Checklist for alarm messages
General:
When the installation is operational, the engine management system DIANE will not only control the
engine but will also perform engine-failure management. The engine-failure management system checks
all relevant system variables and will issue a warning or switch off the installation if certain set values are
exceeded or underrun.
The error messages can be called up in the DIANE alarm management system.
Turn off motor according to technical instruction no. 1100-0105 and secure against unauthorized
restart.
It is forbidden simply to reset a failure and then start the engine again!
Resetting a failure:
Turn the operation mode selector switch to STOP.
Press the Quit key on the extra panel (under the screen unit - first key from the left).
Procedure:
The alarm management MESSAGE WINDOW will display the failure number. The relevant entry
should be displayed in the selection window (dotted lines). Use the screen buttons (∧∨) to move the
selection window one line up or down.
3
2
1 2
4 5 6 7 8 9 10 11 12
Function keys:
„▼“: With the F2 key it is possible to page down line by line.
„▲“: With the F3 key it is possible to page up line by line.
„▼“: With the F4 key it is possible to page down page by page.
„▲“: With the F5 key it is possible to page up page by page.
„⇊“: With the F6 key it is possible to page to the end of the list.
„⇈“: With the F7 key it is possible to page to the beginning of the list.
GER: With the F8 key it is possible to change the text from the national language into German.
XYZ: With the F9 key it is possible to change the text from German into the respective national
language.
Return: With the function key F10 it is possible to change the last display picture.
Display fields:
Cause: This column contains a list of possible causes for the relevant failure.
Remedy: This column displays a list of the remedial measures for the cause concerned.
Table of contents
- OF MOTOR
There is a defect as e.g. min. or max. remove indicated cause remove ---
oil level. loose contact or wire breakage, or
The current loop (safety loop) is open replace defective monit. device.
- OF AGGREGATE
e.g. min. gas pressure closed current remove cause or complain at ---
loop not released trader;remove loose contact or wire
breakage, or replace defect
monitoring device
- OF THE UNIT
e.g. min. gas pressure closed current check which auxiliary operation is not ---
loop not released running, e.g. HW-circulation pump or
throughflow indicator and machine
room vent flap open, gas warning
installation etc.
40 MOTOR DOES NOT REACH FULL LOAD (while maintaining the guaranteed pollutant
emissions)
combustion air ratio not okay, motor correct leanox adjustment at DIANE ---
too lean (NOx value too low)
- MOTOR SHAKES (quick load fluctuations or great current and voltage fluctuations with
little change of motor output)
faulty ignition check ignition system see maintenance
- GENERATOR MOTOR ESCALATES (great current and voltage fluctuations at only little
change in motor output)inger ve
misfires (motor adjusted too lean) check and adjust with pollutant ---
measuring device check, adjust
- GENERATOR MOTOR ESCALATES (great current and voltage fluctuations at only little
change in motor output)
voltage controller at generator not adjust or repair description -
okay check cables generator
cos phi controller not okay check that connector is firmly located
bad connection in circuit (cables)
- MOTOR ARCHIEVES NOT STABLE CONDITION (output swings slowly up and down)
Non-optimal setting of Leanox-control optimise the controller parameters at ---
parameters constant power setpoint
Check control rods (ball heads worn /
sluggish)
Check gas pressure
Check power control
Check gas-quality fluctuations (landfill
gas, possibly sewage gas)
60 Motor knocking
combustion air ratio not okay check, correct adjustment if Schematic diagram
necessary
- TURBOCHARGER VIBRATING
turbine shovels (compactor shovels) replace wheel or turboloader ---
defective (unbalanced)
1097 COMMS FAILURE RPS (CONTROL SYSTEM) - DISPLAY UNIT (USER INTERFACE)
profibus cable faulty Correct wiring ---
Profibus switch settings wrong Correct switch position
Plant control profibus card failure Switch on 24V power supply,
Check program,
Replace card