
Elastimold interface
C600-0729 15kV 4 lb
T600-2131* 25kV/35kV 6 lb **Cooper(RTE) large interface
C600-1927** 35kV 8 lb
Hi-Line's highly skilled and trained staff has supplied over a half million
custom grounds and jumpers to the utility industry over the last forty
years.
Grounds Testing
When was the last time your grounds Best Practices for Testing: Grounds & Jumpers
and jumpers were tested? After Every 1 Year If Damage
Job Suspected
Hi-Line offers repair, cleaning, testing, and certification pro- Grounds Optional Recommended Required
grams to meet individual customer requirements. Collect all Jumpers Optional Recommended Required
your used and potentially dangersome grounds and jumpers
and have Hi-Line's NAIL Accredited facility refurbish to like Cat. No. HLRTP1 - Grounds Proof Test
new condition. Cat. No. HLRT-(length) - Retest & Clean
GROUNDING
HI-LINE UTILITY SUPPLY CO.
Phone: 800-323-6606 Fax: 847-488-1285 www.hilineco.com 125
Grounding
Yellow Cable Jacket: Thermoplastic Elastomer (TPE) Clear Cable Jacket: Clear polyvinyl chloride (PVC)
This superior quality grounding cable is furnished with 30 ga. (class K) ASTM Class B flexible soft drawn
electrolytic copper. The extra fine strands allow for greater flexibility and handling ease. A water resistant
safety insulator separates the outer sheath.
COPPER FERRULES
Burndy Die Burndy Die
Cable Cat. No Description
(Section A) (Section B)
#2 C600-2606 Unshrouded - Threaded U165 ---
1/0 C600-2607 Unshrouded - Threaded U165 ---
A
2/0 C600-2608 Unshrouded - Threaded U165 ---
4/0 C600-2609 Unshrouded - Threaded U166 ---
#2 C600-2614 Unshrouded - Pressure Type U165 ---
1/0 C600-2615 Unshrouded - Pressure Type U165 ---
B
2/0 C600-2616 Unshrouded - Pressure Type U165 ---
4/0 C600-2617 Unshrouded - Pressure Type U166 ---
#2 C600-2622 Shrouded - Threaded U165 U166
1/0 C600-2623 Shrouded - Threaded U165 U168
C
2/0 C600-2624 Shrouded - Threaded U165 U-L
4/0 C600-2625 Shrouded - Threaded U166 U-L
1/0 T600-2713 Shrouded - Short Threads U165 U168
D
4/0 T600-2714 Shrouded - Short Threads U249 U-L
A B C
#2 C600-2630 Shrouded - Pressure Type U165 U166
1/0 C600-2631 Shrouded - Pressure Type U165 U168
E
2/0 C600-2632 Shrouded - Pressure Type U165 U-L
4/0 C600-2633 Shrouded - Pressure Type U166 U-L
#2 13100 Tin Plated Copper U166 ---
Unshrouded Threaded with Flat
1/0 13101 Tin Plated Copper U166 ---
F Unshrouded Threaded with Flat
2/0 13102 Tin Plated Copper U166 ---
Unshrouded Threaded with Flat
4/0 13103 Tin Plated Copper U168 ---
Unshrouded Threaded with Flat D E F
GROUNDING
HI-LINE UTILITY SUPPLY CO.
126 Phone: 800-323-6606 Fax: 847-488-1285 www.hilineco.com
Grounding
T600-0466 C600-1754 C600-1743 G3605-1 G3367-2 12282
Cat. No. T600-0466 C600-1754 C600-1743 G3605-1 G3367-2 12282
Clamp Range .162"-.814" .128"-.998" .162"-1.5" .162"-2" .232"-2.5" .398"-6.625"
Material Bronze Aluminum Aluminum Aluminum Aluminum Aluminum
Drilled for Tapped for Tapped for Pressure Pressure
Terminal Threaded Threaded Threaded Pressure Type Type Type
Ferrule Ferrule Ferrule
Jaws Smooth Smooth Smooth Smooth Smooth Serrated
Electrical Ratings
Continuous Current 250 350 400 400 400 400
(AMPS)
Fault Current - 15 Cycles 21,000 27,000 43,000 43,000 43,000 54,000
(AMPS)
Fault Current-30 Cycles 15,000 20,000 30,000 30,000 30,000 39,000
(AMPS)
Mechanical Ratings
Torque (in -lb.) 200 250 250 250 250 250
750 kcmil 1000 kcmil
477 kcmil Str. Cu. Cu. 2.5” O.D. 6.625” O.D.
Main Line Range - Max ACSR 636 kcmil 2” O.D. Bus
1590 kcmil Bus Bus
(.814) ACSR ACSR (1.50)
(.998)
#6 Sol. Cu. #8 Sol. Cu. #6 Sol. Cu. #6 Sol. Cu. #4 Str. Cu. 1/O Str.
Main Line Range - Min (.162) (.128) (.162) (.162) (.232) (.398)
1/0 Grd. 2/0 Grd. 4/0 Grd. 4/0 Grd. 4/0 Grd.
Jumper Range - Max 4/0 Grd. Cable
Cable Cable Cable Cable Cable
#2 Grd. #2 Grd. #2 Grd. #2 Grd. 1/0 Grd.
Jumper Range - Min #2 Grd. Cable
Cable Cable Cable Cable Cable
Weight 1.5 lb. 1 lb. 1.5 lb. 1.75 lb. 2-3/8 lb. 5.5 lb.
Type I Type I Type I Type I Type I Type 1
ASTM Designation Class A Class A Class A Class A Class A Class A
Grade 2 Grade 3 Grade 5 Grade 5 Grade 5 Grade 6
GROUNDING CLAMPS
Grounding
21030 1853 4369 4345
21074 C600-1732
21953
All Angle Ground
Clamp
SUPPORT STUDS
These support studs INSULATED HANGER
can be installed in place Cat. No. S1600-7
of the restraining strap The Insulated hanger serves as
Cat. No.
immediately below the a convenient parking stand while
G3627
pressure terminal. The stud linemen are installing Jumper or
serves as a parking stand Cat. No. Grounding Clamps on lines up to
for a second clamp. G3626 34.5kV. The bronze double stud fitting
is 1/2” x 3 1/2” on each side.
T600-1737
• For phase-to-phase grounding with wood, steel LOCK OUT CARD HOLDER
and concrete poles and tower angles Cat. No. 5505
• 5" aluminum alloy bar for C clamps or duckbill Card holder with
• Adjustable wheel binder and 36" chain two position snap loop.
• Hook style for attachment to tower angles Transparent on one side.
Cat. No. Description
10.5" x 6.5"
T600-1549 Pole Mount Cluster Bar TAGGING DEVICE
T600-1737 Tower Mount Cluster Bar
Cat. No. TD - Orange Salcor
Cat. No. 1000 - Yellow Poly
CLUSTER SUPPORT - 1 TERMINAL For tagging open disconnect
Cat. No. C600-0152 switches. 7.25"
• Hangs grounding
sets on the pole WARNING MARKER
to facilitate lifting
clamps one at a time Cat. No. 1632-GR-3VS
to the conductors Warning marker with reflective
• Accepts plain striping for night time visibility.
ferrules on the #2 to 4/0 grounding cable Hook & Loop attachment with
• Copper bar length is 11" snap-tight closure for extra security
GROUNDING
HI-LINE UTILITY SUPPLY CO.
Phone: 800-323-6606 Fax: 847-488-1285 www.hilineco.com 131
Grounding
Cat. No. GRS-17 Cat. No. HLSR20
Heavy duty steel grounding reel with easy cable Manual storage reel with cable guide holds
pay-out and spring rewind. Cable capacity is 75’ of 85’ of 2/0 ground cable.
#2, 75’ of 1/0, and 65’ of 2/O. Rated to 43kA for 30
cycles, but the size and spring pull force of the reel
limits use to 2/0 cable and smaller. Maximum fault
rating of 2/0 cable is 27kA.
Grounding
rollable, reversible, and
easy to clean. Anti-skid is
Anti-Skid Mat
best choice for snow or rain
conditions. Cat. No. Size Color/Material Wgt
6610-NS 58” x 58” Black/Hypalon-Marine Fabric 5 lb.
6615-NS 58” x 120” Black/Hypalon-Marine Fabric 10 lb.
6620-NS 120” x 120” Black/Hypalon-Marine Fabric 20 lb.
6610-NS
"Equipotential Zone"
Temporary protective grounds shall be placed at such locations and
arranged in such a manner as to prevent each employee from being
exposed to hazardous differences in electrical potential.
GROUNDING
HI-LINE UTILITY SUPPLY CO.
134 Phone: 800-323-6606 Fax: 847-488-1285 www.hilineco.com